
3
Carefully unpack the unit and inspect the contents for damage. If
any damage is found at the time of delivery, proper notification and
claims should be made with the carrier.
Check the rating plate to assure model number and voltage, plus
any kits match with what you ordered. The manufacturer should be
notified within 5 days of any discrepancy or parts shortage.
The small air handler should be centrally located and may be
installed in a closet, alcove, utility room, basement. Minimum
clearances must be met.
The air handler comes standard with two different options for
mounting, wall mount or frame mount. Both mounting options require
the unit to be level from side to side and from front to back in order to
allow condensate to properly drain from the unit. Failure to do this will
result in condensate to leak out from the unit potentially causing
structural damage to the surrounding support structures, dry wall,
carpet, etc. around the unit. Also, both mounting structures require
the ability to accommodate a minimum of 150 lb load. Failure to do
this will cause damage to the support structure and potentially
damage the unit.
The air handler comes standard with an upper and lower wall mount
bracket. Reference Figure 3-1 for more detail.
1. Remove lower wall mounting bracket from the back of the unit by
removing one screw which attaches the bracket to the air handler.
Note: Discard the screw after you have removed the wall mounting
bracket.
2. Install bracket on the wall by using 3 wood screws (not provided).
Make sure the bracket is level in order to provided proper drainage
from the unit. Note: Do not attach the wall mounting bracket into
unsupported dry wall. Make sure that the wood screws are going into
a structure that can suppport a minimum of 150 lb load.
3. Lift the air handler above the wall mounting bracket and attached
the unit to the installed bracket. Reference Figure 3-1.
4. Install the additional bottom plate for extra support for this type
mounting (see figure 3-1).
Note: The additional plate is shipped in the bottom of the shipping
carton (only for 30/36k unit).
3.2.1 WALL MOUNT
Fig. 3-2 FRAME MOUNT
The air handler comes with 8 clearance holes 4 on each side. These
holes are used to mount the air handler inside of a frame structure
(see Figure 3-2). When mounting in this fashion, make sure that the
wood screws are mounted from within the air handler and not outside
of the unit. Installing the screws from the outside of the unit, And
notice don’t damage to the coil.
For ensure the proper installation for frame mount, Select the enough
solid and level site. Ensure enough space required for installation and
maintenance(See Figure. 3-3)
3.2.2 FRAME MOUNT
PROVIDED WALL
MOUNT BRACKET
WALL MOUNT PLATE
WOOD SCREWS
SUPPORTING 2˝X4˝
STRUCTURE
WALL STRUCTURE
WOOD SCREWS
WOOD SCREWS
PROVIDED WALL
MOUNT BRACKET
NOTE: MOUNTING WALL AND SUPPORTING
STRUCTURE MUST BE ABLE TO SUPPORT A
MINIMUM OF 150 LBS.
PROVIDED AIR HANDLER
MOUNTING BRACKET
Fig. 3-1 WALL MOUNT
WOOD SCREWS
3
1
.5
˝
Section 3. Installation Instructions
3.1 Unpacking
3.2 Location
WALL STRUCTURE
SUPPORTING
2"X4" STRUCTURE
WOOD SCREWS
SUPPORTING
2"X4" STRUCTURE
STUD ATTACHMANT
HOLES
Содержание TMM4A0A18S21SA
Страница 7: ...7 Fig 4 1...
Страница 12: ...100 A4...