Amana RHA**B2A Series Скачать руководство пользователя страница 6

6

75

60

50

43

37

N/R

N/R

N/R

N/R

N/R

N/R

N/R

N/R

118

95

79

68

59

53

47

N/R

N/R

N/R

N/R

N/R

N/R

188

150

125

107

95

83

75

68

63

58

54

N/R

N/R

301

241

201

172

150

134

120

109

100

93

86

80

75

471

376

314

269

235

209

188

171

157

145

134

125

118

N/R = NOT RECOMMENDED

Wire ampacity and voltage drop calculation based on copper conductors with  75 degree C insulation per
1996 National Electrical Code (NEC)  Conductors in  86 degree F ambient. 
See NEC for ampacity derating for higher ambients.

27.5

30

12.5

15

17.5

20

MAXIMUM ALLOWABLE WIRE LENGTH IN FEET TO LIMIT VOLTAGE DROP TO 2%

10

MINIMUM CIRCUIT AMPACITY OF OUTDOOR UNIT (MCA)

40

32.5

35

37.5

WIRE SIZE 

(AWG)

22.5

25

6

14
12
10

8

TABLE  1

     This table is provided as a guide only.  Wire sizing may be regulated by local codes.

  Local inspection is the final authority on wire sizing.

WARNING

To avoid personal injury or death, open
each valve only until it touches the retainer.
To avoid loss of refrigerant, do not apply
pressure to the retainer.

The outdoor unit is factory charged with enough R-22 for
the matching indoor blower coil or matching A coil plus 25
feet of 3/8 inch liquid line. Add or subtract 0.60 oz. of R-22
per foot of 3/8" liquid line for any difference from 25 feet.
For line sets over 50 feet consult an Amana distributor.

IMPORTANT:  Use only refrigerant which is certified to
meet ARI Standard 700. Used refrigerant may cause
compressor damage, and will void the warranty. (Most
portable machines cannot clean used refrigerant well
enough to meet this ARI Standard.)

IMPORTANT: If adding refrigerant to a system, add only
refrigerant vapor (not liquid) through the suction valve (low
side) on the outdoor unit. Any other practice may cause
compressor damage.

Final Charge Adjustment  -  Cooling Operation

Final  charge adjustment must be performed when the
outdoor temperature is 60°F or higher:

1.

Set the room thermostat to “COOL”.

2.

Set the fan switch to “AUTO”.

3.

Set the temperature control well below room temper-
ature.

4.

Turn the power on.

5.

Let the system run for 15 - 20 minutes, or until
pressures are stabilized.

6.

Measure the high side pressure from the liquid line
service valve port.

7.

Measure the low side pressure from vapor line ser-
vice valve port (for superheat value at outdoor unit).

LIQUID LINE   

SERVICE VALVE

VAPOR LINE

SERVICE VALVE

LOW SIDE    

GAUGE PORT

Figure 4

ID Coil with Expansion Valve:
At stabilized cooling conditions and with an outdoor tem-
perature of 60°F or higher, the system should have from
9°F to 13°F subcooling at the outdoor unit liquid line
service valve. If you have less than 9°F subcooling, add
charge. If you have more than 13°F subcooling, remove
charge.

ID Coil with Orifice:
For a proper superheat reading, measure the refrigerant
pressure and temperature at the outdoor unit  vapor line
service valve. The superheat should be within 3°F of that
shown on the chart on page 8.  If the superheat is higher,
add charge. If the superheat is lower, remove charge.

Содержание RHA**B2A Series

Страница 1: ...ety practices follow them TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 RHA B2A REMOTE HEAT PUMPS Installation Instructions March 1998 2 10845804 A higher standard of comfort Heating Air Conditioning Table of Contents GENERAL 2 Shipping and Handling 2 Location and Clearances 2 Roo...

Страница 2: ...include a vapor barrier The liquid line must be outside of the vapor line s insula tion If part of the liquid line must run through an area that will be hotter than 120 F then that portion of the liquid line must be insulated Avoid burying refrigerant lines If you must bury them first dig the trench so that it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liq...

Страница 3: ...death or injury practice safe handling of refrigerants While these items will not cover every conceivable situa tion they should serve as a useful guide Refrigerants are heavier than air They can push out the oxygen in your lungs or in any enclosed space To avoid possible death or difficulty in breathing Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all r...

Страница 4: ...cylinder of dry nitrogen to the center port on the gauge manifold 3 Open the hand valve a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the manifold gauge Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach 150 psig you may need to further open the hand valve on the nitrogen cylinder Once 150 psig has been reached clos...

Страница 5: ... and handling IV System Start up Preliminary Charge Adjustment IMPORTANT If this unit has a crankcase heater see the wiring diagram or Specification Sheet shipped with unit connect electrical power to the unit for four hours before operating the compressor Failure to do so could result in compressor damage IMPORTANT During all installation and service work follow all regulations of the EPA This sy...

Страница 6: ...igerant may cause compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding refrigerant to a system add only refrigerant vapor not liquid through the suction valve low side on the outdoor unit Any other practice may cause compressor damage Final Charge Adjustment Cooling Operation Final charge adjustm...

Страница 7: ...0 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUPERHEAT O D UNIT OUTDOOR TEMPERATURE DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE 9 0 F I n d o o r 7 0 F I n d o o r 7 5 F I n d o o r 8 0 F I n d o o r 8 5 F I n d o o r ...

Страница 8: ... indoor equip ment If further information is needed see the Remote Heat Pump Service Manual V Defrost System The RHA B2A models are equipped with a time tempera ture type defrost board Defrosting of the OD coil is determined by both coil temperature and compressor run time See the Specification Sheet for factory settings Adjustment can be changed as required There are 30 60 and 90 minute settings ...

Страница 9: ...onal wire s here See BHA TB wiring diagram for details 2 Emergency Heat will stop the compressor but it will not bypass the outdoor thermostat Only the amount of heat controlled by W2 will be energized above the ATK setpoint 3 See notes on page 12 regarding connector GY42 wire and staging of electric heat R W2 G C X RHxEH001 R W1 Y W2 E G C X O R Y W2 E C X O 1 1 ROOM THERMOSTAT 2 6 wires BHA BLOW...

Страница 10: ... INDOOR BHA BLOWER COIL Approved Thermostats are 10636701 10636702 D9807605 D9945804 1213405 1213404 1213403 C ATK Controlling ALL Electric Heat Morning Warmup Could be Slow 4 8 to 28 8KW ROOM THERMOSTAT 6 wires BHA BLOWER COIL 5 wires RH OUTDOOR UNIT R W2 G C X RHxEH003 ATK05 1 1 R Y W2 E C X O R W1 Y E W2 G C X O Notes 1 BHA TB blowers may require additional wire s here See BHA TB wiring diagram...

Страница 11: ... 20 F It is usually desirable to provide a small amount of extra capacity Therefore for this instal lation the outdoor thermostat ATK05 should be set at 25 F This example is for purposes of illustration only Actual selection and application of equipment remains the sole responsibility of the installer If an outdoor thermostat not controlling the first group of electric heaters is to be used 1 Disc...

Страница 12: ...d normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are manual reset switches in the reset position high pressure cutouts relays etc 18 Check the voltage with unit running Does it check within the tolerance of 207 to 253V for 230V or 198 to 228V If using...

Отзывы: