INSTALLATION
2
12
DR6300 SERIES
www.drexelbrook.com
DR6300-LM ATEX, EDO 2-13-118, Issue 1
Equipment category 2 G:
Ex ia and Ex d[ia] devices - with the PROFIBUS PA or FOUNDATION
™
Fieldbus output options
Equipment category 1 D: Ex iaD devices only
Equipment category 1/2 D or 2 D: Ex iaD and Ex tD[iaD] devices
Temperature
class
Ambient temperature
Flange temperature
Drop and horn antennas
Drop and horn antennas with
the distance piece
[
°
C]
[
°
F]
[
°
C]
[
°
F]
[
°
C]
[
°
F]
T6
-40
…
+50
-40
…
+122
-40
…
+50
-40
…
+122
-50
…
+60
1
-58
…
+140
1
-40
…
+42
-40
…
+107
-40
…
+45
-40
…
+113
-50
…
+85
1
-58
…
+185
1
T5
-40
…
+72
-40
…
+161
-40
…
+72
-40
…
+161
-50
…
+75
1
-58
…
+167
1
-40
…
+62
-40
…
+143
-40
…
+66
-40
…
+151
-50
…
+100
1
-58
…
+212
1
T4
2
-40
…
+80
-40
…
+176
-40
…
+80
-40
…
+176
-50
…
+85
1
-58
…
+185
1
-40
…
+74
-40
…
+165
-40
…
+79
-40
…
+174
-50
…
+100
1
-58
…
+212
1
-40
…
+70
-40
…
+158
-40
…
+74
-40
…
+165
-50
…
+110
1
-58
…
+230
1
-40
…
+60
-40
…
+140
-40
…
+68
-40
…
+154
-50
…
+135
1
-58
…
+275
1
T3
3
-40
…
+54
-40
…
+129
-40
…
+64
-40
…
+147
-50
…
+150
1
-58
…
+302
1
-
-
-40
…
+57
-40
…
+134
-50
…
+180
1
-58
…
+356
1
-
-
-40
…
+52
-40
…
+125
-50
…
+200
1
-58
…
+392
1
1
Min. -50
°
C / -58
°
F, if an EPDM gasket is used. Min. -20
°
C / -4
°
F, if a Kalrez
®
6375 gasket is used. Min. -40
°
C / -40
°
F, if an FKM/FPM
gasket is used. Min. -30
°
C / -22
°
F, if a Metaglas
®
feedthrough is used. Min. -50
°
C / -58
°
F, if a PEI feedthrough is used.
2
Max. flange temperature is +100
°
C / +212
°
F, if the PP Drop antenna is used
3
Do not use this temperature class for the PP Drop antenna. Max. flange temperature is +150
°
C / +302
°
F, if the PTFE Drop antenna is
used.
Ambient temperature
Flange temperature
[
°
C]
[
°
F]
[
°
C]
[
°
F]
-40
…
+85
-40
…
+185
-50
…
+200
1
-58
…
+392
1
1
Max. flange temperature is 100
°
C / 212
°
F, if PP Drop antenna used. Max. flange temperature is 150
°
C / 302
°
F, if the PTFE Drop or the
Hygienic antenna is used. Min. -50
°
C / -58
°
F, if an EPDM gasket is used. Min. -20
°
C / -4
°
F, if a Kalrez
®
6375 gasket is used. Min. -40
°
C /
-40
°
F, if an FKM/FPM gasket is used. Min. -30
°
C / -22
°
F, if a Metaglas
®
feedthrough is used. Min. -50
°
C / -58
°
F, if a PEI feedthrough
is used.