American Standart 4A6H4 Скачать руководство пользователя страница 3

Pub. No. 11-BC08D1-7 

PAGE 3

INSTALLER'S GUIDE

7.  Route  the  tubing  making  all  required  bends  and  properly 

secure the tubing before making connections.
8.  To prevent a noise within the building structure due to vi-

bration transmission from the refrigerant lines, the following 

precautions should be taken:
 

a.  When the refrigerant lines have to be fastened to floor joists 

or other framing in a structure, use isolation type hangers.
 

b.  Isolation hangers should also be used when refrigerant 

lines are run in stud spaces or enclosed ceilings.
 

c.  Where the refrigerant lines run through a wall or sill, they 

should be insulated and isolated.
 

d.  Isolate the lines from all ductwork.

D. SErvICE vALvE OPErATION
BrASS LIqUID AND GAS LINE SErvICE vALvES 

The Brass Liquid and Gas Line Service Valves are factory shipped 

in the seated position to hold factory charge. The pressure tap 

service port (when depressed) opens only to the field brazing side 

of the valve when the valve is in the seated position.  The liquid 

line valve is 

not 

a back seating valve (see

 WArNING 

below).

▲ 

wARNING:

  Extreme  caution  should  be 

exercised when opening the Liquid and Gas Line Service 

valves. Turn valve stem counterclockwise only until the 

stem contacts the rolled edge. (See Figures 3 and 5) No 

torque is required.
BrASS GAS LINE BALL SErvICE vALvE 

The Brass Gas Line Ball Service Valve is shipped in the closed 

position to hold the factory refrigerant charge.  The pressure tap 

service port (when depressed) opens only to the field brazing side 

when the valve is in the closed position.

cAP

1/4 TURN oNLy

coUNTERcLockwISE

foR fULL oPEN 

PoSITIoN

vALvE STEM

GAS LINE coNNEcTIoN

UNIT SIDE

of vALvE

cAP

boDy

cooLING

coRE

PRESSURE TAP PoRT

HEATING

GAS LINE bALL SERvIcE vALvE

The  Gas  Line  Service  Valve  is  full  open  with  a  1/4  turn.  See 

Figure 4.

BrAzING rEFrIGErANT LINES

1.  Remove lower access cover to access service valves.
2.  Before  brazing,  remove  plugs  from  external  copper  stub 

tubes.  Clean internal and external surfaces of stub tubes prior 

to brazing.
3.  Cut and fit tubing, minimizing the use of sharp 90° bends.
4.  Insulate the entire gas line and its fittings.
5.  Do 

NOT

 allow uninsulated liquid line to come in direct contact 

with bare gas line.

6.  Precautions should be taken to avoid heat damage to 

the pressure tap valve core during brazing.  It is recom-

mended that the pressure tap port valve core be removed 

and a wet rag wrapped around the valve body.

NOTICE: 

 Use care to make sure that no moisture enters pressure 

tap port, while wet rag is being used.

NOTICE: 

 Precautions should be taken to avoid heat damage 

to basepan during brazing.  It is recommended to keep the flame 

directly off of the basepan.

7.  Use a Dry Nitrogen Purge and Brazing Alloy without flux 

when  brazing  the  field  line  to  the  copper  factory  connection.  

Flow dry nitrogen into either valve pressure tap port, thru the 

tubing and out the other port while brazing.
8.  Braze using accepted good brazing techniques.

LEAk ChECk
IMPOrTANT:

  Replace pressure tap port valve core before at-

taching hoses for evacuation.
After the brazing operation of refrigerant lines to both the outdoor 

and indoor unit is completed, the field brazed connections must 

be checked for leaks.  Pressurize through the service valve ports, 

the indoor unit and field refrigerant lines with dry nitrogen to 

350-400 psi.  Use soap bubbles or other leak-checking methods 

to see that all field joints are leak-free!  If not, 

release pres-

sure

; then repair!

SySTEM EvACUATION

NOTE:  Since the outdoor unit has a refrigerant charge, the gas 

and liquid line valves must remain closed.

1.  Upon completion of leak check, evacuate the refrigerant lines 

and indoor coil before opening the gas and liquid line valves.

4

5

GAS LINE SERvIcE vALvE

Содержание 4A6H4

Страница 1: ...inted a Rose color to indicate the type of refrigerant and may contain a dip tube to allow for charging of liquid refrigerant into the system All R 410A systems use a POE oil that readily absorbs mois...

Страница 2: ...ational Electri cal Code Also the unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit Do not locate unit s close to bedroom s...

Страница 3: ...alve is full open with a 1 4 turn See Figure 4 Brazing Refrigerant Lines 1 Remove lower access cover to access service valves 2 Before brazing remove plugs from external copper stub tubes Clean intern...

Страница 4: ...ise basic safety precautions to avoid the possibility of electric shock 1 Power wiring and grounding must comply with local codes 2 Power supply must agree with equipment nameplate 3 Install a separat...

Страница 5: ...rost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H IG H V O L T A G E W IR IN G C O M P R E S S O R IO L R U N C A P A C IT O R S T A R T C A P A C IT...

Страница 6: ...tes for the system conditions to stabilize before adjusting charge again 8 When system is correctly charged you can refer to System Pressure Curves in Service Facts to verify typical perfor mance Subc...

Страница 7: ...5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4A6H4030B 3 1 1035 40 3 4 829 32 5 8 756 29 3 4 3 4 5 16 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4A6H4036B 4 1 943 37 1 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 9...

Страница 8: ...d 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Veri...

Отзывы: