Universal IV - Level Measurement System

16

2.5  Calibration / Configuration via Display / Keypad (Continued)

"Fct 3.03 
Input value in PF  
(INPT #) 
"

Value in PF

Enter the capacitance value in pF

"Fct 3.04  
Output value in water 
cut%   
(OUT #)"

Value in % water

Enter the cut value associate with the 
capacitance in pF and point index.  Repeat 
FCT 3.02 to FCT 3.04 until all points are 
entered in the strapping table

"Fct 4.00 
Output   
(OUTPUT)"

Configure the output from the unit including 
LRV, URV, damping and fixed output

"Fct 4.01 
Lower  Range Value   
(LRV)"

0.0 (Default)

Enter the lower range value in % water 
equivalent to 4mA output

"Fct 4.02 
Upper  Range Value   
(URV)"

80.0 (Default)

Enter the upper range value in % water 
equivalent to 20mA output

"Fct 4.03 
Damping in Seconds 
(DAMPING)"

0.0 (Default)

Enter damping in seconds to delay and filter 
(software RC filter) the output in case of rapid 
water cut variations

"Fct 4.04 
4mA Trim   
(TRIM 4)"

4.00 (Default)

Use this menu to calibrate the 4 mA output 
which is not common practice.  Requires 
calibrated meter to measure actual current 
output

"Fct 4.05 
20mA Trim   
(TRIM 20)"

20.00 (Default)

Use this menu to calibrate the 20 mA output 
which is not common practice.  Requires 
calibrated meter to measure actual current 
output

"Fct 4.06 
Fixed Output  
(LOCK mA)"

0.00 (Default)

Use this menu to fix the output to a certain 
mA value regardless of the measurement.  
Enter the value in mA.  The output will stay at 
this value until exiting the menu of if display 
times out in approx. 30 seconds

"Fct 4.07 
Device ID  
(POLL)"

0 (Default)

Enter the device ID to be used on the HART 
loop. Each device on the loop must have a 
unique device ID.  Change only for multi-drop 
configuration

"Fct 5.00 
Display (DISPLAY)"

Setup the parameter(s) to be displayed on the 
unit during operation

"Fct 5.01 
Toggle the display 
(TOGGLE?)"

NO (Default)

Toggle between enabled parameters.  YES or 
NO

"Fct 5.02 
Water Cut (H2O)"

ENABLE (Default)

Enable or disable water cut measurement 
display

"Fct 5.03 
Capacitance (CAP)"

DISABLE (Default)

Enable or disable capacitance measurement 
in pF

"Fct 5.04 
Calculated current (4--20)"

DISABLE (Default)

Enable or disable the calculated current output

"Fct 6.00 
Service (SERVICE)"

Use this menu for troubleshooting and service

Содержание Drexelbrook Universal IV

Страница 1: ...ssistance Call 1 800 527 6297 Outside North America 215 674 1234 For the A Leader in Level Measurement Universal IV Cut Monitor Model Transmitters 2 Wire RF Admittance Capacitance Level Measurement Sy...

Страница 2: ...Keith Valley Road Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook info ametek com Website www drexelbro...

Страница 3: ...ption 1 1 2 Unpacking 1 1 3 Safety Information 1 1 4 Commissioning Start Up Checklist 2 1 5 Installation 3 1 6 Mounting The Electronic Unit 5 1 7 Wiring the Electronic Unit 8 1 8 Wiring The Sensing El...

Страница 4: ...TANT NOTICE This quick start guide provides basic guidelines for the Drexelbrook Universal IV Cut Monitor Refer to the Universal IV CM Model Installation and Operation Manual for more detailed instruc...

Страница 5: ...to the factory 1 3 Safety Information Installation start up and service should only be performed by personnel trained in explosive atmosphere installations Substitution of components may impair intrin...

Страница 6: ...espond with the application Ex d applications Have you connected the equipotential bonding system correctly Ex i applicatons Are you using intrinsic barrier within the correct parameters Did you insta...

Страница 7: ...down is preferred but not essential Gas bubbles must be excluded from the active area by maintaining pressure if necessary a degasser upstream as bubbles decrease system accuracy Do not take sensing...

Страница 8: ...Universal IV Level Measurement System 4 1 5 Installation Continued Installation in a Pipe 8 inches or larger Installation in a Pipe 18 inches or larger Figure 1 1 Recommended Installation...

Страница 9: ...cation free from vibration corrosives and any mechanical damage Rated temperatures for mounting mount the UIV CM in a reasonably accessible location with ambient temperatures between 40 F and 167 F 40...

Страница 10: ...Universal IV Level Measurement System 6 1 6 Mounting the Electronic Unit Continued Integral System Mounting Figure 1 3 Integral Mounting Dimensions...

Страница 11: ...Quick Start Guide 7 1 6 Mounting the Electronic Unit Continued Remote System Mounting SENSING ELEMENT DEPENDENT Figure 1 4 Remote Mounting Dimensions...

Страница 12: ...elded twisted pair cables recommended Integral units are pre wired to the sensing element at the factory See Figure 2 5 See Figure 2 6 for wiring connections to the remote unit The cable from the sens...

Страница 13: ...ensing element are shown in Figure 2 6 Do not connect the cable to the sensing element until after the sensing element has been installed in the vessel and the housing has been secured Figure 1 6 Univ...

Страница 14: ...Universal IV Level Measurement System 10 1 8 Wiring the Sensing Element Continued Remote System Sensing Element Wiring Figure 1 7 Universal IV Wiring Connections Remote Mounting...

Страница 15: ...data from transmitter and displays on screen Write to Transmitter F5 button sends new or edited configuration data to transmitter Real Time View F4 button displays real time values of water capacity l...

Страница 16: ...being taken After determining actual water percentage close Real Time View and open Calibration Screen by clicking on the Cut Monitor Calibration button Enter water reading recorded at the time of sam...

Страница 17: ...eduction in span is greater than 20 30 of range better accuracy can be achieved by changing the input output curve to a lower range To re range the instrument it is necessary to select a different inp...

Страница 18: ...Service 800 527 6297 6 5 4 3 2 1 r e b m u N l a i r e S O M E D T L D I g a T Scratch Pad DEMO CALIBRATION Software Version 6 0 4 n o i t i s o P e g n a R c e s 0 e m i T g n i p m a D s t n i o p d...

Страница 19: ...in Light Oil LIGHT D 0 to 50 water in Light Oil LIGHT E 0 to 1 water in Heavy Oil HEAVY F 0 to 5 water in Heavy Oil HEAVY G 0 to 10 water in Heavy Oil HEAVY H 0 to 30 water in Heavy Oil HEAVY I 0 to 5...

Страница 20: ...calibrated meter to measure actual current output Fct 4 05 20mA Trim TRIM 20 20 00 Default Use this menu to calibrate the 20 mA output which is not common practice Requires calibrated meter to measur...

Страница 21: ...SET until power is cycled Fct 6 02 Pad Capcitor in PF PAD CAP 30 0 Default Enter the value of an external capacitor that must be connected to the unit Padding capacitors are used to reduce the sensing...

Страница 22: ...s Substitution of Components May Impair Intrinsic Safety 3 1 3 Device Description The Universal IV is a Continuous Level Measurement System Measurements are displayed via remote communications or an i...

Страница 23: ...e is a good seal around the cable Are the cable glands suitably certified per the application and the hazardous area parameters 6 Do not use the earth terminal in the wiring compartment use the equipo...

Страница 24: ...ed Locations with connections to a 700 Series sensor that is Intrinsically Safe for Class I II Ill Groups A G and Class I Zone 1 Hazardous Classified Locations 3 3 2 FM Canada Approvals Install per 42...

Страница 25: ...d ia IIB T4 40 C Tamb 75 C IP66 For models U 104 0 II 2 1 D Ex tb ia IIIC T90 C 40 C Tamb 75 C IP66 For models U 10 0 700 Universal IV Sensors II 1 G Ex ia IIC T2 T5 Ga 40 C Tamb 75 C II 1 D Ex ia II...

Страница 26: ...d Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook info ametek com Website www drexelbrook com An ISO 90...

Отзывы: