therMal eXpansIon

As water is heated, it expands (thermal expansion). In a closed system 

the volume of water will grow when it is heated. As the volume of water 

grows there will be a corresponding increase in water pressure due to 

thermal expansion. Thermal expansion can cause premature tank failure 

(leakage). This type of failure is not covered under the limited warranty. 

Thermal  expansion  can  also  cause  intermittent Temperature-Pressure 

Relief  Valve  operation:  water  discharged  from  valve  due  to  excessive 

pressure build up. This condition is not covered under the limited warranty. 

The Temperature-Pressure Relief Valve is not intended for constant relief 

of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 

all  closed  systems  to  control  the  harmful  effects  of  thermal 

expansion. Contact a local plumbing service agency to have a 

thermal expansion tank installed.

note: to protect against untimely corrosion of hot and cold water 

fittings, it is strongly recommended that di-electric unions or couplings 

be installed on this water heater when connected to copper pipe.

All gas piping must comply with local codes and ordinances or with the 

National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper and brass tubing 

and fittings (except tin lined copper tubing) should not be used.

fIGure 10.

Figure 10 shows typical attachment of  water piping to the water heater. 

The water heater is equipped with 3/4 inch NPT water connections.

note:

 

If using copper tubing, solder tubing to an adapter before 

attaching the adapter to the water heater connections.  do not solder 

the water lines directly to the water heater connections.  It will harm 

the dip tube and damage the tank.
t & p valve and pipe Insulation

1.  Locate the temperature and pressure relief valve on the water heater 

(also known as a T&P relief valve).  See Figure 11.

2.  Locate the slit running the length of the T&P relief valve insulation.

3.  Spread the slit open and fit the insulation over the T&P relief valve.  See 

Figure 11.  Apply gentle pressure to the insulation to ensure that it is fully 

seated on the T&P Relief Valve. Once seated, secure the insulation with 

duct tape, electrical tape, or equivalent.  IMPORTANT:  The insulation 

and tape must not block the discharge opening or hinder access to the 

manual relief lever (Figure 11).  Ensure a discharge pipe is installed into 

the T&P valve discharge opening per the instructions in this manual.

4.  Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.

5.  Locate the slit running the length of a section of pipe insulation.

6.  Spread the slit open and slip the insulation over the cold water (inlet) 

pipe. Apply gentle pressure along the length of the insulation to ensure 

that it is fully seated around the pipe. Also, ensure that the base of 

the insulation is flush with the water heater.  Once seated, secure the 

insulation with duct tape, electrical tape, or equivalent.  

7.  Repeat steps 5 and 6 for the hot water (outlet) pipe.

8.  Add additional sections of pipe insulation as needed.

fIGure 11.

teMperature-pressure relIef valve

Explosion Hazard

Temperature-Pressure Relief Valve

must  comply  with  ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized Temperature-Pressure 

Relief Valve must be installed in 

opening provided.
Can  result  in  overheating  and

excessive  tank  pressure.
Can cause serious injury or death.

This water heater is provided with a properly rated/sized and certified 

combination Temperature-Pressure  Relief  Valve  (T&P  valve)  by  the 

manufacturer. The valve is certified by a nationally recognized testing 

laboratory  that  maintains  periodic  inspection  of  production  of  listed 

equipment of materials as meeting the requirements for Relief Valves 

for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code 

requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local 

codes, but not less than a combination Temperature-Pressure Relief 

Valve rated/sized and certified as indicated in the above paragraph. 

The new valve must be marked with a maximum set pressure not to 

exceed the marked hydrostatic working pressure of the water heater 

(150 psi = 1,035 kPa) and a discharge capacity not less than the water 

heater Btu/hr or kW input rate as shown on the water heater’s model 

rating plate.
Note: In addition to the factory installed Temperature-Pressure Relief 

Valve on the water heater, each remote storage tank that may be 

installed and piped to a water heating appliance must also have its 

own properly sized, rated and approved Temperature-Pressure Relief 

Valve installed. Call the toll free technical support phone number listed 

on the back cover of this manual for technical assistance in sizing a 

Temperature-Pressure Relief Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure 

Relief Valve must not be removed from its designated opening nor 

plugged. The Temperature-Pressure Relief Valve must be installed 

directly into the fitting of the water heater designed for the relief 

valve. Install discharge piping so that any discharge will exit the 

pipe  within  6  inches  (15.2  cm)  above  an  adequate  floor  drain, 

or  external  to  the  building.  In  cold  climates  it  is  recommended 

that it be terminated at an adequate drain inside the building. Be 

certain that no contact is made with any live electrical part. The 

Содержание vG6250t76nv

Страница 1: ... WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER Low Lead Content www americanwaterheater com American Water Heater Johnson City TN 37605 POWER VENTED GAS MODELS W HOT SURFACE IGNITION NOT FOR USE IN MANUFACTUR...

Страница 2: ...y alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California...

Страница 3: ...3 GENERAL SAFETY INFORMATION ...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk ...

Страница 5: ...ction Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code NFPA 70 4 If after reading this manual you have any questions or do not understand any portion of the instructions call the local gas utility or the manufacturer whose name appears on the rating pla...

Страница 6: ... feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructions Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation...

Страница 7: ...tting 4 Places Shown DD Plastic Top EE On Off Switch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shuttoff Valve H Ground Joint Union J Dirt Leg K Outer Door L Union M Inlet Water Shuttoff Valve N Cold Water Inlet O Inlet Dip Tube P Temperature Pressure Relief Valve HH Bushing II Nipple JJ Co...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1A ...

Страница 9: ... time to burn relationship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use then special precautions must be taken In addition to using lowest possible temperature setting that satisfies demand of application a Mixing Valve sho...

Страница 10: ...stalled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shuttoff device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to...

Страница 11: ...orine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater The results can be hazardous and also cause product failure INSULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary w...

Страница 12: ...e size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air should be provided to replace the exhausted air When an exhaust fan is installed in the same space with a water heater sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized openin...

Страница 13: ... a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 18 27 for complete venting installation instructions FIGURE 9 The confined space should be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing with...

Страница 14: ...ode requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILURE...

Страница 15: ...on 6 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure that the base of the insulation is flush with the water heater Once seated secure the insulation with duct tape electrical tape or equivalent 7 Repeat steps 5 and 6 for the hot water outlet pipe 8 Add...

Страница 16: ...excessive temperatures and pressures in the storage tank The T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Thermal Expansion on page 14 and 15 If you do not understand these instructions or have any questions regarding the Temperature Pre...

Страница 17: ...closing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13 FIGURE 12 GAS PIPING WITH FLEXIBLE CONNECTOR FIGURE 13 GAS PIPING WITH ALL BLACK IRON ...

Страница 18: ... PVC parts should be assembled with ASTM D 2564 grade cement Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may be rotated to a different orientation as needed for the specific installation requirements Note the rotational orientation of each part by marking ...

Страница 19: ... L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm M Clearance under veranda porch deck or balcony 12 inches 30 cm G Clearance to inside corner 18 inches 45 cm In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is lo...

Страница 20: ...or signs of sagging or other stresses in joints as a result of misalignment of any components in system If any of these conditions are found they must be corrected in accordance with venting instructions in this manual before completing installation and putting water heater into service NOTE A For water heaters in locations with high ambient temperatures above 100 F it is recommended that CPVC or ...

Страница 21: ... tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer harness is not fact...

Страница 22: ...line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLATIONS FIGURE 18 Cut a length of PVC pipe about 3 5 inches 8 9 cm longer than wall thickness at the opening Glue vent terminal to this section of pipe Slide the wall plate over the pipe to stop agains...

Страница 23: ...highest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with the additional vent pipe when calculating maximum equivalent feet of venting INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof Th...

Страница 24: ... cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4 Make sure the VAA and vent pipe is supported securely to a permanent fixture stud or wall Use standard support straps not supplied with kit that may be found at a local hardware store Failure to pro...

Страница 25: ...A and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical Vent with 3 or 4 inch Pipe Installation of VAA with 3 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths...

Страница 26: ... above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight virgin PVC mater...

Страница 27: ...d make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solvent cement Apply...

Страница 28: ...28 ...

Страница 29: ... located in an area where the general public does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting water heater temperature at 120 F 49 C Approx mark on...

Страница 30: ...eriod of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthest away be opened for several minutes before any electrical appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there wil...

Страница 31: ...rod which will slowly deplete due to electrolysis prolonging the life of the water heater by protecting the glass lined tank from corrosion Adverse water quality hotter water temperatures high hot water usage and water softening methodscanincreasetherateofanoderoddepletion Oncetheanoderod is depleted the tank will start to corrode eventually developing a leak Certain water conditions will cause a ...

Страница 32: ...ressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death DRAINING AND FLUSHING It is recommended that the water heater storage tank be drained and flushed every 6 months to reduce sediment buildup The water heater should be drained if being shut down during freezing temperatures See Typical Installation secti...

Страница 33: ...oose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances water lines or ground seepage should also be checked To check where threaded portion enters tank insert cotton swab between jacket opening and fitting If cotton is wet follow Draining instructions in th...

Страница 34: ...Sheet 34 Wire Screen 3 35 Wire Screen 4 36 Wall Plate 4 37 Flexible Tubing REPAIR PARTS LIST Nowthatyouhavepurchasedthiswaterheater shouldaneedeverexistfor repairpartsorservice simplycontactthecompanyitwaspurchasedfromor direct from the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on reque...

Страница 35: ...r 3 Ensure maximum number of elbows or maximum equivalent feet of vent or intake air pipe has not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure there are no obstructions in the vent or intake air pipe 5 The gas control valve thermostat has detected an open igniter circuit 1 Check wiring to the hot surface igniter assembly replace igniter ass...

Страница 36: ...valve s immersion probe is either open or shorted 1 Turn the power off for 10 20 seconds then on again to clear these error codes 2 Replace the gas control valve thermostat if the error code persists 14 Self diagnostic check has detected a problem with black resistor wire on the ignitor assembly plug resistor wire is open or shorted 1 Turn off power to the water heater Ensure black resistor wire i...

Страница 37: ...37 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...

Страница 38: ...38 TROUBLESHOOTING GUIDELINES NOTES ...

Страница 39: ...pply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method SERVICE AND REPAIR EXPENSES 4 Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is respon...

Страница 40: ...40 American Water Heater Product Service and Support PO Box 1597 500 Princeton Road Johnson City TN 37605 Phone 800 999 9515 Copyright 2010 American Water Heater Company All rights reserved ...