Notes:
MASTER & SLAVE (NETWORK)
When setting up a SmartCom³ Master and
Slave (Network) system, the master controller
will display
an
error message
during
commissioning. This will clear once the
commissioning is complete.
REMOTE SWITCHED INPUTS
SmartCom³ controllers can be operated
remotely via a remote ON or a remote OFF
signal in the following ways:
A.
Building Management System Control
(BMS).
SmartCom³ controllers can be operated via a
BMS system, by applying a volt free
connection (ie closed circuit to enable) across
terminals B1 and B0 turns the system on.
Making this connection on a master controller
will turn the entire system on whereas making
this connection on a slave unit will only bring
on that zone.
1. BMS Controlling Time only.
Ensure all the programmed ON times in the
SmartCom³ are turned off
(i.e. They read “- -:- -”).
2. BMS Controlling Time and Temperature
.
Ensure all the programmed ON times in the
SmartCom² are turned off
(i.e. They read “- -:- -”). Set all the required
day temperatures to 30°C.
B.
Remote Door Interlock
SmartCom³ controllers can be connect to a
door interlock, remote frost stat or permanent
off switch via terminals B2 and B0. When a
volt free connection is provided (ie closed
circuit to enable) at these terminals, the
controller reverts to a FROST ONLY mode.
Refer to the individual wiring diagrams for
wiring configurations and type.
T h 0 9 : 3 0 Z o n e 1
COMMS ERR Z o n e 6
F ROST ONL Y
EXT ERNAL / DOOR
AUT O
EXT ERNAL / BMS