American Standard 2A7B3018-1000A Скачать руководство пользователя страница 2

PAGE 2

Pub. No. 11-AC17D1-1

INSTALLER'S GUIDE

7. If outdoor unit is mounted above the air handler, maximum
lift should not exceed sixty (60) feet (suction line).  If air handler
is mounted above condensing unit, maximum lift should not
exceed sixty (60) feet (liquid line).

8. Locate and install indoor coil or air handler in accordance
with instruction included with that unit.

NOTE:  Refer to "Refrigerant Piping Software" Pub.
No. 32-3312-0*, and "Refrigerant Piping Manual"
Pub. No. 32-3009-0* (the position of the * denotes latest
revision number).

C. INSTALLING REFRIGERANT LINES

▲ 

CAUTION:

 If using existing refrigerant lines

make certain that all joints are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor unit
for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may be
straight or with a 90 degree bend, depending upon situation
requirements.  This should be thoroughly checked out before
ordering refrigerant line sets.

The gas line must always be insulated.

▲ 

CAUTION:

 In scroll compressor applica-

tions, dome temperatures may be hot. Do not touch top of
compressor, may cause minor to severe burning.

The units are factory charged with the system charge required
when using fifteen (15) feet of rated connecting line.  Unit
nameplate charge is the same.

Final refrigerant charge adjustment is necessary. Use
the Charging Information on page 6 or in the outdoor unit
Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:  Large diameter tubing will be very difficult to rebend
once it has been shaped.

3. Determine the best starting point for routing the refrigerant
tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both liquid
and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly
secure the tubing before making connections.

8. To prevent a noise within the building structure due to
vibration transmission from the refrigerant lines, the following
precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation type hangers.

b. Isolation hangers should also be used when refrigerant

lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill,

they should be insulated and isolated.

d. Isolate the lines from all ductwork.

D. SERVICE VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES

The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory charge. The
pressure tap service port (when depressed) opens only to the
field brazing side of the valve when the valve is in the seated
position.  The liquid line valve is not a back seating valve (see
WARNING below).

▲ 

WARNING:

 Extreme caution should be ex-

ercised when opening the Liquid and Gas Line Service
Valves. Turn valve stem counterclockwise only until the
stem contacts the rolled edge. (See Figures 3 and 5) No
torque is required.

BRASS GAS LINE BALL SERVICE VALVE

The Brass Gas Line Ball Service Valve is shipped in the closed
position to hold the factory refrigerant charge.  The pressure tap
service port (when depressed) opens only to the field brazing
side when the valve is in the closed position.

The Gas Line Service Valve is full open with a 1/4 turn. See
Figure 4.

BRAZING REFRIGERANT LINES

1. Remove lower access cover to access service valves.

2. Before brazing, remove plugs from external copper stub
tubes.  Clean internal and external surfaces of stub tubes prior
to brazing.

BASEPAN TAB REMOVAL

2

3

LIQUID LINE SERVICE VALVE

Содержание 2A7B3018-1000A

Страница 1: ...listed on the nameplate B LOCATION AND PREPARATION OF THE UNIT 1 When removing unit from the pallet notice the tabs on the basepan Remove tabs by cutting with a sharp tool as shown in Figure 2 see pa...

Страница 2: ...vide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kink or dent 7 Route the tubing making all required...

Страница 3: ...line valves must remain closed 1 Upon completion of leak check evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves 2 Attach appropriate hoses from manifold gau...

Страница 4: ...d Leaving this pin open results in the normal mode of operation 2 TST Test Shorting TEST_COMMON to this pin speeds up all defrost board timings 3 FRC_DFT Forced Defrost Short TEST_COMMON to this pin f...

Страница 5: ...aterways LEGEND FACTORY WIRING FIELD WIRING REFRIGERANT CIRCUIT Liquid Pressure Too High Liquid Pressure Too Low Suction Pressure Too High Suction Pressure Too Low Liquid Refrig Floodback TXV System I...

Страница 6: ...optimum performance and the best overall system reliability The following charging methods are therefore prescribed for systems with indoor TXVs 1 Subcooling in the cooling mode is the only recommend...

Страница 7: ...5 2 5 8 210 8 1 4 57 2 1 4 457 18 2A7B3030A 3 2 832 32 3 4 829 32 5 8 756 29 3 4 3 4 5 16 137 5 3 8 86 3 3 8 210 8 1 4 79 3 1 8 508 20 2A7B3036A 3 2 832 32 3 4 829 32 5 8 756 29 3 4 7 8 3 8 137 5 3 8...

Страница 8: ...ked 2 Suction Lines and Fittings properly insulated 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from co...

Отзывы: