Pub. No.  11-HD03D1-3

7

Installer’s Guide

Features

Cycle Rate

The selected number of system cycles per hour. If the cycle
rate were set to 3, each cycle would be 20 minutes long. The
total  ON and/or OFF  times depends on actual indoor space
load. A shorter cycle rate (more cycles per hour) may be
desired for Heating in order to maintain a tighter control on
indoor setpoint. A longer cycle rate may be desirable for
Cooling so the system has the opportunity to remove
moisture from the air and improve indoor comfort.

Auto Changeover

 When the system mode is set to AUTO, the control automati-

cally switches between heating and cooling modes to
maintain the desired comfort level.

Setpoint Deadband

 The number of degrees separating Heating and Cooling

setpoints. The amount of separation between mode
setpoints is user defined between 2 and 10 degrees. When
the control is set to Auto, and the cooling setpoint is
changed to a cooler setting, the heating setpoint also
changes to maintain the selected degrees separation. The
same action occurs when the heating setpoint is changed to
a warmer temperature.

Backlit Display & Keys

The liquid crystal display and the keypad will illuminate
whenever a keypad button  is pressed to improve control
visibility.  The back light stays on for 10 seconds after the
last key press.

Cooling Droop

Cooling Droop is an automatic function that cycles the
compressor on to improve indoor comfort by removing
moisture from the air. The Droop cycle is activated when
temperature is at or below the cooling  temperature
setpoint. When this function is active, the control will
control temperature at 1 or 2 degrees below cooling
setpoint. The Droop cycle is deactivated when the tempera-
ture rises above the cooling setpoint.

Energy Savings

The Energy Savings mode provides instant energy savings
by offsetting the indoor setpoint to a cooler temperature
setting for heating and a warmer temperature setting for
cooling.

The Energy Savings mode is activated by pressing  the
Energy Savings key  “$” on the controls keypad. Pressing
the Energy Savings key  “$” again deactivates the Energy
Savings mode. Pressing and holding the Energy Savings
key  “$” provides quick access to the setpoint offset for both
heating and cooling.

Filter Reminder

FILTER”

 will automatically flash to remind the home-

owner that its time to change the filter once the preset time
has expired. Pressing the “Filter” keypad button automati-
cally resets the internal clock timer. Once the timer has
been reset,  the number of days remaining  till the next
filter change can easily be determined by simply pressing
the “Filter” keypad button. Pressing and holding the
“Filter” keypad button provides quick access to the filter
timer value.

Keypad Lock

Locking the control’s keypad can help prevent unwanted
tampering  or changing the thermostat settings by pressing
the controls UP and DOWN arrow keypad buttons at the
same time and holding for 2 seconds.  “Keypad Locked”  will
be displayed on the LCD. Repeating this combination
unlocks the keypad and the “Keypad Locked” will disap-
pear.

Business Card Drawer

The drawer attached to the mounting base of the control is
designed to provide a convenient location for the home
owner to locate their local servicer. A standard business
card can be folded and inserted into the slot on the drawer
to remind the User whom to call when service is required.

LitePort

LitePort is a patented feature that allows the servicer
access to extended real-time and history data events stored
in the thermostat’s memory.

Manual Test Mode

The built-in Manual Test Mode allows the servicer to
quickly and easily test the control’s individual control
outputs and makes diagnostic procedures a snap.
Set the Mode to OFF, set the Fan to AUTO, and press the
MODE and DOWN arrow keypad buttons at the same time
and hold for 2 seconds. See Table 1, steps 70-78 for details.

Default Factory Settings

The thermostat is shipped with a set of factory default
settings. The factory default settings can be restored at any
time using the control configuration menu. See Table 2,
step 99.

Service Indicator

The

 “SERVICE”

  indicator automatically flashes when an

internal fault or error has been detected by the thermostat.

Minimum Off Time Delay Override

Minimum Off time delays can be overridden for the current
cycle by pressing the Mode and Down arrow keys at the
same time for approximately 2 seconds. It may be neces-
sary to lower the indoor setpoint for cooling or increase the
setpoint for heating to activate the system. Minimum off
time delays will be enforced on the next cycle.

Wait Indicator

“Waiting”  will illuminate when the indoor setpoint is
moved in the direction of calling for additional system
capacity.  “Waiting” indicates system time delays are being
enforced and that the control is adjusting to the new
settings.

Calibrate Indoor Temperature

This option allows calibration (or deliberate miscalibration)
of the room temperature sensor. The selected number is
number of degrees, plus or minus, which will be added to
actual temperature. The number can range b 5
and - 5 degrees in 1/2 degree increments. Factory default is
0. This adjusted value will be used as actual temperature
for both display and control action. For example, if 2 is
selected, 72 degrees actual will read 74 degrees.

Control Response Rate

A set of higher gain Proportional-Integral control constants
can be chosen to increase the responsiveness of the tem-
perature control performance.

Содержание ACONT200AN11AA

Страница 1: ...NG and CAUTION These words are used with the safety alert symbol DANGER indentifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which could result in minor personal injury or product and prop erty damage Note Read the entire instruction manual bef...

Страница 2: ...ed Make sure all wires extend through hole in mounting base 7 Adjust length and routing of each wire to reach proper terminal on the connector block on mounting base Strip only 1 4 in of insulation from each wire to prevent adjacent wires from shorting together when connected 8 Match and connect control wires to proper terminals on the connector block See Figures 3 8 Two 360 ohm resistors 5 watts ...

Страница 3: ...esistor is required on Y to B at the indoor unit low voltage terminal block when outdoor unit contactor coil is not directly connected to Y or if a compressor anti short cycle timer has been installed B C SINGLE STAGE AIR HANDLER Figure 5 R G Y W R G W Y 24VAC HOT COMFORT CONTROL TERMINAL BLOCK SINGLE STAGE AIR HANDLER W ELECTRIC HEAT NO OUTDOOR UNIT FAN COOLING HEATING 360 ohm 5 watt Resistors Re...

Страница 4: ... 50 for option details 1 Set System Mode to OFF 2 Set Fan to AUTO 3 Press and hold Mode and Up Arrow at the same time 4 SET UP will appear on display See Figure 9 Enter USER Setup See Table 2 steps 40 49 for option details Press and hold Mode and Fan at the same time Note Allow a minimum of 5 seconds after saving selections Step 99 SA for the control to write selections to memory If power is lost ...

Страница 5: ... alendar D ays 1 Fan R un Tim e D ays 47 C ooling C ycle Fan O FF D elay 0 0 90 Seconds 16 Indoor Filter R em inder D ays 30 1 180 D ays 0 D isable 48 C om pressor C ooling C ycles Per H our 3 2 6 C ycles per H our 19 C alibrate Indoor Tem perature 0 C alibrated R oom Tem perature 5 D egrees 1 2 degree increm ents 49 C om pressor C ooling C ycle M inim um O n Tim e M inutes 3 2 4 C PH 1 15 M inute...

Страница 6: ... to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or system 4 Heating system requires service or control requires replacement 1 Set Mode to heat and raise the setpoint above room temperature 2 If heating does not come on within 5 minutes Check Heating 3 Check Repair connections 4 Repair system Replace control Cooling will not come on 1 System Mode not set to Cool 2 Min...

Страница 7: ...nd holding the Filter keypad button provides quick access to the filter timer value Keypad Lock Locking the control s keypad can help prevent unwanted tampering or changing the thermostat settings by pressing the controls UP and DOWN arrow keypad buttons at the same time and holding for 2 seconds Keypad Locked will be displayed on the LCD Repeating this combination unlocks the keypad and the Keypa...

Страница 8: ...ericanStandardHeating AirConditioninghasa policyofcontinuousproductandproductdataimprovement it reserves the right to change specifications and design withoutnotice American Standard Heating Air Conditioning 6200 Troup Highway Tyler TX 75707 Notes ...

Отзывы: