![American Standard ACONT200AN11AA Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/american-standard/acont200an11aa/acont200an11aa_installers-manual_2929800004.webp)
4
Pub. No. 11-HD03D1-3
Installer’s Guide
Figure 9
The manual test mode allows the installer to energize the G
fan relay , Table 1, Step 70, and then advance to Step 72 to
energize the Y compressor output with the fan still operating.
It is recommended that this method be used to prevent
damage to the compressor.
The Manual test mode will time out and return to normal
operation after 1 minute from the last key press.
Checkout
There are two methods of verifying that the Comfort Control
operates the system as intended.
Method 1: Normal Mode
This can be accomplished by pressing the appropriate
keypad button(s) to cycle the system through each of the
available modes and increasing or decreasing the
setpoint to activate and deactivate the cycle.
The minimum on and off cycle time delays, selected
during the setup, will be enforced. Press the appropriate
keypad button for the filter timer and energy savings
features to verify they are set to the end user’s desired
preference.
Method 2: Manual Test Mode
TheComfort Control’s load outputs can be verified using
the manual test mode. See Table 1 for navigating
through the manual test mode steps.
To Enter The Manual Test Mode:
1.) Set System Mode to OFF
2.) Set Fan to AUTO
3.) Press and hold Mode and Down Arrow at the same
time.
SETUP
Enter INSTALLER Setup:
(See Table 2, steps 1-50 for option details)
1.) Set System Mode to OFF
2.) Set Fan to AUTO
3.) Press and hold Mode and Up Arrow at the same time.
4.) SET-UP will appear on display. See Figure 9.
Enter USER Setup:
(See Table 2, steps 40-49 for option details)
Press and hold Mode and Fan at the same time.
Note: Allow a minimum of 5 seconds after saving selections
(Step 99 - SA) for the control to write selections to memory.
If power is lost or removed prior to the 5 second elapsed
time, the selections may be lost and must be reentered. If
the SERVICE icon is flashing on the control LCD, press any
key and check / reenter setup choices.
Keypad Navigation:
Use the Mode and Fan buttons to navigate forward and
backward through the configuration and Manual Test Mode
steps.
Press Mode to advance forward to the next step.
Press Fan to return to the previous step.
Use the Up and Down arrow buttons to select or change
setup options.
Lock - Unlock Keypad:
Press and hold Up Arrow and Down Arrow at the same time.
(“Keypad Locked” icon will display on LCD screen)
Defeat Equipment Time Delay:
(Current Cycle only) Press Mode and Down Arrow at the same
time.
Table 1 Manual Test Mode
Menu Item
(Press MODE or FAN)
Default
Setting (Choices)
(Press Up or Down
arrow)
Step
(Press MODE
or FAN)
G - Fan Relay
"G"
"G"
"G"
"G"
Off
On/Off
70
Y -
Compressor
Contactor
(G - must be
ON)
"Y"
"Y"
"Y"
"Y"
Off
On/Off
72
W - Heating
relay
"Ui"
"Ui"
"Ui"
"Ui"
Off
On/Off
75
LCD
"SC"
"SC"
"SC"
"SC"
----
All icons On (See Fig.
8)
All icons Off
78
Factory Use
Only
Press and hold MODE to advance to step
80 and press "$" Energy Savings key to
exit.
79-82