TECHNICAL  SPECIFICATIONS 

 

The equipment must be powered by a voltage SELV, with limited power, with maximum output current of 0.6 A

 

Nominal Supply Voltage: 

13,8 Vcc

 

Maximum Current Consumption: 

150mA

 

Stand-by Current Consumption: 

8 mA

 

Sound Pressure (Vn=13,8V ): 

Type = TONE   108 dB(A) at 1 m

 

Sound and Light Timing without control: 

3’

 

Back-up Battery: 

12 V  , 2,2 Ah - Flammability class UL94-HB

 

Dimensions: 

210mm(L) x 295mm(H) x 70mm(P)

 

Weight: 

800g without battery

 

Working Temperature: 

40 °C ¸ + 60 °C

 

IP  Grade 

IP44 

 

Installation must be carried out following the local installation norms by qualified personnel.

 

The manufacturer refuses any responsibility when changes or unauthorized repairs are made to the product/system.

 

It is recommended to test the operation of the alarm product/system at least once a month. Despite frequent testing and 
due to, but not limited to, any or all of the following: tampering, electrical or communication disruption or improper use, it 
is possible for the product/system to fail to prevent burglary, rubbery, fire or otherwise. A properly installed and maintained 
alarm system can only reduce the risk that this happens.

 