5 Service

 

 

CAUTION

: Servicing the DH-100V with its 

high-

pressure

 refrigerant system and 

high voltage

 circuitry 

presents a health hazard, which could result in 

death

serious bodily 

injury

, and/or property 

damage

. Only 

qualified service people should service this unit. 

5.1 Warranty

 

See page 9 for warranty terms.  Read the warranty 
before any repair is initiated.  If a warranty repair is 
required, call the factory first at 1-800-255-7749 for 
warranty claim authorization and technical assistance. 

5.2 Technical Description

 

The DH-100V uses a refrigeration system similar to an 
air conditioner's to remove heat and moisture from 
incoming air, and add heat to the air that is discharged 
(see Fig. 1). 
 
Hot, high-pressure refrigerant gas is routed from the 
compressor to the condenser coil (see Fig. 1). The 
refrigerant is cooled and condensed by giving up its heat 
to the air that is about to be discharged from the unit. 
The refrigerant liquid then passes through a filter/drier 
and capillary tubing, which cause the refrigerant 
pressure and temperature to drop. It next enters the 
evaporator coil where it absorbs heat from the incoming 
air and evaporates.  
 

 

 

Figure 1: Refrigeration System of DH-100V 

The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet. 
 
The mixture of gas and liquid refrigerant enter the 
accumulator after leaving the evaporator coil. The 
accumulator prevents any liquid refrigerant from 
reaching the compressor. The compressor evacuates 
the cool refrigerant gas from the accumulator and 
compresses it to a high pressure and temperature to 
repeat the process. 

5.3 Troubleshooting

 

No dehumidification, neither blower nor compressor 
run with fan switch OFF. 

1. 

Unit unplugged or no power to outlet. 

2. 

Humidity control set too high or defective  (Sec. 3.1 
& 5.7). 

3. 

Loose connection in internal wiring. 

 

No dehumidification, compressor does not run but 
blower runs with fan switch OFF and humidity 
control turned to ON. 

1. 

Defective compressor run capacitor (Sec. 5.6). 

2. 

Loose connection in compressor circuit       (see 
Fig. 2). 

3. Defective 

compressor 

overload (Sec. 5.6A). 

4. 

Defective compressor (Sec.5.6). 

5. 

Defrost thermostat open (Sec. 5.8). 

 

Blower runs with fan switch OFF, but compressor 
cycles on & off. 

1. 

Low ambient temperature and/or  humidity, causing 
unit to cycle through defrost mode. 

2. Defective 

compressor 

overload (Sec. 5.6A). 

3. 

Defective compressor (Sec. 5.6). 

4. Defrost 

thermostat 

defective (Sec. 5.8). 

 

Blower does not run with fan switch in either 
position. Compressor runs briefly but cycles on & 
off. 

1. Loose connection in blower circuit (see Fig. 2). 
2. Obstruction prevents impeller rotation. 
3. Defective blower. 
4. Blower switch defective. 

 

Evaporator coil frosted continuously, low 
dehumidifying capacity. 

1. 

Defrost thermostat loose or defective (Sec. 5.8).

 

2. Low refrigerant charge 
3. Dirty air filter or airflow restricted. 

 

Содержание DH-100V

Страница 1: ...to obtain maximum benefit from your DH 100V dehumidifier 1 Specifications Model DH 100V Dehumidifier Electrical 110 120 VAC 6 8 Amps grounded Capacity 100 pints day 80 F 60 RH Operating Temp Range 53 F min 105 F max Air Flow 255 CFM without external ducting 170 CFM 0 15 in wg external static Refrigerant Charge 1 lbs 14oz R 22 Optional Duct connections 8 round inlet outlet Size w o duct collars 20 ...

Страница 2: ...ied air into the room in which it s located An adequate airflow path must exist between the two rooms for this method to work well An additional humidity control may need to be mounted in the humid area and wired to the DH 100V to accurately maintain the desired humidity Local electrical codes must be followed when wiring the control 2 2 Electrical Requirements The DH 100V plugs into a common grou...

Страница 3: ...onger to reduce the area s RH to the setting The ALDES DHV 100V unit and refrigerant based dehumidifiers in general will reduce a warm space s RH to a lower level than that of a cool space It is therefore pointless to set the humidity control to excessively low levels in cool rooms doing so will result in long periods of ineffective dehumidifier run time Quality humidity meters are available from ...

Страница 4: ...ture across the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching the compressor The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process 5 3 Troubleshooting No dehumid...

Страница 5: ...mpressor circuit Test each component for continuity see the appropriate section if a defect is suspected 3 Unplug the unit then disconnect the red and yellow wires from compressor terminals R S Using an ohmmeter check continuity between the points listed below 4 Compressor terminals C and S No continuity indi cates an open start winding The compressor must be replaced Normal start winding resistan...

Страница 6: ... not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour An alternate method of removing moisture and non condensibles from the system requires evacuation to 29 Hg vacuum Then break the vacuum with 35 to 50 PSIG refrigerant vapor charge Leave the vapor charge in the system for at least 5 minut...

Страница 7: ...Figure 2 Electrical Schematic of the DH 100V Dehumidifier 7 ...

Страница 8: ...35 MFD 370V 4017799 1 Compressor Run Capacitor for Tecumseh 25 MFD 440V 9 4021396 1 Condenser Coil 10 4021409 1 Cord Wire Harness 11 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 11 12 4021395 1 Evaporator Coil 13 4020955 1 Filter Drier 14 4021626 1 Hose Drain 56 ID x 8 15 4021469 1 Humidity Controller 16 4021495 1 Knob Humidity Controller 17 4020554 1 Switch SPDT fo...

Страница 9: ...nd American ALDES Ventilation Corporation s reasonable control Limitations and Exclusions If any American ALDES Dehumifier Dehumidifying Ventilator part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto All warranty periods shall be extended by the period of time if any that the unit is out of service while awaiting co...

Страница 10: ...10 ...

Отзывы: