Page B-651-438

Service Facts

*DY100R9V4W - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =

2nd STAGE CAPACITY =

62,000
93,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 7

SW 8

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

923

61

110

955

59

165

960

58

210

958

58

265

947

59

310

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1020

55

145

1047

53

190

1053

53

250

1042

54

295

1029

54

350

MEDIUM **

ON

OFF

CFM

TEMP. RISE

WATTS

1156

48

185

1166

48

240

1172

48

300

1177

48

350

1178

48

420

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1275

44

225

1305

43

290

1328

42

365

1328

42

445

1328

42

510

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1298

66

235

1320

65

305

1335

65

380

1343

64

445

1343

64

520

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1439

60

310

1459

59

390

1482

58

470

1483

58

550

1470

59

610

MEDIUM **

ON

OFF

CFM

TEMP. RISE

WATTS

1639

53

430

1650

52

525

1650

52

600

1644

52

680

1496

58

640

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1790

18

570

1818

47

670

1813

47

770

1708

50

750

1535

56

675

 NOTES:   * - First letter may be "A" or "T"
  ** Factory setting
  *** Above MAX temperature change

*DY100R9V4W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 1

SW 2

SW 3

SW 4

0.1

0.3

0.5

0.7

0.9

2.5

LOW

(350 CFM/TON)

ON

ON

OFF

ON

CFM

WATTS

870
100

885

140

887

185

881

230

876
270

NORMAL

(400 CFM/TON)

ON

ON

OFF

OFF

CFM

WATTS

989
120

1018

180

1016

230

1012

285

999
325

HIGH

(450 CFM/TON)

ON

ON

ON

OFF

CFM

WATTS

1124

175

1139

225

1130

275

1135

335

1135

390

3.0

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

1053

145

1075

200

1070

245

1070

295

1049

350

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

1186

195

1205

255

1220

310

1220

370

1216

440

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

1336

255

1366

340

1383

405

1385

470

1381

545

3.5

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

1216

190

1225

255

1235

320

1240

385

1243

445

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1394

270

1422

360

1436

430

1437

505

1430

580

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1579

395

1604

475

1610

555

1599

645

1517

640

4.0

LOW

(350 CFM/TON)

OFF

OFF

OFF

ON

CFM

WATTS

1377

270

1412

355

1426

430

1433

510

1428

575

NORMAL

(400 CFM/TON)

OFF

OFF

OFF

OFF

CFM

WATTS

1599

425

1624

510

1636

585

1618

670

1512

635

HIGH

(450 CFM/TON)

OFF

OFF

ON

OFF

CFM

WATTS

1801

580

1818

690

1815

775

1694

735

1525

660

 NOTES:  * - First letter may be "A" or "T"
  1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
  2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
     NORMAL airflow (400 cfm/ton) is typical setting;
     HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Содержание ADY060R9V3W

Страница 1: ... is to remain with this unit Please return to service information pack upon completion of work DISCONNECT POWER BEFORE SERVICING WARNING UY060R9V3W Upflow Horizontal 39 000 37 000 60 000 56 000 35 65 DIRECT 10 x 8 1 Variable See Fan Performance Table 1 2 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Yes High Velocity 1 17x25 1 in 2 Round Aluminized Steel Type I 20 3 4...

Страница 2: ...0 Yes High Velocity 2 16x20 1 in 3 Round Aluminized Steel Type I 20 6 45 6 56 Redundant Two Stage Hot Surface Igniter Multiport Inshot 6 115 1 60 15 2 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 206 196 DY100R9V4W Downflow Horizontal 65 000 60 000 100 000 94 000 35 65 DIRECT 10 x 10 1 Variable See Fan PerformanceTable 3 4 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Ye...

Страница 3: ... an electrical shock fire injury or death CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connecte...

Страница 4: ...ced draft blower is switched to low speed and de energized after the post purge timer has expired The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN OFF period WARNING Should overheating occur or the gas supply fail to shut off shut off the gas valve to the unit before shutting off the electrical supply Failure to f...

Страница 5: ...lean burners remove burner box cover 6 to 8 screws and top burner bracket Lift burners from orifices NOTE Be careful not to break igniter when removing burners Clean burners with brush and or vacuum cleaner Reas semble parts by reversal of the above procedure The burner box must be resealed when replacing box cover NOTE On LP propane units some light yellow tipping of the outer mantle is normal In...

Страница 6: ...6 Page B 651 438 Service Facts UY WIRING DIAGRAM ...

Страница 7: ...Page B 651 438 7 Service Facts UY SCHEMATIC DIAGRAM ...

Страница 8: ...8 Page B 651 438 Service Facts DY WIRING DIAGRAM ...

Страница 9: ...Page B 651 438 9 Service Facts DY SCHEMATIC DIAGRAM ...

Страница 10: ... OFF CFM WATTS 1325 360 1325 425 1300 460 1175 425 1000 365 NOTES First letter may be A or T 1 At continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY060R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WA...

Страница 11: ...OW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 750 84 750 122 750 154 720 185 710 221 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 840 109 840 146 840 181 840 226 820 264 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 940 136 940 177 940 215 940 274 940 318 2 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 850 113 850 150 ...

Страница 12: ...N OFF OFF ON OFF CFM WATTS 1847 630 1863 735 1816 780 1687 720 1532 665 NOTES First letter may be A or T 1 At Continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY100R9V4W FURNACE HEATING AIRFLOW CFM ...

Страница 13: ...g Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY120R9V5W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st Stage Capacity 2nd Stage Capacity 74 000 112 000 AIRFLOW SETTING DIP SW...

Страница 14: ...FLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 1 5 LOW 350 CFM TON OFF OFF OFF ON CFM WATTS 525 45 525 70 525 100 525 135 525 160 NORMAL 400 CFM TON OFF OFF OFF OFF CFM WATTS 600 55 600 85 600 120 600 150 600 185 HIGH 450 CFM TON OFF OFF ON OFF CFM WATTS 675 65 675 105 625 140 675 175 675 205 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 700 70 700 11...

Страница 15: ... Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting DY080R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st STAGE CAPACITY 2nd STAGE CAPACITY 49 000 73 000 AIRFLOW SETTING DIP SWITCH SETTING ...

Страница 16: ...TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 5 LOW 350 CFM TON ON ON OFF ON CFM WATTS 870 100 885 140 887 185 881 230 876 270 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 989 120 1018 180 1016 230 1012 285 999 325 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 1124 175 1139 225 1130 275 1135 335 1135 390 3 0 LOW 350 CFM TON OFF ON OFF ON CFM WAT...

Страница 17: ...ing DY120R9V5W FURNACE COOLING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER OUTDOOR UNIT SIZE TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 3 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 1225 240 1225 280 1225 340 1225 400 1225 450 NORMAL 400 CFM TON OFF ON OFF OFF CFM WATTS 1400 310 1400 390 1400 470 1400 520 1400 570 ...

Страница 18: ...ONTROL GREEN STATUS LED FLASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Fault Code Reset The last 4 fault codes can be erased from memory by power ing up the control with G energized and then applying R to the W1 terminal 3 times within 6 seconds The control will acknowledge the reset by turning on the red LED for 2 seconds FAULT CODE RECOVERY On power up last ...

Страница 19: ...Page B 651 438 19 Service Facts NOTES ...

Страница 20: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 Formoreinformationcontact yourlocaldealer distributor ...

Отзывы: