background image

Ameritron AL-572 

Instruction Manual 

15 

For 120 volt operation, the wiring between the fuse box and the amplifier ac outlet must be 
number 14 gauge (or larger) in order to supply the current required (16 A) without a significant 
drop in the line voltage.  The 120 volt outlet should be fused for 20 amperes. 

 

G

ROUNDING

 

Connect a good RF and dc ground to the ground post on the rear panel of the amplifier.  Use the 
heaviest and shortest connection possible. The best materials to use for ground connections are 
(in order of effectiveness) smooth wide copper flashing, copper tubing, or solid copper wire. 

Never

 

use braided or woven conductors unless the lead needs to be flexed. 

 Braided or woven 

conductors offer a much higher impedance to lightning and RF than an equivalent solid 
conductors.  

Water pipes, metal heating ducts, metal fences and other large metallic masses offer convenient 
RF grounds. If a water pipe ground is used, inspect all the pipe connections to be sure that no 
plastic or rubber connections are insulating the pipes. Insulated pipe connections will interrupt 
the electrical continuity in the water supply system. Install a jumper around any insulated pipe 
connections you find.  Use heavy copper wire or flashing with stainless hose or pipe clamps for 
the jumpers. 

The following tips will help prevent lightning damage and RF grounding problems: 

1. Avoid using braided or woven conductors, they have very high resistance for RF and 

lightning. Remember that RF and lightning flows along the surface of conductors, almost no 
current flows in the center of the conductor. The lowest RF resistance occurs with large 
surface area, smooth conductors.  

2. Avoid routing a single small gauge conductor along the various pieces of equipment (or to 

connect multiple ground sources). Instead, use multiple ground leads that connect to a single 
wide buss at the operating position.  Keep all ground leads as short and wide as possible. 

3.  Buried radials provide much better lightning and RF ground connections than ground rods do, 

although both are needed for safety. 

4. Avoid sharp bends in ground leads. When changing the direction of a ground lead use a 

gradual radius turn. 

5. Avoid second story operation.  A good ground is much easier to obtain on the first floor or in 

the basement of a structure. 

6.  Air-core choke baluns should be used on all coaxial feedlines.  The feedlines should be coiled 

into several 4" to 6" diameter turns

 before

 they

 

enter the building.  Either directly bury the 

feedlines a few inches deep in the ground for a minimum distance of ten feet or ground the 
shields to a separate earth ground on the antenna side of the choke. 

 

 

 

Содержание AL-572

Страница 1: ...velope Power vs Average Power 6 Circuit Descriptions 7 ALC 7 Dynamic Bias 7 Wattmeter Circuit 8 Power Supply 8 Filament Supply 8 Plate HV Supply 8 Meters 8 Current Meter plate and grid 8 Multimeter 9...

Страница 2: ...ear panel 19 Driving Power 20 Tube and Component Life 20 Tuning 21 Tuning Procedure 22 ALC SET control 24 Additional SSB Notes 25 AM Amplitude Modulation Operation 25 Audio Distortion 25 FM Frequency...

Страница 3: ...adjustable true ALC circuit and automatic bias switching to make this the best featured and most reliable 572B amplifier available The AL 572 and AL 572Y are factory wired for 120 volt 50 60 Hz ac lin...

Страница 4: ...s holes Firmly press the tubes into the socket Do NOT twist or force the tubes into their socket Install the anode connector on the tube s anode terminal Install the fuses and fuse caps on the back of...

Страница 5: ...Ameritron AL 572 Instruction Manual 3...

Страница 6: ...anges The AL 572 has two illuminated cross needle panel meters The left meter provides a continuous reading of grid and plate currents The right meter reads peak RF power output on one scale and Plate...

Страница 7: ...0 watts nominal 1 2 hour PEP two tone test 1000 watts 1 2 hour continuous carrier RTTY not rated contact factory for specification Frequency Coverage 1 8 to 21 MHz amateur bands Export models include...

Страница 8: ...timeter Peak forward power continuously The second scale switches between peak reflected power and SWR ALC threshold ALC output voltage and high voltage Current meter Plate and grid current simultaneo...

Страница 9: ...de the amplifier operate at high enough temperatures to cause burns 7 NEVER make any unauthorized component or circuit modifications to this product The only acceptable source for modifications is Ame...

Страница 10: ...begin on page 17 DYNAMIC BIAS Conventional bias circuits force high power linear amplifiers to dissipate hundreds of watts during low or no signal periods This creates needless heat since virtually no...

Страница 11: ...a heavy duty 21 pound transformer Filtering is accomplished by a bank of high quality computer grade capacitors totaling 26 mFd Large 50k ohm 7 watt bleeders are used for safety and superior voltage...

Страница 12: ...ale FWD This scale is calibrated in 100 watt steps up to 2 kW The right hand scale of this meter provides four metering functions that are selected by the MULTIMETER switch These functions include the...

Страница 13: ...emperatures normally do NOT produce anode color The graphite anode is coated or mixed with a getter material that de gasses the tube This material is activated by normal operating anode temperatures T...

Страница 14: ...eding 1100 mA will not cause loss of emission or shorten the amateur service life of the tubes in this amplifier The application of filament voltage causes thermal stresses from rapid and uneven tempe...

Страница 15: ...ly For service or written correspondence use the following address AMERITRON 116 Willow Rd Starkville MS 39759 Telephone 662 323 8211 FAX 662 323 6551 Note Service history has clearly shown that most...

Страница 16: ...ortant to avoid restricting the air inlet 2 The exhaust airflow is over 30 CFM Do not assist the exhaust airflow with cabinet mounted fans 3 The most efficient way to improve airflow is to pressurize...

Страница 17: ...ashing with stainless hose or pipe clamps for the jumpers The following tips will help prevent lightning damage and RF grounding problems 1 Avoid using braided or woven conductors they have very high...

Страница 18: ...ansformer of the AL 572 has fourteen different voltages available on the primary and is rated at full power on frequencies of 50 and 60 Hz The jumper connections chart below indicates the proper place...

Страница 19: ...he rear panel provides 12 Vdc at 200 mA maximum to operate external dial lamps or accessories such as the ATR 15 Antenna Tuner 6 Connect the ALC jack to the ALC input of the exciter with a shielded ca...

Страница 20: ...control is rotated beyond the point of maximum output The linearity however will increase The proper position for this control is slightly clockwise from the setting that produces maximum output with...

Страница 21: ...output power however The fullness of ALC action is indicated by the meter reading in the multimeter ALC position More exciter audio gain or power output will drive the amplifier s ALC circuit harder...

Страница 22: ...ill automatically self adjust to the value required by the exciter If the ALC voltage requirements are low and or if the ALC attack time is slow the ALC may cause the output power to pump at a very sl...

Страница 23: ...er if this condition occurs Non linear operation splatter and excessive grid current will occur if the LOAD setting is too low Excessive plate current is the proper indicator that the drive power limi...

Страница 24: ...ltage and arcing in the tank circuit or excessive grid current Repeated tripping of the grid overload circuit or intermittent arcing probably indicates the LOAD control is adjusted too low The goal of...

Страница 25: ...proper voltage outlet 3 Place the main power switch in the ON position The meter lamps should light and the blower should start Read the 3500 volt scale on the multimeter It should indicate 2800 volts...

Страница 26: ...utput to the exciter s ALC input Steps 10b and 11b should be used if the exciter and amplifier ALC lines are not connected Note Step 10 requires the simultaneous observation of the plate current Ip an...

Страница 27: ...is adjusted until the multimeter ALC position indicates the desired ALC level This setting should normally allow around 120 mA grid current on a steady carrier or whistle Note If the ALC is not conne...

Страница 28: ...nt For the cleanest audio the microphone gain can be reduced until the ALC meter just flickers AM AMPLITUDE MODULATION OPERATION The efficiency of any conventional linear amplifier must remain below h...

Страница 29: ...than vacuum relay systems they will allow over 90 of the available receive time to be used at 60 WPM Ameritron highly recommends using the external QSK 5 switch This stand alone PIN diode switch can...

Страница 30: ...equipment failure or personal injury The cover should be removed and a low value 40 to 500 ohm two watt or larger resistor should be secured to the chassis The other end of this resistor should be con...

Страница 31: ...200 2122 C133 2200 uF 25 V 203 0207 C134 220 uF 25 V 203 0565 R101 4 7k mox 1 W 103 1747 R102 470k 1 4 W 100 0188 R103 104 121 10k 1 4 W 100 4100 R105 10 ohm 1 2 W 100 0727 R106 1 5 ohm 2 W 1 103 340...

Страница 32: ...20 30 330 9 75T 405 1097 220 208 5175 15 17 270 8 75T 405 1087 180 208 5396 10 12 100 3 75T 405 1037 C217 68 pF METER BOARD 50 0057 3 Designator Description Ameritron PN D301 1N34A 300 0346 C301 302 4...

Страница 33: ...5 6 V zener 301 710 IC501 LM 358 dual op amp 311 0724 Q501 NPN transistor MJF3055 305 3055 Q502 PNP transistor 2N3906 307 0722 Q503 504 NPN transistor 2N3904 305 0645 R501 503 10k 1 2 W 101 0643 R504...

Страница 34: ...2 50 0080 3 Metering Board Assembly 50 0572 3 50 0080 4 RF Tank Board Assembly only parts L1 L2 50 0572 4 50 0080 5 Timer Overload Board Assembly optional See page 31 50 0572 5 L1 L Coil 10 13165 L2 L...

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Отзывы: