Networked Indexer/Driver User Manual
C
ONFIGURATION
M
ODE
D
ATA
F
ORMAT
65
Output Data Format (continued)
Configuration Word 1 Format (continued)
Bit 9:
Binary_Input_Format –
Set to “0” to have the Motor Position, Encoder Position, and Trapped
Encoder Position reported in the
shown in table R6.1 on page 60. Set to
“1” to have the Motor Position, Encoder Position, and Trapped Encoder Position reported as signed
32-bit integers with the location of the least significant bits determined by the value of the
Binary_Endian bit. (See bit 7 below.)
Bit 8:
Binary_Output_Format –
Set to “0” to program the Target Position and Programmed Speed parame-
ters in the
shown in table R6.1 on page 60. Set to “1” to program the Target
Position and Programmed Speed parameters in signed 32-bit integer format with the location of the
least significant bits determined by the value of the Binary_Endian bit. (See bit 7 below.)
Bit 7:
Binary_Endian –
Only used when bits 8 and/or 9 (Binary_Output_Format and
Binary_Input_Format) are set to “1”. Set to “0” to have 32-bit values transmitted in little endian for-
mat. Set to “1” to have the 32-bit values transmitted in big endian format. EtherNet/IP applications
should reset this bit to “0”. Modbus TCP and PROFINET applications should start with this bit set to
“1”. These protocols typically use big endian format, but you should refer to you PLC’s documenta-
tion to verify the format used by your processor. See table R6.2,
found on page 61 for examples of the different formats.
Bits 6 - 3: Reserved –
Must equal zero.
Bit 2:
IN3_Active_Level –
Determines the active state of Input 3. Set to “0” if your sensor has Normally
Closed (NC) contacts and the input is active when there is no current flow through it. Set to “1” if
your sensor has Normally Open (NO) contacts and current flows through the input when it is active.
Bit 1:
IN2_Active_Level –
Determines the active state of Input 2. Set to “0” if your sensor has Normally
Closed (NC) contacts and the input is active when there is no current flow through it. Set to “1” if
your sensor has Normally Open (NO) contacts and current flows through the input when it is active.
Bit 0:
IN1_Active_Level –
Determines the active state of Input 1. Set to “0” if your sensor has Normally
Closed (NC) contacts and the input is active when there is no current flow through it. Set to “1” if
your sensor has Normally Open (NO) contacts and current flows through the input when it is active.
The AMCI Networked Driver does not report the state of the inputs when they are configured
as encoder inputs (ABZ). The driver reports the state of the
Active Level Bit
for the input.
Notes on Other Configuration Words
used when programming the Starting Speed can be found
on page 60.
Changes to the Idle Current only take effect at the
end of the first move after re-configuration
.
settings for all AMCI motors can be found starting on page 43.
Содержание SD17060E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S172 E2 Technology E2 Technology...
Страница 10: ...ABOUT THIS MANUAL Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 22: ...UL CUL RECOGNIZED INSTALLATIONS Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 22 Notes...
Страница 54: ...CALCULATING MOVE PROFILES Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Страница 88: ...COMMAND MODE DATA FORMAT Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 106: ...INSTALLING AN AMCI NETWORKED DRIVER Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 106 Notes...
Страница 130: ...ETHERNET IP EXPLICIT MESSAGING Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 130 Notes...
Страница 134: ...MODBUS TCP CONFIGURATION Networked Indexer Driver User Manual ADVANCED MICRO CONTROLS INC 134 Notes...
Страница 144: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...