18-GE04D2-5

5

Installer’s Guide

HORIZONTAL RIGHT

a. For maximum efficiency and Customer ease of

filter maintenance, it is recommended that a prop-
erly sized remote filter grille be installed for
horizontal applications. Airflow should not exceed
the face velocity of the filter being used. The fac-
tory installed filter should then be removed
from the unit.

b. Unit is shipped from the factory in the upflow or

horizontal right configuration. Unit conversion is
not required.

c. The unit is designed for suspension using 1/4" -

20 threaded rods. Other means of suspension are
allowed as long as the unit is supported from
both ends as well as the middle to prevent sag-
ging and service access is not obstructed.

d. If the unit is not suspended it must be isolated

carefully to prevent sound transmission. Vibra-
tion isolators (purchased locally) must be placed
under the unit.

e. It is always recommended that an auxiliary drain

pan be installed under a horizontal air handler
(See Condensate Drain Piping) to prevent possible
damage to ceilings.

f. Isolate the auxiliary drain pan from the unit or

from the structure.

g. Connect the auxiliary drain line to a separate drain

line (no trap is needed in this line) and terminate
according to local codes.

h. If a return duct is connected to the Air Handler, it

must be the same dimensions as the return opening
shown in the outline drawings.

j. Openings where field wiring enters the cabi-

net must be completely sealed.  Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts and cage nut openings.

C. DUCT CONNECTIONS

The supply and return air ducts should be connected to
the unit with flame retardant duct connectors.

Convertible duct flanges are provided on the discharge
opening to provide a “flush fit” for 3/4" or 1-1/2" duct board
applications, see the Outline drawing on page 10 for sizes
of the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.

NOTE:
If the convertible duct flanges are not used, they must be
removed and discarded for proper airflow.

D. REFRIGERANT PIPING

IMPORTANT:
Refrigerant piping must be routed to maintain service access
to blower compartment and provide easy removal of filter
access panel and filter.

NOTE:

Refrigerant piping must be sealed along with field wiring

1. Refrigerant connections are made outside the cabi-

net.

2. Installation of refrigerant lines is covered in the in-

stallation instructions packaged with the outdoor unit.
Evacuation, leak testing and brazing procedures are
included in those instructions. Read those instruc-
tions before starting installation of refrigerant lines.

NOTE:  TXV Equipped is Non-Bleed, and may require a
start kit on the outdoor unit.

E.  BRAZING TO EVAPORATOR SECTION

IMPORTANT:
Do not unseal refrigerant tubing until ready to cut and fit
refrigerant lines.

Note:
TXV bulb MUST be protected (wrapped with wet rag) or
removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and
performance of the air handler.

NOTE:
A brazing shield is provided in the information pack accom-
panying this unit. This shield fits over the refrigerant fittings
while brazing. Wet the shield before brazing. See Fig. 5.

1. Remove both sealing caps from indoor coil.

2. Field supplied tubing should be cut square, round

and free of burrs at the connecting end. Clean the

BRAZE SHIELD

5

Содержание 4TEE3F31A

Страница 1: ... not cover all variations in systems or provide for every possible contingency Should further in formation be desired or particular problems arise which are not covered sufficiently by this manual contact your local distributor or the manufacturer as listed on the air handler nameplate These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully con...

Страница 2: ...ly in a single story residence within conditioned space 11 If the outdoor unit is to be installed later or by oth ers then installation of the air handler must be This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are sui...

Страница 3: ...pplied nar row coil baffle using the screws removed previ ously See Figure 3 c Position unit on Pedestal or other suitable foundation If Pedestal is not used a frame strong enough to support the total weight must be provided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same dimensions as shown in the ou...

Страница 4: ...here field wiring enters the cabinet must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers to seal all unused electri cal knockouts and cage nut openings HORIZONTAL LEFT a For maximum efficiency and Customer ease of filter maintenance it is recommended that a prop erly sized remote filter and grille be installed for horizontal applications Airflow...

Страница 5: ...NECTIONS The supply and return air ducts should be connected to the unit with flame retardant duct connectors Convertible duct flanges are provided on the discharge opening to provide a flush fit for 3 4 or 1 1 2 duct board applications see the Outline drawing on page 10 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE If the conve...

Страница 6: ...of the two should be connected as a backup to prevent conden sate overflow by a blocked primary drain For proper drainage of condensate the following steps should be followed 1 The primary drain line must be trapped with a minimum of 2 water seal as shown in Figures 7 8 Do not use preformed 3 4 PVC running traps The use of Field fabricated or manufactured traps as shown in Figures 7 8 is acceptabl...

Страница 7: ... FAN OFF DELAY AUXILIARY HEAT SPEEDS 0 OFF OFF 50 80 100 if necessary 50 Dehumidify Fast Coil Cooling and Heating Efficiency 7 5 minutes 3 minutes 1 minute FAN OPERATION CFM COMPRESSOR OPERATION ON OFF as required From Dwg 800796a CFM SELECTION LIGHT DIP SWITCHES ICM FAN CONTROL Figure 9 If an electric heater is not installed connections are made through the 7 8 knockout into the air handler junct...

Страница 8: ...8 18 GE04D2 5 Installer s Guide 4TEE3F AIR HANDLERS WITH SINGLE STAGE COOLING 2 STAGE HEAT 4TEE3F AIR HANDLERS WITH TWO STAGE COOLING 2 STAGE HEAT From Dwg No B801074 ...

Страница 9: ...out door unit size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 10 If the airflow needs to be increased or decreased see the Airflow Label on the air handler or the Blower Per formance Table in the Service Facts Information on changing the speed of the blower motor for your specific outdoor model size is in the Blower P...

Страница 10: ...2 6 12 7 2 E L B A T E C N A R A E L C T I N U M U M I N I M O T E L B I T S U B M O C L A I R E T A M D E R I U Q E R E C I V R E S E C N A R A E L C D E D N E M M O C E R S E D I S 0 2 T N O R F 0 1 2 K C A B 0 0 T C U D T E L N I 0 1 T C U D T E L T U O 1 C I R T C E L E N E H W T C U D T E L T U O F O T F 3 T S R I F E H T R O F 1 8 0 4 1 5 0 4 1 R T H Y A B S L E D O M T P E C X E D E L L A T...

Страница 11: ...0 21 00 1 50 CAGE NUT MOUNTING LOCATION FOR 4TEE3F AIR HANDLERS FOR TWO PIECE CABINET ONLY Model No H W A B 4TEE3F31A 43 00 21 50 17 00 39 00 4TEE3F37A 45 00 23 50 19 00 41 00 4TEE3F40A 51 75 26 00 23 80 47 75 4TEE3F49A 57 90 29 00 53 90 4TEE3F65A 62 75 31 25 58 75 ...

Страница 12: ... power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they must be open and unrestricted 5 Check drain lines and be sure all joints are tight 6 Make sure secondary drain pan is installe...

Отзывы: