5
098-0003 Rev. B
2.0 SYSTEM INSTALLATION
CAUTION:
Local plumbing and electrical codes must be observed
.
2.1
SRO
1.
The electrical source for the S100 controller must be a single phase, 3-conductor
receptacle with a ground fault interrupter (GFI) at 120V, 20amp, and 60Hz. The
proper polarity and ground integrity must be initially checked and thereafter
maintained. Failure to do so may result in electrical shock to the operator. The SRO
must only be plugged directly into a GFI receptacle. It must not be plugged into an
extension cord or power strip that could cause low amperage.
To avoid electrical shock, always unplug and disconnect the SRO system
power source before opening the back of the electrical controller.
2.
Mount the SRO (level) on a wall near a drain that can handle the reject water flow. (It
is recommended to secure the frame to the wall with anchoring bolts.)
3.
SRO is equipped with sediment and chlorine removal.
4.
Connect the feed water supply to the inlet
1/2” fitting on the SRO prefilter.
5.
The feed water supply requires a minimum dynamic pressure of 20 psi and maximum
of 50 psi (at the pre filter gauge). Feed water supply tubing should be large enough to
provide the required feed flow rate for the SRO. Connect the water supply from your
isolation valve to the INLET of the pre filter.
6.
Connect the REJECT WATER to an open drain, maintaining a 2” air gap.
7.
Connect a product line to the fitting marked PRODUCT WATER.
8.
Remove and discard the 5 micron sediment filter (part number 20-1051) that has been
factory installed and Install the supplied 10 micron Carbon Block filter cartridge (part
number 20-5101).
9.
Always maintain water flow and pressure to avoid damage to the RO pump.
CAUTION: To ensure proper assembly, all tubing extensions MUST be fully inserted
into fitting bodies, to the tube stops.
10.
Plug the power cord into a dedicated 120-volt, 20-amp GFI receptacle.