background image

© 2007 American Standard Inc.  All Rights Reserved

2

18-GE06D1-4

Installer’s Guide

6. It is recommended that the outline drawing be stud-

ied and dimensions properly noted and checked
against selected installation site. By noting in ad-
vance which knockouts are to be used, proper clear-
ance allowances can be made for installation and
possible future service.

7. When the air handler with supplementary heater is

to be installed in the downflow position on combus-
tible flooring an accessory sub-base (TAYBASE102
for 2/4TEE3F40- 065) must be used. See Figure 1.

8. If supplementary heat is to be added, power supply

must be sufficient to carry the load. In addition,
minimum air flow settings, unit and duct clearances
to combustible material must be maintained as
stated on the air handler rating nameplate.

CAUTION

!

For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
American Standard Inc. Only heaters built by American
Standard Inc. are approved for use in the air handler.
These heaters have been designed and tested in accor-
dance with UL standards to provide safe and reliable
operation. A list of approved heaters is provided on the
air handler rating nameplate. Heaters that are not fac-
tory approved could cause damage and are not cov-
ered under equipment warranty.

NOTE: If air handler is used WITHOUT a supplementary
electric heater, a sheetmetal plate is required to cover
the open hole in the airflow system. See Figure 2

.

 Also

seal the cabinet air tight where the wire enters.

9. If field installed electric heaters are applied, mini-

mum air flow settings, unit and duct clearances to
combustibles must be maintained as stated on the
air handler rating nameplate.

10. If the unit is installed without a return air duct, ap-

plicable local codes may limit this air handler to in-
stallation only in a single story residence & within
conditioned space.

AIR HANDLER SUB-BASE

Figure 1

FLOOR OPENING - SIZE

 MODEL NO.

A

B

 TAYBASE102

26-3/4

14-13/16

NOTE: CONDENSATION MAY OCCUR ON THE SUR-
FACE OF THE AIR HANDLER WHEN INSTALLED IN AN
UNCONDITIONED LOCATION. WHEN UNITS ARE IN-
STALLED IN UNCONDITIONED SPACES, VERIFY THAT
ALL ELECTRICAL AND REFRIGERANT LINE PEN-
ETRATIONS ON THE AIR HANDLER ARE SEALED
COMPLETELY.

This area may also be used for other purposes, includ-
ing an electric hot water heater - but in no case shall
a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.

In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted sup-
ply and return air.

This equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280
or the equivalent. “SUITABLE FOR MOBILE HOME
USE”

For proper installation the following items must be con-
sidered:

1. If adequate power is available and correct according

to nameplate specifications.

2. Pursuant to Florida Building Code 13-610.2.A.2.1,

this unit meets the criteria for a factory sealed
air handler.

3. Insulate all ducts, particularly if unit is located out-

side of the conditioned space.

4. The Refrigerant lines must be sealed and Electri-

cal inlets need to be sealed at both the low and
the high voltage.

5. To ensure maximum efficiency and system perfor-

mance, the existing supply and return duct system
static pressures must not exceed the total available
static pressure of the air handler. Reference ACCA
Manual D, Manual S and Manual RS along with the
air handler Product Data and Service Facts for addi-
tional information.

Содержание 2TEE3F62A1000A

Страница 1: ...or or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or h...

Страница 2: ...aintained as stated on the air handler rating nameplate 10 If the unit is installed without a return air duct ap plicable local codes may limit this air handler to in stallation only in a single story...

Страница 3: ...ater or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 12 Make sure there are provisions...

Страница 4: ...enough to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same d...

Страница 5: ...tab i When supplementary heaters are used accessory subbase TAYBASE102 for 2 4TEE3F62 must be used See Figure 1 j If a return duct is connected to the air handler it must be the same dimensions as th...

Страница 6: ...n on the outline drawing Use 2 5 clear stickers provided to seal all unused electrical knockouts See Figure 8 k After ductwork connections are made seal air tight and per Local codes HORIZONTAL RIGHT...

Страница 7: ...outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers provided to seal all unused...

Страница 8: ...tion is the primary drain See Figure 14 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection Figure 14 BRAZE SHIELD Figure 13 Two secondary drain connections are provided for the differ...

Страница 9: ...of the cross brace in the center of the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat...

Страница 10: ...size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 18 If the airflow needs to be increased or decreased see the Airflow La...

Страница 11: ...GLE SPEED AIR HANDLERS WITH 2 STAGE HEAT PUMP 2 STAGE HEAT AUTOMATIC OR MANUAL CHANGE OVER COMFORT CONTROL From Dwg 21B801073 COMFORT CONTROL AUTO 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER...

Страница 12: ...CONTROL MANUAL 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER COOLING O D SECTION SINGLE SPEED COOLING O D SECTION SINGLE SPEED AIR HANDLER WITH 2 STAGE COOLING UNIT 2 STAGE HEAT AUTOMATIC CHANG...

Страница 13: ...18 GE06D1 4 13 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3F62...

Страница 14: ...14 18 GE06D1 4 Installer s Guide 2 4TEE3F62 AIR HANDLERS H W 21 0 Model No H W 2TEE3F62A1000A 62 75 24 4TEE3D62B1000A 62 75 24...

Страница 15: ...ed against the following checklist 1 Make sure power is OFF at power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit...

Страница 16: ...ntinuous product and product data improvement it reserves the right to change design and specifications without notice American Standard Inc 6200 Troup Highway Tyler TX 75707 For more information cont...

Отзывы: