113363 - 37
www.adclaundry.com
19
ML-122 Multiple Dryer Venting
16-Inch (40.64 cm) Diameter Minimum Exhaust Connections at Common Duct
IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be
increased to an extent. Maximum proportional ductwork runs cannot exceed 20 feet
(6.09 meters) more than the original limitations of 20 feet (6.09 meters) with two (2)
elbows. When the ductwork approaches the maximum limits as noted in this manual,
a professional heating, ventilating, and air-conditioning (HVAC) firm should be
consulted for proper venting information.
IMPORTANT: Exhaust back pressure measured by a manometer/magnehelic in the exhaust duct
must be no less than 0 and must not exceed 0.3 in WC (0.74 mb).
NOTE: It is recommended that exhaust or booster fans not be used in the exhaust ductwork system
except where necessary to maintain exhaust back pressure (in the exhaust duct) between zero
and 0.3 inch water column. Where employed, booster fans must not activate the dryer airflow
proving switch (sail switch) when the dryer is not in operation.