Ambirad COBRA CB40 Скачать руководство пользователя страница 3

Model

Natural Gas G20

CB40

11.8 mbar

Model

CB40

Nominal heat input gross
Natural Gas (G20)

kW

38

Injector size

7 holes @dia 2.4

Number of injectors

1

Gas flow rate 

m3/hr

3.6

Gas supply

Connection R 1/2 1/2 BSP external thread

Gas pressure
Natural Gas (G20)

max. 25.0 mbar - min 17.0 mbar

Electrical supply 

230 Volts 1 phase 50 Hz

Current rating

0.55 amps max. (inductive)

External fuse rating

3 amps

Ignition

Electronic programme start-up with spark ignition

Noise level dBA @ 3m ‘free field’

40

Dimensions

mm

2298L x 1865W x 256D

Flue diameter

OD

125mm

Ducted air diameter

OD

102mm

Total installed weight

kg

152

Minimum mounting height m

5.7

Electrical motor details

V220 ac 50Hz Class F

Fan rating

0.5A

1

Technical data

Injector gas pressure

1  Gas supply/connection/

technical data

This heater is for use on:-

Natural gas G20, 20 mbar.

The gas connection on the Cobra heater is

R1/2 (1/2 in. BSP internal thread).

Natural gas

Max supply pressure  25 mbar

Min supply pressure  17 mbar

Correct burner gas pressure is indicated in
the table below.

To gain access to the gas connection, see
section 10.

Ambi-Rad heaters must be installed in
accordance with the relevant provisions
of the Gas Safety (Installations and Use)
Regulations 1998.  Due account should
also be taken of any obligations arising

from the Health and Safety at Works Act
1974.  In addition the installation must be
carried out in accordance with the 
current IEE 1992 (BS 7671), BS 6896:1991
(Industrial & Commercial) and any other
relevant British Standards and Codes of
Practice.

A gas meter is connected to the service
pipe by the local gas region or a qualified
local gas region contractor.  An existing
meter should be checked preferably by
the Gas Region or a qualified local gas
region contractors to ensure that the
meter is adequate to deal with the rate of
gas supply required.  Installation pipes
should be fitted in accordance with BS
6891:1998, such that the minimum 
pressure at least (Please see the technical
data table below) will be achieved and
any other British Standards and Codes of
Practice.   

Pipes of smaller size than the heater inlet
gas connection should not be used.  

The complete installation must be tested
for soundness as described in the 
previous standard.

The gas supply must not be in the 
position where it is subject to overheating.

The gas union service cock MUST be fitted
in the gas supply close to the heater, but
not onto the burner.

It is essential to provide some flexibility in
the final gas connection by use of a 
tested and certified metallic hose to BS
6501 Part 1:1991 (minimum acceptable
quality Type ‘B’ Class 1).  When stainless
steel flexible hoses are used the hose
should be connected in a 180˚ (bend 
without any strain or torsion).  (See figure
1 overleaf).

Note:  Take care when making a gas 
connection to the heater not to apply 
excessive turning force to the internal 
controls.

Содержание COBRA CB40

Страница 1: ...Operation maintenance and servicing manual CB40 GAS FIRED RADIANT TUBE HEATERS COBRA...

Страница 2: ...s 8 Installation of Cobra heaters 9 Flue connection 10 Access to the burner gas flue electrical connection 11 Fresh air ducted inlet all models 12 Commissioning for individually flued and unflued heat...

Страница 3: ...addition the installation must be carried out in accordance with the current IEE 1992 BS 7671 BS 6896 1991 Industrial Commercial and any other relevant British Standards and Codes of Practice A gas m...

Страница 4: ...mmended by the institute of Gas Engineers the manufacturer and Ambi Rad Ltd These instructions must becarried out inaccordance withthe relevant provisions of the gas safety installation and use regula...

Страница 5: ...if required manual control switches and a frost thermostat Circuits and controls All such controls and switchgear must be rated to handle the total inductive load of the circuit they control Load per...

Страница 6: ...e case of drop rods a closed formed hook The hanging attachments to overhead steelwork etc must be purpose made to good sound engineering practice or of a proprietary type fixing They must be adequate...

Страница 7: ...onstruction Alternatively 10mm diameter mild steel drop rods can be used Figure 4 Mounting of Cobra heater Wall mounting brackets must support the heater at an angle of inclination between 30 and 45 a...

Страница 8: ...s an optional extra by the manufacturer must be fitted to the flue exit this kit connects from the flue outlet to a 5 adaptor The flue fitting is designed to accept either 5 single wall or 5 twin wall...

Страница 9: ...will pull in Safe start checks are carried out automatically and a purge period of approximately 9 seconds will commence At the end of the purge period the ignition sequence will commence The spark ig...

Страница 10: ...e section 10 Figure 10 Replace mains input connector and start the heater Using a suitable screwdriver adjust the pressure regulator if necessary set pressure as stated on data label Switch off the he...

Страница 11: ...emove the combustion fan disconnect the electrical connection from the burner control assembly and remove the fan securing screws to the side of the burner box Figure 14 Figure 15 Remove fan spigot by...

Страница 12: ...the product it is now possible to replace components as follows Injector Figure 18 Remove the four screws securing the burner spigot to the burner box Lift off the burner assembly and gasket checking...

Страница 13: ...eed as follows Figure 23 Figure 24 Disconnect gas fittings disconnect wiring harness from valve Remove rear panel of burner box Remove the two screws securing the gas valve to the panel and two screws...

Страница 14: ...ections Vacuum switch Figure 26 Disconnect the two silicon rubber tubes and the electrical connectors Noting correct orientation Figure 27 Remove the two screws securing the vacuum switch in position...

Страница 15: ...sure 2 Burner nozzle pressure 3 Check live and neutral polarity and a good earth is present Check 1 Check vacuum switch tubes 2 Check emitter tubes air inlet and the flue is not obstructed 3 Check ope...

Страница 16: ...ner head wiring assembly 900225 3 pin mains socket 2135 5 3 pin fan socket 3123 5 Silicone tube 2198 Fan air inlet 201125 Burner orifice plate 201063 08 Injector 201007 24 Vacuum switch 201013 17 Spar...

Страница 17: ...flue pipe 5 46 1 75 6 06 2 He 2 50 6 22 Note 1m of actual flue with two 90 bends gives the minimum equivalent flue height of 0 25m for 100mm diameter flue and 0 62m for 125mm diameter flue The maximu...

Страница 18: ...s again switch off heater and call out a service engineer Note U bend will glow but this is acceptable To switch off Cobra heater 1 Switch off electrical supply to the heater The burner will shut off...

Отзывы: