Installer’s Guide

C. UNIT INSTALLATION

UPFLOW

a. For maximum efficiency, the horizontal drip

tray should be removed. See Figures 5, 6  and 7.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. There is a coil support tab at the top of the
coil connected to the case must be removed first.
Remove 1 inch insulation strip covering the lip of
the drip tray. The tray is detached by removing
the two screws at the drain pan. Remove the two
screws holding the two brackets at the top of the
coil. Remove drip tray by gently breaking the
seal between the drip tray and drain pan.

b. Remove the factory installed baffle assembly

from the apex of the coil by using a 5/16"
nutdriver to remove the screw. Replace this
baffle with the factory supplied narrow coil baffle
using the screws removed previously. See Figure
10. Reinstall coil assembly.

CAUTION

!

When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.

c. Position unit on Pedestal or other suitable foun-

dation. If Pedestal is not used, a frame strong
enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches for
proper unrestricted airflow.

d. If a return air duct is connected to the air han-

dler, it must be the same dimensions as shown in
the outline drawing on page 13.

e. Pedestal and unit should be isolated from the

foundation using a suitable isolating material.

f. Openings where field wiring enters the

cabinet must be completely sealed. Location
of power entry is shown on the Outline Drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 8.

g. After ductwork connections are made, seal air-

tight and per Local codes.

DOWNFLOW

a. For maximum efficiency, the horizontal drip

tray should be removed. See Figures 5, 6 and 7.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. There is a coil support tab at the top of the
coil connected to the case must be removed first.
Remove 1 inch insulation strip covering the lip of
the drip pan. The tray is detached by removing
the two screws at the drain pan and the two
screws holding the two brackets at the top of the
coil. Remove drip tray by gently breaking the
seal between the drip tray and drain pan.

Figure 5 Drip Pan Foam Removal

Figure 7 Drip Pan Bracket Removal

Figure 6 Horitzontal Drip Pan Removal

Содержание 2TEE3F62A1000A

Страница 1: ...or or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or h...

Страница 2: ...aintained as stated on the air handler rating nameplate 10 If the unit is installed without a return air duct ap plicable local codes may limit this air handler to in stallation only in a single story...

Страница 3: ...ater or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 12 Make sure there are provisions...

Страница 4: ...enough to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same d...

Страница 5: ...tab i When supplementary heaters are used accessory subbase TAYBASE102 for 2 4TEE3F62 must be used See Figure 1 j If a return duct is connected to the air handler it must be the same dimensions as th...

Страница 6: ...n on the outline drawing Use 2 5 clear stickers provided to seal all unused electrical knockouts See Figure 8 k After ductwork connections are made seal air tight and per Local codes HORIZONTAL RIGHT...

Страница 7: ...outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers provided to seal all unused...

Страница 8: ...tion is the primary drain See Figure 14 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection Figure 14 BRAZE SHIELD Figure 13 Two secondary drain connections are provided for the differ...

Страница 9: ...of the cross brace in the center of the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat...

Страница 10: ...size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 18 If the airflow needs to be increased or decreased see the Airflow La...

Страница 11: ...GLE SPEED AIR HANDLERS WITH 2 STAGE HEAT PUMP 2 STAGE HEAT AUTOMATIC OR MANUAL CHANGE OVER COMFORT CONTROL From Dwg 21B801073 COMFORT CONTROL AUTO 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER...

Страница 12: ...CONTROL MANUAL 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER COOLING O D SECTION SINGLE SPEED COOLING O D SECTION SINGLE SPEED AIR HANDLER WITH 2 STAGE COOLING UNIT 2 STAGE HEAT AUTOMATIC CHANG...

Страница 13: ...18 GE06D1 4 13 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3F62...

Страница 14: ...14 18 GE06D1 4 Installer s Guide 2 4TEE3F62 AIR HANDLERS H W 21 0 Model No H W 2TEE3F62A1000A 62 75 24 4TEE3D62B1000A 62 75 24...

Страница 15: ...ed against the following checklist 1 Make sure power is OFF at power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit...

Страница 16: ...ntinuous product and product data improvement it reserves the right to change design and specifications without notice American Standard Inc 6200 Troup Highway Tyler TX 75707 For more information cont...

Отзывы: