41
ReliaTel Control
The RTRM has the ability to provide the service personnel
with some unit diagnostics and system status information.
Before turning the main power disconnect switch “Off”, fol-
low the steps below to check the ReliaTel Refrigeration Mod-
ule (RTRM). All diagnostics & system status information stored
in the RTRM will be lost when the main power is turned “Off”.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting
of this product, it may be necessary to work with live
electrical components. Have a qualified licensed electri-
cian or other individual who has been properly trained in
handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury.
To prevent injury or death from electrocution, it is the re-
sponsibility of the technician to recognize this hazard and
use extreme care when performing service procedures with
the electrical power energized.
1. Verify that the Liteport LED on the RTRM is burning con-
tinuously. If the LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 VAC is presence be-
tween J1-1 and J1-2. If 24 VAC is present, proceed to
Step 3. If 24 VAC is not present, check the unit main
power supply, check transformer (TNS1). Proceed to Step
3 if necessary.
3. Utilizing “Method 1” or “Method 2” in the “System Status
Diagnostic” section, check the following:
System status
Heating status
Cooling status
If a System failure is indicated, proceed to Step 4. If no
failures are indicated, proceed to Step 5.
4. If a System failure is indicated, recheck Steps 1 and 2. If
the LED is not lit in Step 1, and 24 VAC is present in Step
2, the RTRM has failed. Replace the RTRM.
5. If no failures are indicated, use one of the TEST mode
procedures described in the “Unit Start-Up” section to
start the unit. This procedure will allow you to check all of
the RTRM outputs, and all of the external controls (re-
lays, contactors, etc.) that the RTRM outputs energize, for
each respective mode. Proceed to Step 6.
6. Step the system through all of the available modes, and
verify operation of all outputs, controls, and modes. If a
problem in operation is noted in any mode, you may
leave the system in that mode for up to one hour while
troubleshooting. Refer to the sequence of operations for
each mode, to assist in verifying proper operation. Make
the necessary repairs and proceed to Steps 7 and 8.
Trouble Shooting
7. If no abnormal operating conditions appear in the test mode,
exit the test mode by turning the power “Off” at the main
power disconnect switch.
8. Refer to the individual component test procedures if other
microelectronic components are suspect.
System Status Checkout Procedure
“System Status” is checked by using one of the following two
methods:
Method 1
If the Zone Sensor Module (ZSM) is equipped with a remote
panel with LED status indication, you can check the unit
within the space. If the ZSM does not have LED’s, use
Method 2. BAYSENS010B, BAYSENS011B,
BAYSENS019A, BAYSENS020A, BAYSENS021A &
BAYSENS023A all have the remote panel indication fea-
ture. The LED descriptions are listed below.
LED 1 (System)
“On” during normal operation.
“Off” if a system failure occurs or the LED fails.
“Flashing” indicates test mode.
LED 2 (Heat)
“On” when the heat cycle is operating.
“Off” when the heat cycle terminates or the LED fails.
“Flashing” indicates a heating failure.
LED 3 (Cool)
“On” when the cooling cycle is operating.
“Off” when the cooling cycle terminates or the LED fails.
“Flashing” indicates a cooling failure.
LED 4 (Service)
“On” indicates a clogged filter.
“Off” during normal operation.
“Flashing” indicates an evaporator fan failure
Below is the complete listing of failure indication causes.
System failure
Check the voltage between terminals 6 and 9 on J6, it
should read approximately 32 VDC. If no voltage is present,
a System failure has occurred. Refer to Step 4 in the previ-
ous section for the recommended troubleshooting proce-
dure.
Heating Failure
Verify Heat Failure by Ignition Module (IGN) LED indicator:
OFF:
No Power or Failure
ON:
Normal
Slow Flash:
Normal, Heat Call
Fast Flash:
Error Code:
1 Flash:
Communication Failure
2 Flashes:
System Lockout
3 Flashes:
Pressure Switch Fail
4 Flashes
TC01 or TC02 Open
5 Flashes:
Flame w/o Gas Valve
6 Flashes:
Flame Rollout Open