![AmeriWater CW130 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/ameriwater/cw130-series/cw130-series_operation-and-installation-manual_3043936009.webp)
6
6/07
1.6 Pipe Connections
Recommended pipe size for all pipe connections are noted in schedule.
(Ref: Drawing CW)
Connecting pipe should be of materials compatible in construction to filter manifold.
Dielectric fittings are highly recommended if dissimilar metals are used.
For pipe runs exceeding 20 feet from filter system consult AmeriWater for pipe size
recommendations.
The companion full-face flange to the suction side of the filter pump is to be provided by end-
user or contractor.
Basket or Y strainer (with gauges before and after strainer) is recommended ahead of filter
pump.
Ref: Drawing CWT for typical installation.
Properly secure all pipe runs with M & F clamps (or similar). Pipe movement may cause filter
and / or pipe damage.
Supply and Return Lines
NOTE: Isolation valves are recommended convenient to filter.
a. Connect influent (supply) line from pre-selected point in cooling system to
suction side of filter pump.
NOTE: A foot valve / check valve should be installed on suction side of self-priming
pump to prevent loss of pump prime.
b. Connect effluent (return) line from the outlet connection to the pre-selected point in the cooling
system (downstream of inlet connection).
NOTE: Filter return must be connected to a point in the cooling system where cooling system
pressure is equal to or less than pressure to filter pump suction.
NOTE: Filter supply and return lines should be connected to the cooling system where they
are in an area of 'common' flow.
Содержание CW130 Series
Страница 1: ...Rev 6 07 High Efficiency Sand Filters CW130 Series ...
Страница 21: ...18 6 07 2 4 Startup Data Sheet ...
Страница 22: ...19 6 07 2 5 Filter Log Sheet ...
Страница 31: ...28 6 07 ...
Страница 36: ...33 CP Control Panel Enclosure with Labeled Components ...
Страница 37: ...34 ...
Страница 38: ......
Страница 39: ...36 TBIO Input output strips on Terminal block labeled to indicate connection points ...
Страница 40: ...37 CPIO Input output strips on PLC labeled to indicate connection points ...
Страница 42: ......
Страница 44: ...41 6 System Component Cut Sheets ...
Страница 45: ...Model MCC INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS INSTRUCTION MANUAL IM060R04 ...