The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor 

should use only industry-recognized procedures.

Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.

Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver air along the perimeter of the space. If 

they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Air grilles must be properly sized 

to carry air back to the blower.If they are too small, they also cause noise.

The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living 

space.

--- Shaded boxes represent airflow outside the required 300-450 cfm/ton. 

NOTES: 

1. Airflow based upon dry coil at 230V with no electric heat, no filter.

2. Airflow is equivalent for front or bottom return configurations.

3. SCFM is nearly the same with cooling performance airflow, the gap is in the 1 to 2%.

0[0] 

0.1[.02]  0.2[.05]  0.24[.06]  0.3[.07]  0.4[.10]  0.5[.12]  0.6[.15]  0.7[.17]  0.8[.20] 

CFM 

997 

948 

903 

891 

861 

809 

760 

RPM 

755 

789 

817 

828 

846 

870 

903 

Watts 

305 

295 

287 

283 

278 

271 

263 

Amps 

1.53 

1.51 

1.49 

1.48 

1.47 

1.46 

1.44 

CFM 

1187 

1125 

1076 

1055 

1021 

974 

912 

RPM 

875 

899 

916 

924 

935 

952 

967 

Watts 

339 

331 

324 

321 

317 

309 

302 

Amps 

1.67 

1.66 

1.64 

1.63 

1.62 

1.61 

1.59 

CFM 

1306 

1249 

1166 

1132 

1069 

1008 

937 

860 

759 

RPM 

956 

968 

982 

987 

994 

1007 

1015 

1027 

1041 

1054 

Watts 

427 

417 

409 

406 

400 

391 

384 

375 

363 

351 

Amps 

2.20 

2.18 

2.16 

2.15 

2.15 

2.13 

2.11 

2.09 

2.07 

2.05 

CFM 

 1106 

 1056 

1007 

 990 

960 

918 

857 

RPM 

818 

843 

868 

878 

893 

916 

941 

Watts 

371 

361 

349 

346 

338 

328 

316 

Amps 

1.62 

1.58 

1.53 

1.52 

1.49 

1.44 

1.4 

CFM 

 1269 

 1213 

 1153 

 1131 

 1097 

 1069 

 973 

RPM 

920 

933 

947 

956 

965 

982 

997 

Watts 

410 

401 

391 

385 

380 

368 

357 

Amps 

1.79 

1.74 

1.70 

1.67 

1.65 

1.60 

1.55 

CFM 

 1375 

 1320 

 1267 

 1248 

 1204 

 1142 

 1082 

 1011 

 919 

801 

RPM 

986 

996 

1007 

1011 

1018 

1030 

1040 
 

1051 

1063 

1079 

Watts 

461 

450 

440 

436 

427 

416 

402 

388 

376 

358 

Amps 

2.01 

1.96 

1.92 

1.90 

1.87 

1.81 

1.76 

1.70 

1.65 

1.57 

External Static Pressure-Inches W.C.[kPa] 

 CFM(Watts) 

36 

Low 

Middle 

High 

Motor 

Speed 

Low 

Middle 

30 

High 

Model 

Number 

1195 

Содержание TMM4A0A18S21SA

Страница 1: ...o air conditioning applications Field installed electric resistance heaters are available 18 GF07D1 1 FRONT OR BOTTOM RETURN AIR PAINTED FINISH ON GALVANIZED STEEL STURDY POLYCARBONATE DRAIN PANS The...

Страница 2: ...ause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servi...

Страница 3: ...by using 3 wood screws not provided Make sure the bracket is level in order to provided proper drainage from the unit Note Do not attach the wall mounting bracket into unsupported dry wall Make sure t...

Страница 4: ...ACCA Manual D Design for Residential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Wa...

Страница 5: ...commonly used with AC single stage cooling with electric heat The thermostat will energize the fan on a demand for cool Install the thermostat on an inside wall away from drafts lights or other heat s...

Страница 6: ...lines 4 Verify that all electrical connections are tight 5 Check all duct outlets they must be open and unrestricted 6 Check drain lines and be sure all joints are tight 7 Be sure the return air filte...

Страница 7: ...7 Fig 4 1...

Страница 8: ...861 878 885 903 923 945 Watts 236 231 227 226 221 217 211 Amps 1 03 1 01 1 0 0 99 0 98 0 96 0 94 CFM 938 894 860 859 813 764 710 674 573 465 RPM 921 937 950 953 967 980 994 1010 969 1051 Watts 300 29...

Страница 9: ...rn configurations 3 SCFM is nearly the same with cooling performance airflow the gap is in the 1 to 2 0 0 0 1 02 0 2 05 0 24 06 0 3 07 0 4 10 0 5 12 0 6 15 0 7 17 0 8 20 CFM 997 948 903 891 861 809 76...

Страница 10: ...conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten only Section 7 Dimensional Data 10...

Страница 11: ...er TX 75707 www trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications withou...