Ambirad AMBIRAD VISION VSX Series Скачать руководство пользователя страница 9

Doc No. 700015  Page 9 of 36 

 

1.7 Ventilation 

Requirements 

 
AmbiRad VSX tube heaters can be operated as 
flued or unflued appliances in accordance with 
the relevant national requirements in the 

 

 

country of installation. 
 

1.7.1 Unflued Radiant Heater 
 

Radiant tube heaters can be operated as 

 

 

 

 

unflued appliances so that the concentration of 
Carbon Dioxide (CO

2

) at positions where the air 

will be inhaled does not exceed 0.28%. BS EN 
13410 is a guide to achieving this requirement. 
 
If the building air change rate exceeds 1.5 per 
hour or if the heat input is less than 5W/m³, no 
additional ventilation is required. 
 
In addition to the ventilation requirements, 

 

 

consideration  needs  to  be  given  to  the         
possibility of condensation forming on cold 

 

 

surfaces. 
 
It should be noted that the clearance distance 
around the burner increases when the unit is 
operated unflued (see section 1.5). It should be 
ensured that the combustion gases do not   
impinge on any combustible materials. 
 

Mechanical Ventilation 

Mechanical ventilation must be rated at 

 

 

 

 

 

 

minimum 

10m³/h 

per 

kW 

input 

using             

appropriately sized fans and interlocked with 
heaters. 

Natural Ventilation 

BS EN 13410 should be used to size air vents 
to provide adequate ventilation, an example of 
this calculation is given below: 
 
Site Details: 
20°c Internal Operating Temperature 
0°c Outside Air Temperature 
5m between high and low level vents 
 
Following the sizing procedure in BS EN 13410 
gives an air exit velocity of 1.6m/s. This 
equates to a free area vent at both high level 
and low level of 17.36cm²/kW free area. 

 
1.7.2 Flued Radiant Heater 
 

In buildings having an air change rate of less 
than 0.5 per hour, additional mechanical or  
natural ventilation is required. For detailed 

 

 

information, please see BS6896 section 
5.2.2.2.1 
 

Mechanical Ventilation 

Mechanical ventilation must be installed to 

meet a minimum of 0.5 air changes per hour 
using appropriately sized fans and interlocked 
with the heaters. 
 

Natural Ventilation 

Low level ventilation openings with a free area 
of at least 2cm²/kW shall be provided. See    
section 5.2.2.2.2.1. 
 
 

1.8  Flue  and  Combustion  Air  Inlet         
-  Options 
 

Dependent on the type of burner fitted to your 
heater it is possible to have configurations of 
flue and combustion air inlet options to those 
shown overleaf: 

 

• Option 1 

For flued products of combustion and no 
ducted air please refer to Figure 6.a. 

• Option 2 

For ducted air and products of combustion to 
ventilated area please refer to Figure 6.b. 

• Option 3 

For flued products of combustion and ducted 
air via concentric pipe please refer to Figure 
6.c. 
 
 

1.8.1 Important Information 

 
1.8.1.1  Option 1 and 2 

A suitable flue system complying with EN1856-1 
(type T250 N1 D Vm L11040 O50) should be 
used. Flue size 125mm diameter twin wall. 
 
Flue systems can run either vertically or 

 

 

 

 

 

 

 

horizontally up to a 

maximum length of 9.5m 

(including up to 2 x 90° bends plus the terminal). 
The minimum flue length shall be 1m.  
 
The flue system 

must be terminated in a 

 

 

 

vertical position 

and in accordance with the 

British Standard Code of Practice BS 5440: Part 
1 - Installation and maintenance of flues and 
ventilation for gas appliances of rated input not 
exceeding 70kW net (1st, 2nd and 3rd   family 
gases), and the flue system manufacturers 

 

 

instructions as supplied with the flue. 
 

1.8.1.2  Option 3

 

A suitable flue system complying with EN1865-1 
(type T200 P1 W V2 L50050 O00) should be 
used. Flue size 100mm diameter single wall. 
 
The 

maximum flue length 

shall be 9.0m 

(including up to 2 x 90° bends plus the terminal). 
The minimum flue length shall be 1m. 
 

Содержание AMBIRAD VISION VSX Series

Страница 1: ...tallation must be carried out in accordance with the current IEE wiring regulations BS 7671 BS 6896 Industrial Commercial and any other relevant British Standards and Codes of Practice by a quali ed i...

Страница 2: ...ion Natural Ventilation 1 7 2 Flued Radiant Heater Mechanical Ventilation Natural Ventilation 1 8 Flue Combustion Air Inlet 1 8 1 Important Information 1 8 2 Flue Installation 1 8 3 Condensation Consi...

Страница 3: ...See fig 1b Attachment to the heater support lugs should be made by a speed link D shackle or in the case of drop rods a closed formed hook The hanging attachments to overhead steelwork etc must be pur...

Страница 4: ...ned maximum recommended angle of inclination is 15 Shackle method of attachment Pin must be tightened by pliers Drop rod with formed hook note hook or eyebolt must be closed tight 15 max THE HEATER SH...

Страница 5: ...ances MUST be adhered to at all times VSXUT 20 25 30 35 40 45 50 Above Reflector A 100 100 100 Above Burner Heater Outlet B 500 500 500 To the Sides C 1300 1300 1300 Below Tubes D 2300 2500 2500 Horiz...

Страница 6: ...her position in between these angles is acceptable A clearance distance x of min 200mm must be observed to allow side door access Care must be taken to observe the minimum pipe bend diameter minimum 2...

Страница 7: ...Green Yellow Earth Blue Neutral Brown Live It is recommended the heater or group of heaters are controlled by thermostats a time switch and if required manual control switches and a frost thermostat...

Страница 8: ...GREY WHITE FLAME SENSOR IGNITER 8 7 9 11 10 12 1 3 2 4 BLACK PINK WHITE LAMPS ON BURNER GREY YELLOW BLACK GRN YEL BROWN SOLENOID VALVE SWITCH N C N O C GREY EMC FILTER MAINS INPUT L N FAN N L ON MAIN...

Страница 9: ...natural ventilation is required For detailed information please see BS6896 section 5 2 2 2 1 Mechanical Ventilation Mechanical ventilation must be installed to meet a minimum of 0 5 air changes per h...

Страница 10: ...Regulations shown below The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice BS 5440 Part 1 Installation...

Страница 11: ...n K 127mm 5ins to 100mm 4ins Reducer L 127mm 5ins Twin Wall Flue Pipe Ducted air must be used in locations where there is airborne dust or where there is a polluted atmosphere e g Chlorinated Vapours...

Страница 12: ...used in locations where there is airborne dust or where there is a polluted atmosphere e g Chlorinated Vapours Maximum length 9m Minimum diameter 100mm Maximum no of bends 2 Products of combustion to...

Страница 13: ...ere is a polluted atmosphere e g Chlorinated Vapours Maximum length 9m Minimum diameter 100mm Maximum no of bends 2 Maximum flue length 9 0m 125mm Maximum no of bends 2 All flues must terminate vertic...

Страница 14: ...44 0 39 6 4 2 11 6 2 9 450x5927x746 158 0 5 2560 VSX50UT4M 49 5 44 6 4 7 12 8 2 5L 450x7692x746 205 0 5 2560 VSX30UT3M 30 0 27 0 2 9 10 5 2 0 450x5927x746 158 1 0 2507 VSX45UT4M 44 0 39 6 4 2 11 6 2...

Страница 15: ...o complete the tasks laid out in this manual Pozidrive Screwdriver Trestles Leather Faced Gloves Tape Measure Spanner Set 4 5mm Allen keys 2 2 4 Reflectors All reflectors AND canopies must be position...

Страница 16: ...6x 2 3 Identification check list 2x 1x 1x 1x 4x 4x 5x 2x 2x 4x 3x 4x 10x M8 Full Nut 16x 22x 28x No 5 Torque Screw 13x 14x 15x Turbulators 2 2 6 Burner and Heat Exchanger Assembly Slide the burner ass...

Страница 17: ...ide of End Caps if saw horses cannot be located ensure any alternative is sound and can carry the heater weight Methodology To cater for the expansion of the firing leg all U bolts on the firing leg e...

Страница 18: ...n for location length 3 CAUTION SHARP EDGES 2x 3x 3x 5x Working at the opposite ends of the tubes to the burner locate position two couplers so that the socket heads are facing outwards the pre fitted...

Страница 19: ...nd bracket 2 5 3 Reflectors 2x 3x 7 CAUTION SHARP EDGES Slide end reflector so that the innermost slotted holes line up with 1st bracket fixing holes then fix in place using M6 x 35mm pins washers nut...

Страница 20: ...ng outwards 3x 3x 3x 3x 1x 2x 1x 2x 12 13 3x 3x 3x 3x 2x 2x 11 3x 3x 3x 3x 3x 2x 3x 3x 2 5 5 Canopies Remove protective film before starting Slide the outer canopies over the reflectors from the U ben...

Страница 21: ...rofile at the U bend end fix with screws Repeat procedure for cut out canopy end cap again ensuring the flange faces inwards 2 5 6 Canopy End Caps 16 2x 2x 12x 12x CAUTION SHARP EDGES 17 1x 1x 1x 1x 2...

Страница 22: ...700015 Page 22 of 36 2600mm 20kW ONLY 3400mm 25 30KW TURBULATORS 976mm TURBULATOR COUPLER 1365mm 1650mm 50 mm O LAP 50mm O LAP 38mm 150 4047mm REFERENCE 3400mm TUBE Y Z X Z Z W Y Y Figure 7 VSX2M 20...

Страница 23: ...of 36 Figure 8 VSX3M 30 35 40 45 5927mm REFERENCE 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP COUPLER 138mm 5200mm TUBE 1365mm 976mm TURBULATOR 2600mm TURBULATOR 150 2600mm TURBULATOR 1880mm 1650mm Y...

Страница 24: ...90mm REFERENCE 50mm O LAP COUPLER 976mm TURBULATOR 1200mm 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP 50mm O LAP 293mm 1880mm 1880mm 1650mm 150 COUPLER 3400mm TURBULATOR 3400mm TURBULATOR 50kW ONLY 52...

Страница 25: ...Doc No 700015 Page 25 of 36 Figure 10 VSX Heater Breakdown 3 module shown...

Страница 26: ...operation of air pressure switch Leave the instructions with a responsible person These appliances should be commissioned by a qualified engineer 3 1 Tools Required The following tools and equipment...

Страница 27: ...1 Tools Required The following tools and equipment are advisable to complete the tasks laid out in this manual Suitable alternative tools may be used Large Adjustable Spanners or 22 26 27mm Spanners f...

Страница 28: ...he heat exchanger and remove the flexible hose from the burner Step 6 Slacken the set screw on the burner support casting to enable the burner to be removed from the radiant tube Step 7 Remove the bur...

Страница 29: ...pper pot burner head can be replaced ensuring the 5 holes on the outer ring are aligned alongside the probes Step 3 The condition of the igniter assembly can be checked for deterioration However we ad...

Страница 30: ...nd remove any dust with a soft brush Step 6 Remove any dust from fan scroll and from around the motor Step 7 Ensure the impeller rotates freely Step 8 Refit components 4 7 Radiant Tube Servicing Step...

Страница 31: ...the heat exchanger refit 4 9 Reflector Servicing The condition of the reflectors should be noted If necessary the reflectors can be cleaned with a mild detergent This can significantly improve the ef...

Страница 32: ...section 1 10 Injector Item 201284 Ignitor Assembly Part No Description 200988 Pepperpot Head Item 2175 Amber Neon Burner On 2180 Red Neon Mains On 200420 Jet Carrier all except See Section 1 10 Combu...

Страница 33: ...partment NO NO Does the vacuum switch pull in Check 1 Wiring harness plugs 2 Vacuum switch operation 3 Replace fan Is the burner sparking Does the gas valve open Check 1 Burner controller 2 Replace ga...

Страница 34: ...ove Step 5 Fit new burner controller Step 6 Refit HT leads and refit burner controller to wiring harness Step 7 Test product and close access doors 7 2 Air Pressure Switch Replacement Step 1 Disconnec...

Страница 35: ...5 From within the combustion chamber remove the two screws holding the front of the gas valve Step 6 Turning the housing over remove the four screws holding the rear burner plate in position Step 7 O...

Страница 36: ...the heater is cold and mains electric isolated cleaning of the reflectors with a soft cloth and a mild detergent non solvent based cleaners only in water can be undertaken Additional removal of dust f...

Отзывы: