3
6/07
1.4 Filter System Assembly
Placing, Arranging, and Leveling Vessel(s)
Skid mounted systems:
a) Place system skid in desired location and level skid.
NOTE: If system was shipped assembled, the pipe assembly may be loose at flanges to
avoid flex damage. Some systems will be shipped broken down to avoid damage from flexing.
b) Arrange vessels with valves front.
c) Multi vessel systems are labeled and should be arranged in order from left to
right. (Use lower pipe manifold as guide for spacing and leveling vessels.)
CAUTION!
WARNING!
CAUTION!
PERSONAL INJURY MAY RESULT!
READ FOLLOWING CAREFULLY BEFORE PROCEEDING!
TIPPING HAZARD may exist on empty, freestanding, multi-vessel systems with upper
manifold attached.
READ THE FOLLOWING PARAGRAPH BEFORE PROCEEDING!
With vessels properly aligned and leveled and with lower manifold and pipe stands
attached, add base (stone) media. (See media addition sec 6 in this manual).
This will counter balance the system and reduce tipping hazard.
NOTE: Be sure that vessels are properly placed and aligned before adding base
media. Vessels will be difficult to move with media added.
Содержание CW130 Series
Страница 1: ...Rev 6 07 High Efficiency Sand Filters CW130 Series ...
Страница 21: ...18 6 07 2 4 Startup Data Sheet ...
Страница 22: ...19 6 07 2 5 Filter Log Sheet ...
Страница 31: ...28 6 07 ...
Страница 36: ...33 CP Control Panel Enclosure with Labeled Components ...
Страница 37: ...34 ...
Страница 38: ......
Страница 39: ...36 TBIO Input output strips on Terminal block labeled to indicate connection points ...
Страница 40: ...37 CPIO Input output strips on PLC labeled to indicate connection points ...
Страница 42: ......
Страница 44: ...41 6 System Component Cut Sheets ...
Страница 45: ...Model MCC INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS INSTRUCTION MANUAL IM060R04 ...