Amana PGA**C Скачать руководство пользователя страница 4

4

Refer to the Roof Curb Installation Instructions for proper
curb installation. Curbing must be installed in compliance
with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower
than supply air end.

If using a fork lift, see Figure 1 for location of fork prongs.
Make certain prongs support unit weight.

Fork Lift From
Back Of Unit 

Figure 1

 Rigging

IV. Gas Piping

IMPORTANT NOTE: This unit is factory set to operate on
natural gas at the altitudes shown on the rating plate.

WARNING

To prevent death, personal injury or property
damage when either using propane gas
alone or at higher altitudes, obtain and
install the proper conversion kit(s).  Failure
to do so can result in unsatisfactory
operation and/or equipment damage.  High
altitude kits are for U.S. installations only
and are  not approved for use in Canada.

The rating plate is stamped with the model number, type of
gas and gas input rating. Make sure the unit is equipped to
operate on the type of gas available.

Inlet Gas Pressure

Natural

Min. 5.0" W.C., Max. 10.0" W.C.

Propane

Min. 11.0" W.C., Max. 13.0" W.C.

Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in

Table Above.

Table 1

The minimum supply pressure should not vary from that
shown in the table above because this could prevent the unit
from having dependable ignition. In addition, gas input to the
burners must not exceed the rated input shown on the rating
plate. Overfiring of the unit could result in premature heat
exchanger failure.

HIGH ALTITUDE DERATE  (US. INSTALLATIONS
ONLY)
IMPORTANT NOTE: The gas/electric units will naturally
derate itself with altitude. Do not attempt to increase the
firing rate by changing orifices or increasing the manifold
pressure. This can cause poor combustion and equipment
failure.

At all altitudes, the manifold pressure must be within 0.3
inches W.C. of that listed on the “Specification Sheet” for the
fuel used. At all altitudes and with either fuel, the air tempera-
ture rise must be within the range listed on the unit name-
plate.

Refer to the “Specification Sheet” for kits for conversion
from natural gas to propane gas and for altitude adjust-
ments.

PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory op-
eration or equipment damage due to under firing of equip-
ment, do not undersize the natural/propane gas piping from
the meter/tank to the unit. When sizing a trunk line as shown
in Table 2, include all appliances on that line that could be
operated simultaneously.

The rating plate is stamped with the model number, type of
gas and gas input rating. Make sure the unit is equipped to
operate on the type of gas available.

The gas line installation must comply with local codes, or in
the absence of local codes, with the latest edition of the
National Fuel Gas Code (ANSI Z223.1).

NATURAL GAS CONNECTION

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Length of 

Nominal Black  Pipe Size (inches)

Pipe in Feet

1/2

3/4

1

1  1/4

1  1/2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based 

on 0.60 Specific Gravity Gas)

CFH =

BTUH Furnace Input   
Heating Value of Gas (BTU/Cubic Foot)

Table 2

Содержание PGA**C

Страница 1: ...nslistedinthisInstallationManualshould not supersede existing practices but should be consid ered as supplemental information ATTENTION INSTALLING PERSONNEL PGA C PGB C and PGD C Single Package Gas El...

Страница 2: ...on adjustments alterations service or maintenance when servicing or performingmaintenancetothisunitconsult this manual service manual qualified installer service agency or gas supplier WARNING This pr...

Страница 3: ...tional Fuel Gas Code ANSI Z223 1 and National Standard of Canada CAN CGA 2 3 The heating and cooling capacities of the unit should be greaterthanorequaltothedesignheatingandcoolingloads of the area to...

Страница 4: ...ALLATIONS ONLY IMPORTANT NOTE The gas electric units will naturally derate itself with altitude Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure This...

Страница 5: ...on Installed Ahead Of Gas Valve Reduce coupling 1 2 x 1 8 with 1 8 pipe plug to measure line gas pressure Figure 2 Proper Piping Practice CHECKING THE GAS PIPING CAUTION To prevent personal injury or...

Страница 6: ...edropinlinesbetweenregulators andbetween second stage regulator and the appliance Pipe size required will depend on length of pipe run and total load of all appliances Completeinformationregardingtank...

Страница 7: ...igure 5 V Electrical Wiring LOCATING THE THERMOSTAT Thermostat should be mounted 5 feet above the floor on a vibration free inside wall in a room or a hallway that has good air circulation Movement of...

Страница 8: ...WORK Duct systems and register sizes must be properly designed for the C F M and external static pressure rating of the unit Ductwork should be designed in accordance with the rec ommended methods of...

Страница 9: ...n the return air duct s or return air filter grille s Filters installed external to the unit should be sized in accordance with their manufacturer recommendations A throwaway filter must be sized for...

Страница 10: ...in or near the blower motors Duct covers must be removed before operating unit HEAT ANTICIPATOR SETTING The heat anticipator in the room thermostat must be cor rectlyadjustedtoobtainthepropernumberof...

Страница 11: ...e external to the unit 11 Turn on the electrical power supply to the unit 12 Set the thermostat to desired setting GAS INPUT AND PRESSURES Gas supply pressure and manifold pressure with the burn ers o...

Страница 12: ...or minus 0 3 inches water column from the specified pressure Any major changes in flow should be made by changing the size of the burner orifices The measured input rate to the furnace must not excee...

Страница 13: ...air circulating blower motor condenser motor and the combustion fan motor are permanently lubri cated No additional oiling is required FLAME SENSOR QUALIFIED SERVICER ONLY A drop in the flame sensing...

Страница 14: ...d blue dust may cause orange tips but must not be yellow The flames must extend directly outward from the burner without curling floating or lifting off Figure 17 Check the burner flames for 1 Good ad...

Страница 15: ...vers Compressor Sound Blanket Horizontal Filter Kit Propane Gas Conversion Kit High Altitude Kit Standard on PGA C Table 4 Accessory List FUNCTIONAL PARTS Blower Housing Flame Roll Out Switch Blower M...

Отзывы: