COIL ROTATION
If the water connection layout makes it necessary to turn the
coil around, first remove the cabinet and then proceed as
follows.
a) Disconnect the electrical connections from the terminal
board.
b) Remove the temperature probe from the coil.
c) Remove the drip tray fixing screws and remove the tray.
d) Remove the coil fixing screws and remove the coil.
e) Remove the push-out covers from the right hand side.
f) Turn the coil around and re-fit it using the fixing screws
removed previously.
g) Re-fit the drip tray using the screws removed previously.
All drip trays are designed for condensate draining from
either side.
h) Move the polythene condensate drain plug to the left
hand side.
i) Fit the plastic plugs provided in the water ports on the left
hand side from which the water connections were remo-
ved previously.
l) Move the terminal board and the earthing point to the left
hand side.
m)Pull out the electric motor cable from the right hand side.
n) Remove the rectangular push-out cover from the left hand
side panel and close the hole with adhesive tape.
o) Recover the cable gland and fit it in the left hand side.
p) Move the electric motor cable to the left hand side, threa-
ding it through the cable gland and arranging it so that it
easily reaches the connector on the side panel.
q) Move the control panel from the right to the left of the
coil head, and use the plastic cover you removed to close
the hole.
r) Fit the adhesive cable clamps provided to the fan coil
head, arranging them to keep the cable close to the inner
surface of the head.
s) Unwind the switch cable for the length necessary to reach
the terminal board on the left hand panel.
t) Press the switch cable into the cable clamps.
u) Reconnect the control panel electrical connections to the
terminal board.
GB
ELECTRICAL CONNECTIONS
WARNING: always check that the electricity supply to the
unit has been disconnected before carrying out any opera-
tions.
In the specific case of electrical connections, the following
must be checked:
- Measurement of the isolation resistance on the electrical
system.
- Testing of the continuity of protection conductors.
Electric circuits are connected to mains voltage of 230V;
make sure that all components correspond to this voltage.
CONNECTING CABLES
Use H05V-K or N07V-K cables with insulation 300/500 V
in conduit or raceway. All cables exterior to the fancoil
must be protected in this way.
Only use power cables with a minimum cross section of
1.5mm
2
.
Position cable lengths not protected by the conduit or
raceway in such a way as to ensure that they are not subject
to stress, twisting or external agents.
When making connections, always refer to the wiring dia-
grams supplied with the unit and shown in this document.
To protect fan coils against short circuits, always fit the
power cable to the units with 2A 250V (IG) thermo-
magnetic all-pole switches with a minimum contact gap of
3 mm.
Each control panel controls a single fancoil.
Warning: probes have double insulation due to the presence of
230V AC.
Содержание Omnia HL PC
Страница 2: ......
Страница 15: ...15 SCHEMI DI MONTAGGIO L N OMNIA HL PC HL PCM I...
Страница 27: ...L N 27 INSTALLATION DIAGRAMS OMNIA HL PC HL PCM GB...
Страница 39: ...L N 39 SCH MAS DE MONTAGE OMNIA HL PC HL PCM F...
Страница 51: ...L N 51 EINBAUPL NE OMNIA HL PC HL PCM D...
Страница 63: ...L N 63 ESQUEMAS DE MONTAJE OMNIA HL PC HL PCM E...
Страница 67: ......