Page B-651-438

17

Service Facts

*DY120R9V5W - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =

2nd STAGE CAPACITY =

74,000

112,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 8

SW 7

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1025

65

150

1025

65

200

1000

67

240

1000

67

290

1000

67

340

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1200

56

230

1200

56

270

1200

56

330

1200

56

390

1200

56

450

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1350

49

280

1350

49

340

1350

49

490

1350

49

470

1350

49

530

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1550

43

400

1550

43

490

1550

43

560

1550

43

620

1450

46

600

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1550

66

380

1550

66

470

1550

66

540

1550

66

610

1450

71***

690

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1850

56

660

1850

56

750

1850

56

780

1700

60

720

1500

69

640

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

2050

50

860

2000

51

880

1850

56

810

1700

60

750

1550

66

670

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

2105

49

1000

2050

50

940

1900

54

880

1775

58

820

1625

63

750

 NOTES:
  * First letter may be "A" or "T"
  ** Factory setting

*DY120R9V5W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW  1

SW  2

SW  3

SW  4

0.1

0.3

0.5

0.7

0.9

3.5

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

1225

240

1225

280

1225

340

1225

400

1225

450

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

1400

310

1400

390

1400

470

1400

520

1400

570

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

1600

450

1600

520

1600

590

1600

640

1450

600

4.0

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

1400

300

1400

380

1400

450

1400

520

1400

570

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1600

460

1600

530

1600

610

1600

670

1450

600

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1800

610

1800

700

1800

760

1650

690

1500

630

5

LOW

(350 CFM/TON)

OFF

OFF

OFF

ON

CFM

WATTS

1750

580

1750

640

1750

720

1650

680

1450

610

NORMAL

(400 CFM/TON)

OFF

OFF

OFF

OFF

CFM

WATTS

2000

830

2000

860

1850

800

1700

740

1550

660

HIGH

(450 CFM/TON)

OFF

OFF

ON

OFF

CFM

WATTS

2100

970

2000

910

1900

850

1650

780

1600

710

 NOTES:   * - First letter may be "A" or "T"
 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
     NORMAL airflow (400 cfm/ton) is typical setting;
     HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Содержание ADY060R9V3W

Страница 1: ... is to remain with this unit Please return to service information pack upon completion of work DISCONNECT POWER BEFORE SERVICING WARNING UY060R9V3W Upflow Horizontal 39 000 37 000 60 000 56 000 35 65 DIRECT 10 x 8 1 Variable See Fan Performance Table 1 2 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Yes High Velocity 1 17x25 1 in 2 Round Aluminized Steel Type I 20 3 4...

Страница 2: ...0 Yes High Velocity 2 16x20 1 in 3 Round Aluminized Steel Type I 20 6 45 6 56 Redundant Two Stage Hot Surface Igniter Multiport Inshot 6 115 1 60 15 2 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 206 196 DY100R9V4W Downflow Horizontal 65 000 60 000 100 000 94 000 35 65 DIRECT 10 x 10 1 Variable See Fan PerformanceTable 3 4 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Ye...

Страница 3: ... an electrical shock fire injury or death CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connecte...

Страница 4: ...ced draft blower is switched to low speed and de energized after the post purge timer has expired The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN OFF period WARNING Should overheating occur or the gas supply fail to shut off shut off the gas valve to the unit before shutting off the electrical supply Failure to f...

Страница 5: ...lean burners remove burner box cover 6 to 8 screws and top burner bracket Lift burners from orifices NOTE Be careful not to break igniter when removing burners Clean burners with brush and or vacuum cleaner Reas semble parts by reversal of the above procedure The burner box must be resealed when replacing box cover NOTE On LP propane units some light yellow tipping of the outer mantle is normal In...

Страница 6: ...6 Page B 651 438 Service Facts UY WIRING DIAGRAM ...

Страница 7: ...Page B 651 438 7 Service Facts UY SCHEMATIC DIAGRAM ...

Страница 8: ...8 Page B 651 438 Service Facts DY WIRING DIAGRAM ...

Страница 9: ...Page B 651 438 9 Service Facts DY SCHEMATIC DIAGRAM ...

Страница 10: ... OFF CFM WATTS 1325 360 1325 425 1300 460 1175 425 1000 365 NOTES First letter may be A or T 1 At continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY060R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WA...

Страница 11: ...OW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 750 84 750 122 750 154 720 185 710 221 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 840 109 840 146 840 181 840 226 820 264 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 940 136 940 177 940 215 940 274 940 318 2 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 850 113 850 150 ...

Страница 12: ...N OFF OFF ON OFF CFM WATTS 1847 630 1863 735 1816 780 1687 720 1532 665 NOTES First letter may be A or T 1 At Continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY100R9V4W FURNACE HEATING AIRFLOW CFM ...

Страница 13: ...g Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY120R9V5W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st Stage Capacity 2nd Stage Capacity 74 000 112 000 AIRFLOW SETTING DIP SW...

Страница 14: ...FLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 1 5 LOW 350 CFM TON OFF OFF OFF ON CFM WATTS 525 45 525 70 525 100 525 135 525 160 NORMAL 400 CFM TON OFF OFF OFF OFF CFM WATTS 600 55 600 85 600 120 600 150 600 185 HIGH 450 CFM TON OFF OFF ON OFF CFM WATTS 675 65 675 105 625 140 675 175 675 205 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 700 70 700 11...

Страница 15: ... Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting DY080R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st STAGE CAPACITY 2nd STAGE CAPACITY 49 000 73 000 AIRFLOW SETTING DIP SWITCH SETTING ...

Страница 16: ...TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 5 LOW 350 CFM TON ON ON OFF ON CFM WATTS 870 100 885 140 887 185 881 230 876 270 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 989 120 1018 180 1016 230 1012 285 999 325 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 1124 175 1139 225 1130 275 1135 335 1135 390 3 0 LOW 350 CFM TON OFF ON OFF ON CFM WAT...

Страница 17: ...ing DY120R9V5W FURNACE COOLING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER OUTDOOR UNIT SIZE TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 3 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 1225 240 1225 280 1225 340 1225 400 1225 450 NORMAL 400 CFM TON OFF ON OFF OFF CFM WATTS 1400 310 1400 390 1400 470 1400 520 1400 570 ...

Страница 18: ...ONTROL GREEN STATUS LED FLASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Fault Code Reset The last 4 fault codes can be erased from memory by power ing up the control with G energized and then applying R to the W1 terminal 3 times within 6 seconds The control will acknowledge the reset by turning on the red LED for 2 seconds FAULT CODE RECOVERY On power up last ...

Страница 19: ...Page B 651 438 19 Service Facts NOTES ...

Страница 20: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 Formoreinformationcontact yourlocaldealer distributor ...

Отзывы: