American Standard 2A7B3018-1000A Скачать руководство пользователя страница 6

PAGE 6

Pub. No. 11-AC17D1-1

INSTALLER'S GUIDE

R-22 SUBCOOLING CHARGING TABLE

LIQUID

TEMP.

(°F)

DESIGN SUBCOOLING VALUES (°F)

8

10

12

14

LIQUID LINE PRESSURE (psi)

45

89

93

96

100

50

98

102

105

109

55

107

111

115

119

60

117

121

126

130

65

128

132

137

141

70

139

144

148

153

75

151

156

161

166

80

163

168

174

179

85

176

182

187

193

90

190

196

202

208

95

205

211

217

223

100

220

226

233

239

105

236

243

249

256

110

253

260

267

274

115

271

278

285

293

120

289

297

305

313

125

309

317

325

333

SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE

60
50
40
30
25

Add 5 psig to Subcool Charging Table Pressure

20
15

Use Design Subcool Value from Table

10

0

Subtract 5 psig from S.C. Table Pressure

10

20

25

30

40

60

80

TOTAL REFRIGERANT LINE LENGTH  (FEET)

REFRIGERANT

LINE LIFT (FEET)

SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT

American Standard has always recommended installing
American Standard approved matched indoor and outdoor systems.

All 13 SEER American Standard split systems are ARI rated
with only TXV indoor systems.

The benefits of installing approved indoor and outdoor split
systems are maximum efficiency, optimum performance and
the best overall system reliability.

The following charging methods are therefore prescribed for
systems with indoor TXVs.

1. Subcooling (in the cooling mode) is the only recommended
method of charging above 55°F ambient temperatures.

2. For best results - the indoor temperature should be kept
between 70°F to 80°F. Add system heat if needed.

3. At start-up, or whenever charge is removed or added, the
system must be operated for a minimum 20 minutes to stabilize
before accurate measurements can be made.

4. Measure Liquid Line Temperature and Refrigerant Pres-
sure at service valves.

5. Determine total refrigerant line length, and height (lift) if
indoor section is above the condenser.

6. Determine the Design Subcool Charging Temperature from
the unit nameplate.

7. Locate this value in the appropriate column of the Subcooling
Charging Table. Locate your liquid line temperature in the left
column of the table, and the intersecting liquid line pressure
under your nameplate subcool value column. Add refrigerant to
raise the pressure to match the table, or remove refrigerant to
lower the pressure. Again, wait 20 minutes for the system
conditions to stabilize before adjusting charge again.

8. When system is correctly charged, you can refer to System
Pressure Curves (in Service Facts) to verify typical performance.

Содержание 2A7B3018-1000A

Страница 1: ...listed on the nameplate B LOCATION AND PREPARATION OF THE UNIT 1 When removing unit from the pallet notice the tabs on the basepan Remove tabs by cutting with a sharp tool as shown in Figure 2 see pa...

Страница 2: ...vide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route the tubing making all required...

Страница 3: ...line valves must remain closed 1 Upon completion of leak check evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves 2 Attach appropriate hoses from manifold gau...

Страница 4: ...d Leaving this pin open results in the normal mode of operation 2 TST Test Shorting TEST_COMMON to this pin speeds up all defrost board timings 3 FRC_DFT Forced Defrost Short TEST_COMMON to this pin f...

Страница 5: ...aterways LEGEND FACTORY WIRING FIELD WIRING REFRIGERANT CIRCUIT Liquid Pressure Too High Liquid Pressure Too Low Suction Pressure Too High Suction Pressure Too Low Liquid Refrig Floodback TXV System I...

Страница 6: ...optimum performance and the best overall system reliability The following charging methods are therefore prescribed for systems with indoor TXVs 1 Subcooling in the cooling mode is the only recommend...

Страница 7: ...5 2 5 8 210 8 1 4 57 2 1 4 457 18 2A7B3030A 3 2 832 32 3 4 829 32 5 8 756 29 3 4 3 4 5 16 137 5 3 8 86 3 3 8 210 8 1 4 79 3 1 8 508 20 2A7B3036A 3 2 832 32 3 4 829 32 5 8 756 29 3 4 7 8 3 8 137 5 3 8...

Страница 8: ...ked 2 Suction Lines and Fittings properly insulated 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from co...

Отзывы: