American Standart 4A6H4 Скачать руководство пользователя страница 2

PAGE 2 

Pub. No. 11-BC08D1-7

INSTALLER'S GUIDE

It is recommended that these precautions be taken for 

units being installed in areas where snow accumulation 

and prolonged below freezing temperatures occur.

1. 

Units  should  be  elevated  3  to  12  inches  above  the  pad  or 

rooftop, depending on local weather.  This additional height will 

allow  better  drainage  of  snow  and  ice  (melted  during  defrost 

cycle) prior to its refreezing. 

 This should prevent a buildup of 

ice  around  the  unit  which  occurs  when  unit  is  not  elevated.  

 

Insure that drain holes in unit base pan are not obstructed  

preventing draining of defrost water.

2.  If possible, avoid locations that are likely to accumulate snow 

drifts.  If not possible, a snow drift barrier should be installed 

around the unit to prevent a buildup of snow on the sides of the 

unit and should be of sufficient distance from the unit to prevent 

restriction of airflow to and from the unit.  Also allow for proper 

maintenance space.  The barrier should be constructed of materi-

als which will blend in with the building design.
3.  Avoid locating the unit where condensation and freezing of 

defrost vapor may annoy the customer.  For instance, installing 

the unit under a bedroom, kitchen, or picture window may be 

annoying to the customer since condensate and fog will occur 

during the defrost cycle.
4.  Avoid locating the unit under the eaves or other overhead 

structures  as  sizeable  icicles  may  form  and  the  unit  may  be 

damaged by these falling icicles.

B.  LOCATION AND PrEPArATION OF ThE UNIT

1.  When removing unit from the pallet, notice the tabs on the 

basepan. Remove tabs by cutting with a sharp tool as shown on 

page 2, Figure 2, and slide unit off of pallet.

2.  The unit should be set on a level support pad at least as large 

as the unit base pan, such as a concrete slab. If this is not the 

application  used  please  refer  to  application  bulletin AMSSP-

APG002-EN.
3.  The  support  pad  must  NOT  be  in  direct  contact  with  any 

structure.  Unit must be positioned a minimum of 12" from any 

wall or surrounding shrubbery to insure adequate airflow.  Clear-

ance must be provided in front of control box (access panels) & 

any other side requiring service access to meet National Electri-

cal Code.  Also, the unit location must be far enough away from 

any structure to prevent excess roof runoff water from pouring 

directly on the unit. Do not locate unit(s) close to bedroom(s).
4.  The top discharge area must be unrestricted for at least five (5) 

feet above the unit.
5.  When the outdoor unit is mounted on a roof, be sure the roof 

will support the unit’s weight. Properly selected isolation is rec-

ommended to prevent transmission to the building structure.
6.  The  maximum  length  of  refrigerant  lines  from  outdoor  to 

indoor unit should NOT exceed sixty (60) feet.
7.  If outdoor unit is mounted above the air handler, maximum 

lift should not exceed sixty (60) feet (suction line).  If air handler 

is  mounted  above  condensing  unit,  maximum  lift  should  not 

exceed sixty (60) feet (liquid line).
8.  Locate and install indoor coil or air handler in accordance 

with instruction included with that unit.

C.  INSTALLING rEFrIGErANT LINES 

▲ 

cAUTIoN:

 If using existing refrigerant lines 

make certain that all joints are brazed, not soldered.

Condensing units have provisions for braze connections. 
Pressure taps are provided on the service valves of outdoor unit 

for compressor suction and liquid pressures.
The indoor end of the recommended refrigerant line sets may 

be straight or with a 90 degree bend, depending upon situation 

requirements.    This  should  be  thoroughly  checked  out  before 

ordering refrigerant line sets.
The gas line must always be insulated.

▲ 

cAUTIoN:

 In scroll compressor applications, 

dome temperatures may be hot. Do not touch top of com-

pressor, may cause minor to severe burning.

The units are factory charged with the system charge required 

when using fifteen (15) feet of connecting line.  Unit nameplate 

charge is the same.

Final  refrigerant  charge  adjustment  is  necessary. 

Use 

the Charging Information in the outdoor unit Service Facts or 

on page 6.
1.  Determine the most practical way to run the lines.
2.  Consider types of bends to be made and space limitations.

NOTE:  Large diameter tubing will be very difficult to rebend 

once it has been shaped.

3.  Determine the best starting point for routing the refrigerant 

tubing — INSIDE OR OUTSIDE THE STRUCTURE.
4.  Provide a pull-thru hole of sufficient size to allow both liquid 

and gas lines.
5.  Be sure the tubing is of sufficient length.
6.  Uncoil the tubing — do not kink or dent.

bASEPAN TAb REMovAL

2

3

LIQUID LINE SERvIcE vALvE

Содержание 4A6H4

Страница 1: ...inted a Rose color to indicate the type of refrigerant and may contain a dip tube to allow for charging of liquid refrigerant into the system All R 410A systems use a POE oil that readily absorbs mois...

Страница 2: ...ational Electri cal Code Also the unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit Do not locate unit s close to bedroom s...

Страница 3: ...alve is full open with a 1 4 turn See Figure 4 Brazing Refrigerant Lines 1 Remove lower access cover to access service valves 2 Before brazing remove plugs from external copper stub tubes Clean intern...

Страница 4: ...ise basic safety precautions to avoid the possibility of electric shock 1 Power wiring and grounding must comply with local codes 2 Power supply must agree with equipment nameplate 3 Install a separat...

Страница 5: ...rost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H IG H V O L T A G E W IR IN G C O M P R E S S O R IO L R U N C A P A C IT O R S T A R T C A P A C IT...

Страница 6: ...tes for the system conditions to stabilize before adjusting charge again 8 When system is correctly charged you can refer to System Pressure Curves in Service Facts to verify typical perfor mance Subc...

Страница 7: ...5 8 92 3 5 8 210 8 1 4 79 3 1 8 508 20 4A6H4030B 3 1 1035 40 3 4 829 32 5 8 756 29 3 4 3 4 5 16 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4A6H4036B 4 1 943 37 1 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 9...

Страница 8: ...d 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Veri...

Отзывы: