20
The main duct may be any shape or cross-sectional area, so long as the minimum cross section area is
provided. The
illustrations
on
page 21
show the minimum cross section area for multiple dryer round or
square venting. These figures
must be
increased 10 square inches (64.51 square centimeters) when
rectangular main ducting is used, and the ratio of duct width to depth
should not be
greater than 3-1/2 to 1.
These figures
must be
increased in proportion if the main duct run to the last dryer to where it exhausts to
the outdoors is unusually long (over 20 feet [6.09 meters]) or has numerous elbows (more than two [2]) in
it. In calculating ductwork size, the cross section area of a square or rectangular duct
must be
increased
twenty percent (20%) for each additional 20 feet (6.09 meters). The diameter of a round exhaust
must be
increased ten percent (10%) for each additional 20 feet (6.09 meters). Each 90° elbow is equivalent to an
additional 15 feet (4.57 meters).
IMPORTANT:
For extended ductwork runs, the cross section area of the ductwork can only be
increased to an extent. Maximum proportional ductwork runs
cannot
exceed
20 feet (6.09 meters) more than the original limitations of 20 feet (6.09 meters) with
two (2) elbows. When the ductwork approaches the maximum limits as noted in this
manual, a professional heating, venting, and air conditioning (HVAC) firm
should be
consulted for proper venting information.
IMPORTANT:
Exhaust back pressure measured by a manometer at each dryer exhaust duct area
must not exceed
0.3 inches (0.74 mb) of water column (W.C.).
The duct
should be
smooth inside with no projections from sheet metal screws or other obstructions, which
will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be
connected.
ALL
ductwork joints
must be
taped to prevent moisture and lint from escaping into the building.
Inspection doors
should be
installed at strategic points in the exhaust ductwork for periodic inspection and
cleaning of lint from the ductwork.
NOTE:
When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible
materials, the opening
must be
2-inches (5.08 cm) larger than the duct (all the way around).
The duct
must be
centered within this opening.
a. Outside Ductwork Protection
1) To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward
should be
installed where the exhaust exits the building. If the exhaust ductwork travels vertically
up through the roof, it
should be
protected from the weather by using a 180° turn to point the
opening downward. In either case, allow at least twice the diameter of the duct between the duct
opening and nearest obstruction.
IMPORTANT:
DO NOT
use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
Содержание ML-130 II
Страница 59: ...ADC 113314 1 06 21 01 25 ...