ACONT900AC43UA

Pub. No. 11-HD04D1-2

69-2080—05

10

Dual Fuel Heat Pump 
Control

0345

1

0, 1, 2

0 - Compressor lockout 
only
1 - Heat Pump Compressor 
lockout and failed to 
maintain heat protection
2 - Heat Pump Compressor 
lockout and Auxiliary Heat 
lockout and Failed to 
maintain heat protection in 
between. To access aux 
heat lockout, select option 
2.

If compressor is “Failing to 
maintain heat”, revert to aux 
heater above balance point.

Dual Fuel Heat Pump 
Upstage to Furnace 
Timer

0346

60

0, 30, 45, 
60, 75

0 - Disabled
30 - 30 minutes
45 - 45 minutes
60 - 60 minutes
75 - 75 minutes

System will switch to gas 
furnace to satisfy call for 
heat if second stage 
compressor timer expires.

Heat Pump 
Compressor Lockout 
Outdoor Temperature

0350

0,
40 (dual 
fuel)

0, 5 - 60

0 - No compressor lockout
5 - 5°F (-15.0°C)
10 - 10°F (-12.0°C)
15 - 15°F (-9.5°C)
20 - 20°F (-6.5°C)
25 - 25°F (-4.0°C)
30 - 30°F (-1.0°C)
35 - 35°F (1.5°C)
40 - 40°F (4.5°C)
45 - 45°F (7.0°C)
50 - 50°F (10.0°C)
55 - 55°F (13.0°C)
60 - 60°F (15.5°C)

System will switch to gas 
furnace to satisfy call for 
heat if the highest 
compressor stage, 
continuous-run timer 
expires.

Auxiliary Heat 
Lockout Outdoor 
Temperature

0360

0

0, 5 - 65

0 - No auxiliary heat 
lockout
5 - 5°F (-15.0°C)
10 - 10°F (-12.0°C)
15 - 15°F (-9.5°C)
20 - 20°F (-6.5°C)
25 - 25°F (-4.0°C)
30 - 30°F (-1.0°C)
35 - 35°F (1.5°C)
40 - 40°F (4.5°C)
45 - 45°F (7.0°C)
50 - 50°F (10.0°C)
55 - 55°F (13.0°C)
60 - 60°F (15.5°C)
65 - 65°F (18.5°C)

Not available for dual fuel 
unless option 2 is selected 
in ISU#0345. Default will be 
50 in this case.

1st Stage Heater 
Defrost Balance 
Point

0361

0

0, 5 - 55

0 - Disabled
5 - 5°F (-15.0°C)
10 - 10°F (-12.0°C)
15 - 15°F (-9.5°C)
20 - 20°F (-6.5°C)
25 - 25°F (-4.0°C)
30 - 30°F (-1.0°C)
35 - 35°F (1.5°C)
40 - 40°F (4.5°C)
45 - 45°F (7.0°C)
50 - 50°F (10.0°C)
55 - 55°F (13.0°C)

Only shown if outdoor 
temperature is available.

Table 4. Installer Setup Menu

Selection

Installer Setup 

Number (ISU)

Factory 

Setting

Choices

Comments

Option

Description

Содержание ACONT900AC43UA

Страница 1: ...al fuel systems via digital 2 way communications The Comfort Control will communicate with and identify all AccuLinkTM components in the system It is easily manually configured via the user friendly I...

Страница 2: ...150 F 34 4 C 65 6 C 5 90 RH non condensing Operating Temperature Range 0 F 120 F 17 8 C 37 2 C 5 90 RH non condensing System Mode Heat Cool Auto Emergency Heat and Off Fan Mode On Auto and Circ Coolin...

Страница 3: ...Control from the subbase to expose mounting holes 4 Position and level the sub base wallplate for appearance only The Comfort Control functions properly even when not level 5 Use a pencil to mark the...

Страница 4: ...Stage Cooling Unit B BK Y2 Y1 O R D W1 W3 G W2 B D B R D X2 Y2 Y1 O COMFORT CONTROL 24VAC HOT 24VAC Common DATA INDOOR UNIT OUTDOOR UNIT COM COM COM LOW VOLTAGE WIRING TO BE NO 18 AWG MINIMUM CONDUCT...

Страница 5: ...received during Discovery mode NOTE While in Discovery mode the LED indicator located in the upper right corner of the Comfort Control will be illuminated NOTE All discovered values will be saved int...

Страница 6: ...See Figure 5 Fig 5 Clock Activation NOTE If the system is not powered the Real Time Clock battery life is approximately 20 weeks The Comfort Control is designed to automatically keep the current time...

Страница 7: ...y to exit the Installer Setup screen NOTE Manually changing an ISU setting to an option other than E disables Discovery mode for that ISU setting If power is lost all custom settings are retained in t...

Страница 8: ...minimum of 1H or 1C is required Fan Operation 0180 E E 0 1 E Auto Discover 0 Equipment controls fan operation in heat mode fossil 1 Comfort Control controls fan operation in heat mode electric Only se...

Страница 9: ...ight comes on with a key press 1 Backlit is on continuously Comfort Control backlight will come on full brightness with a key press and display will dim 45 seconds after the last keypress Changeover 0...

Страница 10: ...0 F 6 5 C 25 25 F 4 0 C 30 30 F 1 0 C 35 35 F 1 5 C 40 40 F 4 5 C 45 45 F 7 0 C 50 50 F 10 0 C 55 55 F 13 0 C 60 60 F 15 5 C System will switch to gas furnace to satisfy call for heat if the highest c...

Страница 11: ...alled For future use Leave at factory default setting E Indoor Humidity Sensor 0370 1 0 1 2 0 Disabled 1 Internal sensor 2 Remote sensor Indoor Humidification Control 0372 E 0 E 0 1 2 E Auto Discover...

Страница 12: ...ous days 12 120 continuous days 13 180 continuous days 14 365 continuous days When set to Auto Discover and the discovered value is not 0 disabled the Comfort Control will display the filter timer val...

Страница 13: ...rnal timer simply press the More key to access the filter timer value and then press the Reset key Humidifier Pad Replacement Reminder 0510 E 0 E 0 3 E Auto Discover 0 Disabled 1 90 continuous days 30...

Страница 14: ...e V S only 5 5 seconds 10 10 seconds 20 20 seconds 30 30 seconds For Variable Speed indoor units choices are 0 and 1 For Non variable Speed indoor units choices are 0 5 10 20 and 30 Compressor Cool Fa...

Страница 15: ...on Circ Circulation control will provide a variable circulation determined by the Adaptive Intelligent Circulation AIC algorithm running the fan between 20 and 60 of the time Temperature Control in Co...

Страница 16: ...2D2 1 69 2009 for a listing of all equipment Alert codes Equipment Damage Hazard Minimum compressor off time is bypassed during Installer System Test Avoid cycling compressor quickly Observe compresso...

Страница 17: ...e Heating setpoint is changed to a warmer temperature NOTE The deadband is restricted to a range of 5 to 9 if ISU 0380 is set to Integrated Temperature and Humidity Control ITHC Backlit Display When c...

Страница 18: ...will be displayed when the setpoint is changed in the direction of calling for additional system capacity or the outdoor unit is in Charge AssistTM mode Wait indicates system time delays are being enf...

Страница 19: ...isable any blower off delays and disable continuous fan mode when the indoor humidity is above the dehumidification setpoint This will help prevent coil condensation from being evaporated back into th...

Страница 20: ...e the Comfort Control by 1 Choose Heat Pump Application in Installer Setup Number 0172 2 Choose Fossil Fuel Option as the backup heat source in Installer Setup Number 0200 3 Outdoor Temperature Sensor...

Страница 21: ...610 are 60 F 99 F 15 5 C 32 2 C 2 Unlock keypad ISU 0670 Room temperature overshoots when the Heat Cool setting is changed more than 2 degrees 1 Oversized heating cooling equipment under current condi...

Страница 22: ...rates ISU 0220 0230 Heating cycle too fast or too slow narrow or wide temperature swing The location of the control and or the size of the heating system may be influencing the cycle rate Verify adju...

Страница 23: ...ACONT900AC43UA Pub No 11 HD04D1 2 23 69 2080 05...

Страница 24: ...American Standard Heating Air Conditioning Troup Highway Tyler TX 75711 9010 Pub No 11 HD04D1 2 69 2080 05 M S Rev 11 08 U S Registered Trademark 2008 American Standard Heating Air Conditioning All R...

Отзывы: