ADACSNET USB CONTROL MODULE 

8200-0310-01, REV. B 

INSTALLATION GUIDE 

4 of 6

 

 

 

 

 

 

 

 

 

 

USB with J-Boxes 

Unterminate when 
more than one port 
is used (P4–P6 or 
P1–P3). 

Repeating is not 
needed when the 
USB module and 
the last J-BOX are 
less than 1km 
(3300ft) apart. 

Unterminate the 
HOST when it is 
not at the end of 
the line. 

USB 
Module

J-Box 1

J-Box 2 

Terminate the 
HOST when it is at 
the end of the line.

Balance connection ports with 

domes (do not load on one side).

REPEATER 

REPEATER 

91m (300ft) 

305m (1000ft) 

• 

Only use the AUX-to-HOST connection if the 
distance from the HOST to the last J-BOX is 
more than 1km (3300ft). 

• 

From J-BOX 1 to J-BOX 2, use the HOST-to-
HOST connection only when the distance 
from the HOST and the last J-BOX is less 
than 1km (3300ft). 

• 

If using the J-BOX to amplify the signal, it is 
best to install it between 500 and 750m 
(1600-2500ft). 

Содержание ADACSNET

Страница 1: ...LED also blinks every time a data packet is sent to the camera dome Termination switch Termination is indicated by a resistor symbol near the switch See SensorNet Rules and Network Types in this document for when to set the switch The following diagram shows how to hook up the control module between the host Intellex or PC and a camera Software Installation for Non Intellex Systems If not connecti...

Страница 2: ... repeaters in the path of any two camera domes A SensorNet line or branch cannot exceed 1km 3300ft Use signal repeaters only when exceeding the maximum distance or noise is an issue Signal levels for SensorNet compatible devices are from 0 3 5V 1 5V is recommended Network Types Star Network The star network allows you to relocate devices However this network is not recommended in high noise enviro...

Страница 3: ... J Boxes consider the following rules also refer to the following diagram Only use the AUX to HOST connection if the distance from the HOST to the last J BOX is more than 1km 3300ft Repeating is not needed when the USB module and the last J BOX are less than 1km 3300ft apart From J BOX 1 to J BOX 2 use the HOST to HOST connection only when the distance from the HOST and the last J BOX is less than...

Страница 4: ... J Box 1 J Box 2 Terminate the HOST when it is at the end of the line Balance connection ports with domes do not load on one side REPEATER REPEATER 91m 300ft 305m 1000ft Only use the AUX to HOST connection if the distance from the HOST to the last J BOX is more than 1km 3300ft From J BOX 1 to J BOX 2 use the HOST to HOST connection only when the distance from the HOST and the last J BOX is less th...

Страница 5: ...ng FM 0 Link layer framing SDLC HDLC Link layer channel Bi directional half duplex Collision avoidance Polling by USB Module Application protocol Proprietary Network nodes Domes junction boxes secondary TouchTracker and SensorNet I O unit Power Input voltage 5 0Vdc 5 0 75W Internal voltage CPU Misc Support 3 3Vdc 5 Surge Protection SensorNet Gas discharge tube impulse rated at DC breakdown voltage...

Страница 6: ...n customer service and support Dealers should contact American Dynamics at 800 507 6268 or 561 912 6259 or on the web at www americandynamics net WARRANTY DISCLAIMER Sensormatic Electronics Corporation makes no representation or warranty with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose NOTICE The informat...

Отзывы: