Part Number 8200-0341-9900 A0

©Copyright 2003 Sencormatic Electronics Corp.

4.

Locate jumper P-24 (Figure-1).

5.

Move jumper P-24 from Operate position (Figure-2) to
Program position (Figure-3)

6.

Insert the MEU into the patch panel within one (1)
minute. The heartbeat LED on the patch panel will blink
rapidly, indicating MP-48 is ready to receive download
information.

7.

Connect the null modem cable from COM 1 on your PC
to the DB-9 connector on the patch panel.

8.

Read the 

Readme.txt

 file.

9.

For 32-bit Windows Operating Systems, run 

MP48.bat

(for COM1) or 

MP48COM2.bat 

(for COM2).

10. For 16-bit Windows Operating Systems, follow the

directions in the 

Readme.txt

 file for further instructions.

11. When the download is complete, remove the MEU. Move

the P-24 jumper back to Operate mode (Figure-2) and
replace the cover.

12. Insert the MEU. The heartbeat LED should blink once per

second.  Establish communication with the keyboard.

13. Using your keyboard (the key switch must be in 

Program

for AD2088/2079 keyboards, 

unlocked

 for an ADTTE

keyboard), type 

70

 

F2

 Figure 1

 Figure 2

 Figure 3