American Standard ACONT900AC43UA Скачать руководство пользователя страница 3

ACONT900AC43UA

Pub. No. 11-HD04D1-2

3

69-2080—05

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
these instructions can damage the product or cause 
a hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After completing installation, use these instructions 
to check out the product operation.

WARNING

Voltage Hazard. Can cause electrical shock or 
equipment damage.

Disconnect power before beginning installation.

Location

Install the Comfort Control about 5 ft. (1.5m) above the 
floor in an area with good circulation at average 
temperature. See Figure 1.

Fig. 1. Selecting Comfort Control Location

Do not install the Comfort Control where it can be affected 
by:

• drafts or dead spots behind doors and in corners.
• hot or cold air from ducts.
• radiant heat from sun or appliances.
• concealed pipes and chimneys.
• unheated (uncooled) areas such as an outside wall 

behind the Comfort Control.

Sub-base Installation

The Comfort Control can be mounted horizontally on the 
wall or on a 2 in. by 4 in. wiring box. Position sub-base 
horizontally on the wall or on a 2 in. by 4 in. wiring box.

1.

Turn OFF all power to heating and coolingequip-
ment.

2.

If an existing Comfort Control is being replaced:
a. Remove existing Comfort Control from wall.
b. Disconnect wires from existing control, one at a 

time. Be careful not to allow wires to fall back 
into wall.

c. As each wire is disconnected, record wire color 

and terminal marking. 

d. Discard or recycle old Comfort Control.

3.

Separate the Comfort Control from the subbase to 
expose mounting holes.

4.

Position and level the sub-base wallplate (for 
appearance only). The Comfort Control functions 
properly even when not level.

5.

Use a pencil to mark the mounting holes.

6.

Remove the sub-base from the wall and drill two 
3/16 in. holes in the wall (if drywall) as marked. For 
firmer material such as plaster, drill two 7/32 in. 
holes. Gently tap anchors (provided) into the drilled 
holes until flush with the wall.

7.

Position the sub-base over the holes, pulling the 
wires through the wiring opening.

8.

Insert the mounting screws in the holes and tighten.

Wiring

All wiring must comply with local electrical codes and 
ordinances. See Figures 2 and 3 wiring diagrams for 
specific equipment applications. Refer to Table 2 for 
terminal designations.

WARNING

Voltage Hazard. Can cause electrical shock or 
equipment damage.

Disconnect power before beginning installation

NOTE: The maximum total cable length for the entire 

Comfort Control communicating system is 500 
feet 18 AWG. The maximum distance of any 
single cable from a transformer is 250 feet 
18 AWG.

1.

Loosen the terminal screws on the sub-base. Insert 
wires into the terminal block next to the loosened 
screw. See Figure 4.

IMPORTANT 

Use 18-gauge color-coded Comfort Control cable for 
proper wiring. Shielded cable is not 
typically required. Keep this wiring at least one foot away 
from large inductive loads such as 
Electronic Air Cleaners, motors, line starters, lighting 
ballasts and large distribution panels. Failure to follow 
these wiring practices may 
introduce electrical interference (noise) which can cause 
erratic system operation. All unused Comfort Control wire 
to be grounded at indoor unit chassis ground only. 
Shielded cable may be required if the above wiring 
guidelines cannot be met. Ground the shield only to the 
system chassis.

5 FEET

[1.5 METERS]

YES

NO

NO

NO

Содержание ACONT900AC43UA

Страница 1: ...al fuel systems via digital 2 way communications The Comfort Control will communicate with and identify all AccuLinkTM components in the system It is easily manually configured via the user friendly I...

Страница 2: ...150 F 34 4 C 65 6 C 5 90 RH non condensing Operating Temperature Range 0 F 120 F 17 8 C 37 2 C 5 90 RH non condensing System Mode Heat Cool Auto Emergency Heat and Off Fan Mode On Auto and Circ Coolin...

Страница 3: ...Control from the subbase to expose mounting holes 4 Position and level the sub base wallplate for appearance only The Comfort Control functions properly even when not level 5 Use a pencil to mark the...

Страница 4: ...Stage Cooling Unit B BK Y2 Y1 O R D W1 W3 G W2 B D B R D X2 Y2 Y1 O COMFORT CONTROL 24VAC HOT 24VAC Common DATA INDOOR UNIT OUTDOOR UNIT COM COM COM LOW VOLTAGE WIRING TO BE NO 18 AWG MINIMUM CONDUCT...

Страница 5: ...received during Discovery mode NOTE While in Discovery mode the LED indicator located in the upper right corner of the Comfort Control will be illuminated NOTE All discovered values will be saved int...

Страница 6: ...See Figure 5 Fig 5 Clock Activation NOTE If the system is not powered the Real Time Clock battery life is approximately 20 weeks The Comfort Control is designed to automatically keep the current time...

Страница 7: ...y to exit the Installer Setup screen NOTE Manually changing an ISU setting to an option other than E disables Discovery mode for that ISU setting If power is lost all custom settings are retained in t...

Страница 8: ...minimum of 1H or 1C is required Fan Operation 0180 E E 0 1 E Auto Discover 0 Equipment controls fan operation in heat mode fossil 1 Comfort Control controls fan operation in heat mode electric Only se...

Страница 9: ...ight comes on with a key press 1 Backlit is on continuously Comfort Control backlight will come on full brightness with a key press and display will dim 45 seconds after the last keypress Changeover 0...

Страница 10: ...0 F 6 5 C 25 25 F 4 0 C 30 30 F 1 0 C 35 35 F 1 5 C 40 40 F 4 5 C 45 45 F 7 0 C 50 50 F 10 0 C 55 55 F 13 0 C 60 60 F 15 5 C System will switch to gas furnace to satisfy call for heat if the highest c...

Страница 11: ...alled For future use Leave at factory default setting E Indoor Humidity Sensor 0370 1 0 1 2 0 Disabled 1 Internal sensor 2 Remote sensor Indoor Humidification Control 0372 E 0 E 0 1 2 E Auto Discover...

Страница 12: ...ous days 12 120 continuous days 13 180 continuous days 14 365 continuous days When set to Auto Discover and the discovered value is not 0 disabled the Comfort Control will display the filter timer val...

Страница 13: ...rnal timer simply press the More key to access the filter timer value and then press the Reset key Humidifier Pad Replacement Reminder 0510 E 0 E 0 3 E Auto Discover 0 Disabled 1 90 continuous days 30...

Страница 14: ...e V S only 5 5 seconds 10 10 seconds 20 20 seconds 30 30 seconds For Variable Speed indoor units choices are 0 and 1 For Non variable Speed indoor units choices are 0 5 10 20 and 30 Compressor Cool Fa...

Страница 15: ...on Circ Circulation control will provide a variable circulation determined by the Adaptive Intelligent Circulation AIC algorithm running the fan between 20 and 60 of the time Temperature Control in Co...

Страница 16: ...2D2 1 69 2009 for a listing of all equipment Alert codes Equipment Damage Hazard Minimum compressor off time is bypassed during Installer System Test Avoid cycling compressor quickly Observe compresso...

Страница 17: ...e Heating setpoint is changed to a warmer temperature NOTE The deadband is restricted to a range of 5 to 9 if ISU 0380 is set to Integrated Temperature and Humidity Control ITHC Backlit Display When c...

Страница 18: ...will be displayed when the setpoint is changed in the direction of calling for additional system capacity or the outdoor unit is in Charge AssistTM mode Wait indicates system time delays are being enf...

Страница 19: ...isable any blower off delays and disable continuous fan mode when the indoor humidity is above the dehumidification setpoint This will help prevent coil condensation from being evaporated back into th...

Страница 20: ...e the Comfort Control by 1 Choose Heat Pump Application in Installer Setup Number 0172 2 Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200 3 Outdoor Temperature Sensor...

Страница 21: ...610 are 60 F 99 F 15 5 C 32 2 C 2 Unlock keypad ISU 0670 Room temperature overshoots when the Heat Cool setting is changed more than 2 degrees 1 Oversized heating cooling equipment under current condi...

Страница 22: ...rates ISU 0220 0230 Heating cycle too fast or too slow narrow or wide temperature swing The location of the control and or the size of the heating system may be influencing the cycle rate Verify adju...

Страница 23: ...ACONT900AC43UA Pub No 11 HD04D1 2 23 69 2080 05...

Страница 24: ...American Standard Heating Air Conditioning Troup Highway Tyler TX 75711 9010 Pub No 11 HD04D1 2 69 2080 05 M S Rev 11 08 U S Registered Trademark 2008 American Standard Heating Air Conditioning All R...

Отзывы: