4A-V8-SF-1G-EN
11
Charging: Weigh-In Method
Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when
power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the
subcooling charging method.
Table 2. Heat Pumps
A
B
C
D
Model
Factory
Charge
Charge
adder for
Indoor Coil
Charge
multiplier for
interconnecting
refrigerant tube
length
024
7 lb.
6 oz.
6 oz.
0.6 oz/ft
036
8 lb.
3 oz.
8 oz.
0.6 oz/ft
037
9 lb.
8 oz.
12 oz.
0.6 oz/ft
048
9 lb.
13 oz.
13 oz.
0.6 oz/ft
049
10 lb.
12 oz.
15 oz.
0.6 oz/ft
060
11 lb.
14 oz.
1 lb., 2 oz.
0.6 oz/ft
Table 3. Air Conditioners
A
B
C
D
Model
Factory
Charge
Charge
adder for
Indoor Coil
Charge
multiplier for
interconnecting
refrigerant
tube length
024
7 lb.
6 oz.
6 oz.
0.6 oz/ft
036
7 lb.
14 oz.
7 oz.
0.6 oz/ft
037
9 lb.
6 oz.
12 oz.
0.6 oz/ft
048
11 lb.
1 oz.
1 lb., 0 oz.
0.6 oz/ft
060
11 lb.
14 oz.
1 lb., 2 oz.
0.6 oz/ft
Table 4. New Installations — Calculating Charge using the Weigh-In method
1. Measure in feet the distance between the outdoor unit and the indoor
unit and record on Line 1. Include the entire length of the line from the
service valve to the IDU.
2. Enter the charge multiplier from Column D.
3. Multiply the total length of refrigerant tubing (Line 1) times the value on
Step 2. Record the result on Line 3 of the Worksheet.
4. Locate the outdoor equipment size in Column A. Record the value shown
in Column C of Table 16 for Heat Pumps or Table 17 for Air Conditioners.
5. Add the values from Step 3 and Step 4 and record the resulting value.
This is the amount of refrigerant to weigh-in prior to opening the service
valves.
New Installation Weigh-In Method Worksheet
1. Line Length (ft)
________________________
2. Value from Column D
x ________________________
3. Step 1 x Step 2
= ________________________
4. Charge Adder (column C) + ________________________
5. Refrigerant (Steps 3+4)
= ________________________
Table 5. Sealed-System Repairs — Calculating Charge using the Weigh-In method.
1. Measure in feet the distance between the outdoor unit and the indoor
unit and record on Line 1. Include the entire length of the line from the
service valve to the IDU.
2. Enter the charge multiplier from Column D.
3. Multiply the total length of refrigerant tubing (Line 1) times the value on
Line 2. Record the result on Line 3 of the Worksheet.
4. Locate the outdoor equipment size in Column A. Record the value shown
in Column C of Table 16 for Heat Pumps or Table 17 for Air Conditioners.
5. Record the value in Column B to Line 5 of the Worksheet.
6. Add the values from Step 3, Step 4, and Step 5 and record the resulting
value on Line 6. This is the amount of refrigerant to weigh-in.
New Installation Weigh-In Method Worksheet
1. Line Length (ft)
________________________
2. Value from Column D
x ________________________
3. Step 1 x Step 2
= ________________________
4. Charge Adder (column C)
+ ________________________
5. Factory Charge (column B) + ________________________
6. Refrigerant (Steps 3+4+5) = ________________________
Note:
The only mode approved for setting or validating system charge is using Charging Mode-Cooling. Charging Mode-Cooling is a variable
speed test mode found in the 850/950 comfort control Technician Menu. Outdoor Temperature must be between 55
°F and 120°F with
Indoor Temperature kept between 70
°F and 80°F.
Содержание 4A6V8024A1000B
Страница 12: ...12 4A V8 SF 1G EN Wiring D157619P04...
Страница 41: ...4A V8 SF 1G EN 41 Communication Loss Yes Yes No Yes No No Yes No...
Страница 42: ...42 4A V8 SF 1G EN Breaker Trip Procedure...
Страница 43: ...4A V8 SF 1G EN 43 Start Compressor...
Страница 44: ...44 4A V8 SF 1G EN Compressor Verification Parameters...
Страница 45: ...4A V8 SF 1G EN 45 Run Drive Diagnostic Test e t...
Страница 46: ...46 4A V8 SF 1G EN Compressor Verification Short...
Страница 47: ...4A V8 SF 1G EN 47 Compressor Verification Open No Yes...
Страница 48: ...48 4A V8 SF 1G EN Inverter Temperature e e...
Страница 52: ...52 4A V8 SF 1G EN T Te ec ch hn ni ic ci ia an n M Mo on ni it to or r M Me en nu u...
Страница 57: ...4A V8 SF 1G EN 57 T Te ec ch hn ni ic ci ia an n C Co on nt tr ro ol l M Me en nu u...
Страница 58: ...58 4A V8 SF 1G EN TECH CONTROL Charge Check Charge Modes...
Страница 59: ...4A V8 SF 1G EN 59 Pressure Curves Figure 20 4A6V8024A...
Страница 60: ...60 4A V8 SF 1G EN Figure 21 4A6V8036A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 61: ...4A V8 SF 1G EN 61 Figure 22 4A6V8037A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 62: ...62 4A V8 SF 1G EN Figure 23 4A6V8048A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 63: ...4A V8 SF 1G EN 63 Figure 24 4A6V8049A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 64: ...64 4A V8 SF 1G EN Figure 25 4A6V8060A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 65: ...4A V8 SF 1G EN 65 Figure 26 4A7V8024A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 66: ...66 4A V8 SF 1G EN Figure 27 4A7V8036A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 68: ...68 4A V8 SF 1G EN Figure 29 4A7V8048A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 69: ...4A V8 SF 1G EN 69 Figure 30 4A7V8060A P Pr re es ss su ur re e C Cu ur rv ve es s...
Страница 73: ...4A V8 SF 1G EN 73 N No ot te es s...
Страница 74: ...74 4A V8 SF 1G EN N No ot te es s...
Страница 75: ...4A V8 SF 1G EN 75 N No ot te es s...