Drawing No. :
900454 D R2 USA
NOTES:
NETWORK.
Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS
should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s)
may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for any remote sensors.
To other slave
controllers
SmartCom Mulitizone
NEUT
LIVE
1/L 2/N
10
S/R0 S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41
40
7
8
9
25
14
5
6
(Slave 1)
Burners
Zone B
SmartCom Mulitizone
NEUT
LIVE
(C
O
M
M
O
N
)
eg
E.M.S.
(R
E
M
O
T
E
O
N
)
(R
E
M
O
T
E
O
F
F
)
1/L 2/N
10
S/R0 S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41
40
7
8
9
25
14
5
6
To other slave
controllers
(Master)
IMPORTANT:
Cable A is only required if the24VAC
supply to the panel DOES NOT originate
from the secondary of an isolating transformer.
20 amp Supply
120V 60Hz 1 Ph
C
Relay
S-0755
W1
S-0700
L2
L1 (HOT)
GND
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1
GND
Burners
Zone A
Modulation
Damper
(n.c.)
(HOT)
Cable A
(C
O
M
M
O
N
)
eg
E.M.S.
(R
E
M
O
T
E
O
N
)
(R
E
M
O
T
E
O
F
F
)
20 amp Supply
120V 60Hz 1 Ph
C
Relay
S-0755
W1
S-0700
L2
L1 (HOT)
GND
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1
GND
Modulation
Damper
(n.c.)
(HOT)
Cable A
(n.c.)
(n.c.)