Universal IV - Level Measurement System
16
2.5 Calibration / Configuration via Display / Keypad (Continued)
"Fct 3.03
Input value in PF
(INPT #)
"
Value in PF
Enter the capacitance value in pF
"Fct 3.04
Output value in water
cut%
(OUT #)"
Value in % water
Enter the cut value associate with the
capacitance in pF and point index. Repeat
FCT 3.02 to FCT 3.04 until all points are
entered in the strapping table
"Fct 4.00
Output
(OUTPUT)"
Configure the output from the unit including
LRV, URV, damping and fixed output
"Fct 4.01
Lower Range Value
(LRV)"
0.0 (Default)
Enter the lower range value in % water
equivalent to 4mA output
"Fct 4.02
Upper Range Value
(URV)"
80.0 (Default)
Enter the upper range value in % water
equivalent to 20mA output
"Fct 4.03
Damping in Seconds
(DAMPING)"
0.0 (Default)
Enter damping in seconds to delay and filter
(software RC filter) the output in case of rapid
water cut variations
"Fct 4.04
4mA Trim
(TRIM 4)"
4.00 (Default)
Use this menu to calibrate the 4 mA output
which is not common practice. Requires
calibrated meter to measure actual current
output
"Fct 4.05
20mA Trim
(TRIM 20)"
20.00 (Default)
Use this menu to calibrate the 20 mA output
which is not common practice. Requires
calibrated meter to measure actual current
output
"Fct 4.06
Fixed Output
(LOCK mA)"
0.00 (Default)
Use this menu to fix the output to a certain
mA value regardless of the measurement.
Enter the value in mA. The output will stay at
this value until exiting the menu of if display
times out in approx. 30 seconds
"Fct 4.07
Device ID
(POLL)"
0 (Default)
Enter the device ID to be used on the HART
loop. Each device on the loop must have a
unique device ID. Change only for multi-drop
configuration
"Fct 5.00
Display (DISPLAY)"
Setup the parameter(s) to be displayed on the
unit during operation
"Fct 5.01
Toggle the display
(TOGGLE?)"
NO (Default)
Toggle between enabled parameters. YES or
NO
"Fct 5.02
Water Cut (H2O)"
ENABLE (Default)
Enable or disable water cut measurement
display
"Fct 5.03
Capacitance (CAP)"
DISABLE (Default)
Enable or disable capacitance measurement
in pF
"Fct 5.04
Calculated current (4--20)"
DISABLE (Default)
Enable or disable the calculated current output
"Fct 6.00
Service (SERVICE)"
Use this menu for troubleshooting and service