Installer’s Guide

AIR HANDLER SUB-BASE

7. When the air handler with supplementary heater is

to be installed in the downflow position on combus-
tible flooring an accessory sub-base (TAYBASE101
for 4TEE3F31, TAYBASE100 for 4TEE3F37,
TAYBASE102 for 4TEE3F40- 065A) must be used.
See Figure 1.

8. If supplementary heat is to be added, power supply

must be sufficient to carry the load. In addition,
minimum air flow settings, unit and duct clearances
to combustible material must be maintained as
stated on the air handler rating nameplate.

CAUTION

!

For air handlers not equipped with a factory installed electric
heater, a field installed heater is available from American
Standard Inc. Only heaters built by American Standard Inc.
are approved for use in the air handler.  These heaters have
been designed and tested in accordance with UL standards
to provide safe and reliable operation. A list of approved
heaters is provided on the air handler rating nameplate.
Heaters that are not factory approved could cause damage
and are not covered under equipment warranty.

NOTE:
If air handler is used WITHOUT a supplementary electric
heater, a sheetmetal plate is required to cover the open hole
in the airflow system. See Figure 2

.

 Also seal the cabinet air

tight where the wire enters.

9. If field installed electric heaters are applied, mini-

mum air flow settings, unit and duct clearances to
combustibles must be maintained as stated on the
air handler rating nameplate.

10. If the unit is installed without a return air duct, ap-

plicable local codes may limit this air handler to in-
stallation only in a single story residence & within
conditioned space.

11. If the outdoor unit is to be installed later, or by oth-

ers, then installation of the air handler must be

This area may also be used for other purposes, includ-
ing an electric hot water heater - but in no case shall
a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.

In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted
supply and return air.

This equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280
or the equivalent. “SUITABLE FOR MOBILE HOME
USE”

For proper installation the following items must be con-
sidered:

1. If adequate power is available and correct according

to nameplate specifications.

2. Pursuant to Florida Building Code 13-610.2.A.2.1,

this unit meets the criteria for a factory sealed
air handler.

3. Insulate all ducts, particularly if unit is located out-

side of the conditioned space.

4. The Refrigerant lines must be sealed and Electri-

cal inlets need to be sealed at both the low and
the high voltage.

5. To ensure maximum efficiency and system perfor-

mance, the existing supply and return duct system
static pressures must not exceed the total available
static pressure of the air handler.  Reference ACCA
Manual D, Manual S and Manual RS along with the
air handler Product Data and Service Facts for addi-
tional information.

6. It is recommended that the outline drawing be stud-

ied and dimensions properly noted and checked
against selected installation site. By noting in ad-
vance which knockouts are to be used, proper clear-
ance allowances can be made for installation and
possible future service.

Figure 1

FLOOR OPENING - SIZE

 MODEL NO.

A

B

 TAYBASE100

23-3/4

14-13/16

 TAYBASE101

21-3/4

14-13/16

 TAYBASE102

26-3/4

14-13/16

Содержание 4TEE3F31A

Страница 1: ... not cover all variations in systems or provide for every possible contingency Should further in formation be desired or particular problems arise which are not covered sufficiently by this manual contact your local distributor or the manufacturer as listed on the air handler nameplate These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully con...

Страница 2: ...ly in a single story residence within conditioned space 11 If the outdoor unit is to be installed later or by oth ers then installation of the air handler must be This area may also be used for other purposes includ ing an electric hot water heater but in no case shall a fossil fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are sui...

Страница 3: ...pplied nar row coil baffle using the screws removed previ ously See Figure 3 c Position unit on Pedestal or other suitable foundation If Pedestal is not used a frame strong enough to support the total weight must be provided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same dimensions as shown in the ou...

Страница 4: ...here field wiring enters the cabinet must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers to seal all unused electri cal knockouts and cage nut openings HORIZONTAL LEFT a For maximum efficiency and Customer ease of filter maintenance it is recommended that a prop erly sized remote filter and grille be installed for horizontal applications Airflow...

Страница 5: ...NECTIONS The supply and return air ducts should be connected to the unit with flame retardant duct connectors Convertible duct flanges are provided on the discharge opening to provide a flush fit for 3 4 or 1 1 2 duct board applications see the Outline drawing on page 10 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE If the conve...

Страница 6: ...of the two should be connected as a backup to prevent conden sate overflow by a blocked primary drain For proper drainage of condensate the following steps should be followed 1 The primary drain line must be trapped with a minimum of 2 water seal as shown in Figures 7 8 Do not use preformed 3 4 PVC running traps The use of Field fabricated or manufactured traps as shown in Figures 7 8 is acceptabl...

Страница 7: ... FAN OFF DELAY AUXILIARY HEAT SPEEDS 0 OFF OFF 50 80 100 if necessary 50 Dehumidify Fast Coil Cooling and Heating Efficiency 7 5 minutes 3 minutes 1 minute FAN OPERATION CFM COMPRESSOR OPERATION ON OFF as required From Dwg 800796a CFM SELECTION LIGHT DIP SWITCHES ICM FAN CONTROL Figure 9 If an electric heater is not installed connections are made through the 7 8 knockout into the air handler junct...

Страница 8: ...8 18 GE04D2 5 Installer s Guide 4TEE3F AIR HANDLERS WITH SINGLE STAGE COOLING 2 STAGE HEAT 4TEE3F AIR HANDLERS WITH TWO STAGE COOLING 2 STAGE HEAT From Dwg No B801074 ...

Страница 9: ...out door unit size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 10 If the airflow needs to be increased or decreased see the Airflow Label on the air handler or the Blower Per formance Table in the Service Facts Information on changing the speed of the blower motor for your specific outdoor model size is in the Blower P...

Страница 10: ...2 6 12 7 2 E L B A T E C N A R A E L C T I N U M U M I N I M O T E L B I T S U B M O C L A I R E T A M D E R I U Q E R E C I V R E S E C N A R A E L C D E D N E M M O C E R S E D I S 0 2 T N O R F 0 1 2 K C A B 0 0 T C U D T E L N I 0 1 T C U D T E L T U O 1 C I R T C E L E N E H W T C U D T E L T U O F O T F 3 T S R I F E H T R O F 1 8 0 4 1 5 0 4 1 R T H Y A B S L E D O M T P E C X E D E L L A T...

Страница 11: ...0 21 00 1 50 CAGE NUT MOUNTING LOCATION FOR 4TEE3F AIR HANDLERS FOR TWO PIECE CABINET ONLY Model No H W A B 4TEE3F31A 43 00 21 50 17 00 39 00 4TEE3F37A 45 00 23 50 19 00 41 00 4TEE3F40A 51 75 26 00 23 80 47 75 4TEE3F49A 57 90 29 00 53 90 4TEE3F65A 62 75 31 25 58 75 ...

Страница 12: ... power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they must be open and unrestricted 5 Check drain lines and be sure all joints are tight 6 Make sure secondary drain pan is installe...

Отзывы: