Installer’s Guide

Figure 9

The manual test mode allows the installer to energize the G
fan relay , Table 1, Step 70, and then advance to Step 72 to
energize the Y compressor output with the fan still operating.
It is recommended that this method be used to prevent
damage to the compressor.

The Manual test mode will time out and return to normal
operation after 1 minute from the last key press.

Checkout

There are two methods of verifying that the Comfort Control
operates the system as intended.

Method 1:  Normal Mode

This can be accomplished by pressing the appropriate
keypad button(s) to cycle the system through each of the
available modes and  increasing or decreasing the
setpoint to activate and deactivate the cycle.
The minimum on and off cycle time delays, selected
during the setup, will be enforced. Press the appropriate
keypad button for the filter timer and energy savings
features to verify they are set to the end user’s desired
preference.

Method 2:  Manual Test Mode

TheComfort Control’s load outputs can be verified using
the manual test mode.  See Table 1 for navigating
through the manual test mode steps.

 To Enter The Manual Test Mode:

1.) Set System Mode to OFF

2.) Set Fan to AUTO

3.) Press and hold Mode and Down Arrow at the same

time.

SETUP

Enter INSTALLER Setup:

(See Table 2, steps 1-50 for option details)

1.) Set System Mode to OFF

2.) Set Fan to AUTO

3.) Press and hold Mode and Up Arrow at the same time.

4.) SET-UP will appear on display. See Figure 9.

Enter USER Setup:

(See Table 2, steps 40-49 for option details)

Press and hold Mode and Fan at the same time.

Note:  Allow a minimum of 5 seconds after saving selections
(Step 99 - SA) for the control to write selections to memory.
If power is lost or removed prior to the 5 second elapsed
time, the selections may be lost and must be reentered. If
the SERVICE icon is flashing on the control LCD, press any
key and check / reenter setup choices.

Keypad Navigation:

Use the Mode and Fan buttons to navigate forward and
backward through the configuration and Manual Test Mode
steps.
Press Mode to advance forward to the next step.
Press Fan to return to the previous step.

Use the Up and Down arrow buttons to select or change
setup options.

Lock - Unlock Keypad:

Press and hold Up Arrow and Down Arrow at the same time.

(“Keypad Locked” icon will display on LCD screen)

Defeat Equipment Time Delay:

(Current Cycle only) Press Mode and Down Arrow at the same

time.

Table 1                           Manual Test Mode

Menu Item

(Press MODE or FAN)

Default

Setting (Choices)

(Press Up or Down

arrow)

Step

(Press MODE

or FAN)

G - Fan Relay

"G"

"G"

"G"

"G"

Off

On/Off

70

Y -
Compressor

Contactor 
(G - must be
ON)

"Y"

"Y"

"Y"

"Y"

Off

On/Off

72

W - Heating

relay

"Ui"

"Ui"

"Ui"

"Ui"

Off

On/Off

75

LCD

"SC"

"SC"

"SC"

"SC"

----

All icons On (See Fig.

8)

All icons Off

78

Factory Use
Only

Press and hold MODE to advance to step

80 and press "$" Energy Savings key to
exit.

79-82

Содержание ACONT200AN11AA

Страница 1: ...NG and CAUTION These words are used with the safety alert symbol DANGER indentifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which could result in minor personal injury or product and prop erty damage Note Read the entire instruction manual bef...

Страница 2: ...ed Make sure all wires extend through hole in mounting base 7 Adjust length and routing of each wire to reach proper terminal on the connector block on mounting base Strip only 1 4 in of insulation from each wire to prevent adjacent wires from shorting together when connected 8 Match and connect control wires to proper terminals on the connector block See Figures 3 8 Two 360 ohm resistors 5 watts ...

Страница 3: ...esistor is required on Y to B at the indoor unit low voltage terminal block when outdoor unit contactor coil is not directly connected to Y or if a compressor anti short cycle timer has been installed B C SINGLE STAGE AIR HANDLER Figure 5 R G Y W R G W Y 24VAC HOT COMFORT CONTROL TERMINAL BLOCK SINGLE STAGE AIR HANDLER W ELECTRIC HEAT NO OUTDOOR UNIT FAN COOLING HEATING 360 ohm 5 watt Resistors Re...

Страница 4: ... 50 for option details 1 Set System Mode to OFF 2 Set Fan to AUTO 3 Press and hold Mode and Up Arrow at the same time 4 SET UP will appear on display See Figure 9 Enter USER Setup See Table 2 steps 40 49 for option details Press and hold Mode and Fan at the same time Note Allow a minimum of 5 seconds after saving selections Step 99 SA for the control to write selections to memory If power is lost ...

Страница 5: ... alendar D ays 1 Fan R un Tim e D ays 47 C ooling C ycle Fan O FF D elay 0 0 90 Seconds 16 Indoor Filter R em inder D ays 30 1 180 D ays 0 D isable 48 C om pressor C ooling C ycles Per H our 3 2 6 C ycles per H our 19 C alibrate Indoor Tem perature 0 C alibrated R oom Tem perature 5 D egrees 1 2 degree increm ents 49 C om pressor C ooling C ycle M inim um O n Tim e M inutes 3 2 4 C PH 1 15 M inute...

Страница 6: ... to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or system 4 Heating system requires service or control requires replacement 1 Set Mode to heat and raise the setpoint above room temperature 2 If heating does not come on within 5 minutes Check Heating 3 Check Repair connections 4 Repair system Replace control Cooling will not come on 1 System Mode not set to Cool 2 Min...

Страница 7: ...nd holding the Filter keypad button provides quick access to the filter timer value Keypad Lock Locking the control s keypad can help prevent unwanted tampering or changing the thermostat settings by pressing the controls UP and DOWN arrow keypad buttons at the same time and holding for 2 seconds Keypad Locked will be displayed on the LCD Repeating this combination unlocks the keypad and the Keypa...

Страница 8: ...ericanStandardHeating AirConditioninghasa policyofcontinuousproductandproductdataimprovement it reserves the right to change specifications and design withoutnotice American Standard Heating Air Conditioning 6200 Troup Highway Tyler TX 75707 Notes ...

Отзывы: