48
IRIG-B
The IRIG-B signal connects to a standard BNC connector on DMS-3K CPU. Modulated or
Demodulated mode must be selected via DIP switches, which are accessible from SW1 on the CPU.
Caution: Disconnect power from the system before removing the CPU Module
Figure 2–11, IRIG-B Modulated/Demodulated Selection
IRIG-B Format
Switch SW1
Modulated
Demodulated
1
ON*
OFF
2
ON*
OFF
3
OFF*
ON
4
OFF*
ON