66
a.
PROBABLE CAUSES
1) The lint screen
must
be
cleaned every five (5) drying cycles
2) Wiring back to the PLC (Programmable Logic Controller), 0, 8
3) Clogged lint screen or lint bag
4) Air pressure setting
5) Air pressure switch - PS3 or wiring back to the PLC (Programmable Logic Controller)
b.
PROBABLE SOLUTIONS;
1) Perform preventive maintenance and screen cleaning procedures.
2) Set correct pressure settings.
3) For a quick check of the AIR PRESSURE SWITCH WIRING, perform the following:
Run a drying cycle
Does the pressure switchs indicator come ON?
If YES, switch and its adjustment are okay
If NO, check switch and its adjustment
Verify that PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #5 comes
ON
Does L.E.D. #5 come ON when the switch is active?
If YES, wiring is okay
If NO, check:
Switch, its setting and wiring
Check wiring back to the base electrical junction box
Check PLC (Programmable Logic Controller)
Refer to the blueprints: Main Electrical Panel Diagram, Base Junction Box Wiring Diagram
Retest; verify that the signal is operational