Amana RHA**B2A Series Скачать руководство пользователя страница 2

2

DO locate the unit:

– With the bottom of the unit at least three inches

above the maximum expected snow accumulation
level.

– In accordance with the minimum clearances de-

scribed above.

– To minimize the length of refrigerant piping required.

– To provide adequate service clearances.

– On a level concrete pad (or other sturdy, weather

resistant platform).

– Isolated from the building structure  to avoid trans-

mission of vibrations.

In general, short runs of refrigerant piping are better than
long runs.  Fifty feet is the longest line set allowed with
Amana split system heat pumps.

Locate the unit to provide safe access for future mainte-
nance and service.  If possible, discuss unit location with
the owner before proceeding.

Rooftop Installations Only
Place the unit on a level, weather resistant platform.  Be
sure the roof will support the weight of the unit and
platform.  For approximate unit weight, see the “Specifi-
cation Sheet”.  If in doubt about the adequacy of the roof,
it is your responsibility to contact a qualified architect or
structural engineer before installing the unit.

Application Note
For proper performance, the indoor equipment and duct-
work must be adequate for moving about 400 CFM of
indoor air for every ton of cooling capacity to be installed.
If they are not, modify the ductwork or indoor equipment
accordingly.

I.  Refrigerant Piping

Refrigerant Line Sizing
See unit “Specification Sheet”  for required line sizes.  Be
sure to use the correct size as using smaller vapor lines
can decrease unit performance.  These sizes are suitable
for line lengths of fifty feet or less.  It also assumes that the
indoor coil will not be more than forty feet above or below
the outdoor unit.  Longer runs and greater lifts are not
recommended.

Routing of Refrigerant Lines
All of the vapor line must be insulated.  The insulation
must include a vapor barrier.

The liquid line must be outside of the vapor line’s insula-
tion.

If part of the liquid line must run through an area that will
be hotter than 120°F, then that portion of the liquid line
must be insulated.

Avoid burying refrigerant lines.  If you must bury them, first
dig the trench so that it gradually slopes toward the
compressor (at least 1 inch per 10 feet).  Then, insulate
the liquid and suction lines separately.  Enclose all under-

SAFETY GUIDELINES

1. Allow only qualified, experienced technicians to install

or service this unit.

2. Install the system in accordance with all local codes.

If no local codes exist, follow National Codes (NEC in
the U.S., CEC in Canada).

3. Open the electrical disconnect switch before electri-

cally connecting the unit.

4. Before operating the unit, be certain it is properly

grounded.

5. The unit contains refrigerant gas under pressure.

Avoid puncturing or breaking any tubing.

6. Before operating the unit, complete the refrigerant

connections.

GENERAL

This manual covers only the installation of the remote heat
pump.  For information on accessories, see the unit
“Specification Sheet”.

Shipping and Handling
Check the unit for any shipping damage.  If damage is
found, contact the company where you purchased the
unit.  If no damage is found, carefully remove all shipping
material, and properly dispose of it.

Keep the unit as upright as possible.  Laying the unit on its
side or top could cause equipment damage.

Location and Clearances
This unit is for outdoor installation only.  Refer to Figure     1
for clearances from the sides of the unit to full walls and
other objects.  These clearances will help avoid air recir-
culation.  If installing two or more units at the same
location, allow at least 24 inches between units.

24"

24"

18"

12"

18"

MINIMUM CLEARANCES

SIDE VIEW

TOP VIEW

5'

Figure 1

DO NOT locate the unit:

– Directly under a vent termination for a gas appliance.

– Within 3 feet of a clothes drier vent.

– Where the refreezing of defrost water would create

a hazard.

– Where water may rise into the unit.

Содержание RHA**B2A Series

Страница 1: ...ety practices follow them TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 RHA B2A REMOTE HEAT PUMPS Installation Instructions March 1998 2 10845804 A higher standard of comfort Heating Air Conditioning Table of Contents GENERAL 2 Shipping and Handling 2 Location and Clearances 2 Roo...

Страница 2: ...include a vapor barrier The liquid line must be outside of the vapor line s insula tion If part of the liquid line must run through an area that will be hotter than 120 F then that portion of the liquid line must be insulated Avoid burying refrigerant lines If you must bury them first dig the trench so that it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liq...

Страница 3: ...death or injury practice safe handling of refrigerants While these items will not cover every conceivable situa tion they should serve as a useful guide Refrigerants are heavier than air They can push out the oxygen in your lungs or in any enclosed space To avoid possible death or difficulty in breathing Never sniff a refrigerant Never purge refrigerant into an enclosed room or space In fact all r...

Страница 4: ...cylinder of dry nitrogen to the center port on the gauge manifold 3 Open the hand valve a minimal amount on the line coming from the nitrogen cylinder 4 Open the high pressure valve on the manifold gauge Pressurize the refrigerant lines and the indoor coil to 150 psig 1034 kPA To reach 150 psig you may need to further open the hand valve on the nitrogen cylinder Once 150 psig has been reached clos...

Страница 5: ... and handling IV System Start up Preliminary Charge Adjustment IMPORTANT If this unit has a crankcase heater see the wiring diagram or Specification Sheet shipped with unit connect electrical power to the unit for four hours before operating the compressor Failure to do so could result in compressor damage IMPORTANT During all installation and service work follow all regulations of the EPA This sy...

Страница 6: ...igerant may cause compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding refrigerant to a system add only refrigerant vapor not liquid through the suction valve low side on the outdoor unit Any other practice may cause compressor damage Final Charge Adjustment Cooling Operation Final charge adjustm...

Страница 7: ...0 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUPERHEAT O D UNIT OUTDOOR TEMPERATURE DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE 9 0 F I n d o o r 7 0 F I n d o o r 7 5 F I n d o o r 8 0 F I n d o o r 8 5 F I n d o o r ...

Страница 8: ... indoor equip ment If further information is needed see the Remote Heat Pump Service Manual V Defrost System The RHA B2A models are equipped with a time tempera ture type defrost board Defrosting of the OD coil is determined by both coil temperature and compressor run time See the Specification Sheet for factory settings Adjustment can be changed as required There are 30 60 and 90 minute settings ...

Страница 9: ...onal wire s here See BHA TB wiring diagram for details 2 Emergency Heat will stop the compressor but it will not bypass the outdoor thermostat Only the amount of heat controlled by W2 will be energized above the ATK setpoint 3 See notes on page 12 regarding connector GY42 wire and staging of electric heat R W2 G C X RHxEH001 R W1 Y W2 E G C X O R Y W2 E C X O 1 1 ROOM THERMOSTAT 2 6 wires BHA BLOW...

Страница 10: ... INDOOR BHA BLOWER COIL Approved Thermostats are 10636701 10636702 D9807605 D9945804 1213405 1213404 1213403 C ATK Controlling ALL Electric Heat Morning Warmup Could be Slow 4 8 to 28 8KW ROOM THERMOSTAT 6 wires BHA BLOWER COIL 5 wires RH OUTDOOR UNIT R W2 G C X RHxEH003 ATK05 1 1 R Y W2 E C X O R W1 Y E W2 G C X O Notes 1 BHA TB blowers may require additional wire s here See BHA TB wiring diagram...

Страница 11: ... 20 F It is usually desirable to provide a small amount of extra capacity Therefore for this instal lation the outdoor thermostat ATK05 should be set at 25 F This example is for purposes of illustration only Actual selection and application of equipment remains the sole responsibility of the installer If an outdoor thermostat not controlling the first group of electric heaters is to be used 1 Disc...

Страница 12: ...d normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are manual reset switches in the reset position high pressure cutouts relays etc 18 Check the voltage with unit running Does it check within the tolerance of 207 to 253V for 230V or 198 to 228V If using...

Отзывы: