PROGRAMMING
8
Alarm Settings - Time Delay
The display will show:
Press
or
to change the flashing value representing minutes.
If the air temperature goes out of the preset limits the alarm will go off only after the time set here elapses. The
alarm time delay can be set anywhere between 0 (no delay) and 60 minutes.
Press
when done
Light Off Delay
The display will show:
Next the controller will prompt you to set the automatic light off delay.
The automatic light off delay is the elapsed time between the moment the user turns the light on and the moment
the controller will automatically turn it off.
Set the automatic light off delay by pressing
or
to change the flashing value representing
minutes. The automatic light off delay can be set between 1 and 60 minutes. In case the customer does not want
an automatic light off delay, set this function to “
∞
”.
Press
when done.
The display will show: