3. Electrical Service
The electrical power is connected the dryer at the high voltage section of the control cabinet. On the
ADG-464 dryer, this section is located at the bottom left of the main electrical enclosure.
The ADG-464 dryer
must be
supplied with two (2) independent input power lines. One is 3-phase ( 3ø)
electric service that feeds the dryer itself, and the other is 1ø electric service that feeds the safety sprinkler
system.
Both input lines
must be
independent of each other and individually protected by their
individual fused disconnect.
NOTE
: The ADG-464 with sprinkler option
will not operate
without an independent power source
fed to the Safety Sprinkler System.
Feed the electrical service cables to the dryer using the pre-punched knockouts at the bottom section of the
electrical cabinet right wall.
Connect the ground wires directly to the ground lug located at the same approximate area.
NOTE
:
The sprinkler operates off of single-phase (1ø) nameplate voltage of the dryer.
Before turning power on to the dryer, measure the supply voltage to ensure that it matches the dryer’s
specified input voltage. This input voltage is marked on the aluminum data plate located on the inner right
wall of the electrical cabinet.