2

Thermostat Mounting

1. For new construction, select thermostat mounting

location about five feet above the flo , on an inside

wall, out of direct sunlight, away from sources of

radiant heat (lamps, fireplaces, heating and ai

conditioning equipment, etc.), away from windows

or door to the outside, and avoid areas with poor air

circulation. If the motion sensor in the thermostat is to

be used, point the thermostat towards the area where

you are requiring motion sensing. Ensure location is

out of the path of foot traffic where a person mig

accidentally bump into the thermostats and damage

the device.

2. Set flush-mount base extension aside from mountin

baseplate.

3. Remove thermostat from mounting base plate by

gently pulling apart at the bottom of the thermostat

about 1”, and slide thermostat up to release from the

top of the mounting base plate. If mounting thermostat

flush to wall with extension proceed to step 4. I

mounting thermostat recessed into drywall proceed to

step 7, or if mounting thermostat to an electrical box

proceed to step 10.

4. Place flush-mount base extension against the wal

at desired location and mark placement of the top

and bottom mounting holes. Make sure rectangular

opening is on the left side so that when mated with

the mounting base plate the UP arrow is pointing up

on the mounting base plate.

5. If mounting in drywall, drill 7/32” holes, tap plastic

anchors into wall. For other surfaces, drill hole as

required.

6. Screw mounting base plate and flush-moun

base extension assembly to the wall. Proceed to

Connecting HVAC Wires instructions.

7. If mounting thermostat with wiring compartment

recessed into drywall, cut drywall opening 2” wide

by 2 & 7/8” tall in desired location. The flush-moun

base extension may be used as a template. Due care

should be taken if wiring, plumbing or other contents

behind the wall are unknown.

8. Discard flush-mount base extension. Place th

mounting base plate against the wall in the desired

location and mark placement of right and top

mounting holes. Make sure the UP arrow is pointing

up on the mounting base plate.

9. Drill a 7/32” holes and tap plastic anchors into wall.

Screw mounting base plate to wall. Proceed to

Connecting HVAC Wires instructions.

10. If mounting thermostat to one or two gang electrical

box, discard flush-mount base extension. Scre

mounting base plate to electrical box (Screws not

included).

Connecting HVAC Wires 

Thermostat wires (20 gauge minimum field supplied)

can be connected to the thermostat. WARNING, Power 

should be turned off on the unit prior to connecting wires to

prevent damaging the unit transformer by electrical shorts.

1. Route wires through the rectangular opening on the

flush-mount base extension if used, and through th

label in the area marked by a circle on the mounting

base plate.

2. Loosen set screws on wired terminals and insert wires

into the opening.  Tighten set screws (See following

figures)

Do not snap the thermostat onto the mounting base until 

after the thermostat has been configured

RC

Compressor

R

C

Y_Y1

Y2/G2

G_G1

AUX1

AUX2

DOOR_ACC

GND

O/B_W1

W2

Fan (High speed)

Fan (Low speed)

Reversing Valve

Electric Heat

Thermostat

Heat Pump PTAC Wiring

(Set to B)

RC

Compressor

R

C

Y_Y1

Y2/G2

G_G1

AUX1

AUX2

DOOR_ACC

GND

O/B_W1

W2

Fan (High speed)

Fan (Low speed)

Electric Heat

Thermostat

Cooler PTAC Wiring

Содержание PTAC DS02G-H

Страница 1: ...damage personal injury or death WARNING is a registered trademark of Maytag Corporation or its related companies and is used under license All rights reserved As a professional installer you have an o...

Страница 2: ...es instructions 7 If mounting thermostat with wiring compartment recessed into drywall cut drywall opening 2 wide by 2 7 8 tall in desired location The flush moun base extension may be used as a templ...

Страница 3: ...pears Use the or buttons to select o for an O terminal reversing valve energizes on cooling and b for a B terminal reversing valve energizes on heating 6 Press and release the FAN button until HE appe...

Страница 4: ...90 82 db Auto Changeover Deadband C 1 0 2 5 2 2 C 1 8 4 5 4 0 F 1 0 2 5 2 2 CF Display F or C Temperatures Fahrenheit Scale F Celsius Scale C LC Compressor Lockout Minimum 3 minute Compressor Lockout...

Страница 5: ...d stops blinking after 30 seconds The dot should not be displayed if thermostat left the Zigbee network successful Note Once a thermostat has been bound to Zigbee network it must be removed from that...

Страница 6: ...6 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 7: ...7 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 8: ...is a registered trademark of Maytag Corporation or its related companies and is used under license All rights reserved PTAC DIRECT SALES INC 185 S Kimball Ave Suite 130 Southlake TX 76092 877 454 7822...

Отзывы: