Ambirad Vision VSX Скачать руководство пользователя страница 14

14 

 

7.  User & Operating Instructions. 

7.1 

To Start the Heater 

 

1. Ensure gas supply is turned on. 
 
2. Electrical supply to the controls is on. 
 
3. Ensure that the controls are correctly set 

i.e.; 

 

• 

Clock is correctly set. 

• 

Heater program is correctly set. 

• 

Required room temp is correctly set 

 
4. Once the heating controller ‘calls for heat’ 

power will be supplied to the heater(s). The 
red neon will then illuminate. 

 
5. After a pre-purge period of 10 seconds the 

burner will ignite and the amber neon will 
then illuminate. 

 
6. If lockout occurs press the lockout reset 

button (if available), or switch off electrical 
supply and restart after 15 seconds. 

 
7. If lockout occurs three times consecutively 

switch  off  and  isolate  the  gas  and         
electricity supplies. 
Contact the AmbiRad Service department.

 

 
7.2.  To Switch Off Heater 
 

1. Switch off electrical supply to the heater. 

The burner will stop and the fan will shut 
off. 
 

2. If the heater is to be switched off for      

periods in excess of one week it is highly    
recommended that both the gas and the 
electrical supplies are turned off. 
 

7.3.  Routine Maintenance between Service 

Intervals 

 

After ensuring that the heater is cold and 
mains  electric  isolated,  cleaning  of  the        
reflectors with a soft cloth and a mild 

 

 

 

 

 

 

 

 

 

detergent (non solvent based cleaners only) 
in water can be undertaken. 

 

Additional removal of dust from the radiant 
tubes, burner and heat exchanger can be   
undertaken. 

 

7.4   Frequency of Servicing 
 

The manufacturer recommends that to 

 

 

ensure 

continued 

efficient 

and 

safe         

operation of the appliance, the heater is 
serviced annually by a competent person 
e.g. every year in normal working conditions 
but  in  exceptional  dusty  or  polluted        
conditions more frequent servicing may be 
required. 

 

The manufacturer offers a maintenance 

 

 

 

 

service. Details are available on request. 

 

For Service requirements, please contact   
AmbiRad. 

 

For further technical and service support 
visit our Support Information Database at     
www.s-i-d.co.uk 

Step 12 Ensure step screw is in the correct  
position as indicated in the diagram below. 
 
Step 13 Set gas pressures to data badge or  as 
per  section  1.11  and  ensure  reliable  burner        
performance. 
 
Step 14 Test product and close access doors. 

Step Screw 
Adjustment 

Document re

feren

c

e number

 GB

/VS

/1

90A/0910 

AmbiRad is a registered trademark of AmbiRad Limited. Because of continuous product 
innovation, AmbiRad reserve the right to change product specification without due notice 

AmbiRad Limited  Fens Pool Avenue 
Brierley Hill  West Midlands DY5 1QA  
United Kingdom. 

 

Telephone  01384 489700 
Facsimile  01384 489707 
Email  

[email protected]

 

Website  

www.ambirad.co.uk

 

Technical Support  

www.s-i-d.co.uk

 

Содержание Vision VSX

Страница 1: ...ith the relevant provisions of the Gas Safety Installations and Use Regulations 1998 for gas fired products Due account should also be taken of any obligations arising from the Health and Safety at Wo...

Страница 2: ...t tube heaters specified in these instructions due care 3 9 Reflector Servicing 3 10 Inspection of Flue 3 11 Re commissioning after Service 4 Spare Parts 5 Fault Finding Guide 6 Replacing Parts 6 1 Bu...

Страница 3: ...2 8 2 4 450x5927x746 158 0 5 2560 VSX45UT 44 0 39 6 4 2 11 6 2 9 450x5927x746 158 0 5 2560 VSX50UT 49 5 44 6 4 7 12 8 2 5L 450x7692x746 205 0 5 2560 1 3 Table 1 Technical Details All heaters to run on...

Страница 4: ...nd inspect burner head See servicing instructions Check operation of air pressure switch Leave the instructions with a responsible person Injector pressure test point Adjustment screw under cap to set...

Страница 5: ...Wrench with 13mm Socket 12mm Spanner 3 1 Tools Required The following tools and equipment are advisable to complete the tasks laid out in this manual Suitable alternative tools may be used Large Adjus...

Страница 6: ...nger and remove the flexible hose from the burner Step 6 Slacken the set screw on the burner support casting to enable the burner to be removed from the radiant tube Step 7 Remove the burner and posit...

Страница 7: ...replaced ensuring the 5 holes on the outer ring are aligned alongside the probes Step 3 The condition of the igniter assembly can be checked for deterioration However we advise replacement at each ser...

Страница 8: ...dust with a soft brush Step 6 Remove any dust from fan scroll and from around the motor Step 7 Ensure the impeller rotates freely Step 8 Refit components 3 7 Radiant Tube Servicing Step 1 Brush any d...

Страница 9: ...hanger refit 3 9 Reflector Servicing The condition of the reflectors should be noted If necessary the reflectors can be cleaned with a mild detergent This can significantly improve the efficiency of t...

Страница 10: ...ription See section 1 10 Injector 200358 Extruded Burner Head Item 201284 Ignitor Assembly Part No Description 200988 Pepperpot Head Item 2175 Amber Neon Burner On 2180 Red Neon Mains On 200420 Jet Ca...

Страница 11: ...cuum switch pull in Check 1 Wiring harness plugs 2 Vacuum switch operation 3 Replace fan Is the burner sparking Does the gas valve open Check 1 Burner controller 2 Replace gas valve Check 1 Vacuum swi...

Страница 12: ...tep 5 Fit new burner controller Step 6 Refit HT leads and refit burner controller to wiring harness Step 7 Test product and close access doors 6 2 Air Pressure Switch Replacement Step 1 Disconnect the...

Страница 13: ...impulse tube and the burner head wiring Step 5 From within the combustion chamber remove the two screws holding the front of the gas valve Step 6 Turning the housing over remove the four screws holdin...

Страница 14: ...and a mild detergent non solvent based cleaners only in water can be undertaken Additional removal of dust from the radiant tubes burner and heat exchanger can be undertaken 7 4 Frequency of Servicin...