PRODUCT DESIGN

3

Amana PCC Package Cooling Units are designed for out-
door installations only in either residential or light commer-
cial applications.

The connecting ductwork (Supply and Return) can be con-
nected for either horizontal or vertical airflow. In the vertical
application a matching Roof Curb is recommended.

A return air filter must be installed behind the return air grille(s)
or provision must be made for a filter in an accessible loca-
tion within the return air duct. The minimum filter area should
not be less than those sizes listed in the Specification Sec-
tion.  Under no circumstances should the unit be operated
without return air filters.

A 3/4" pipe and external drain trap is provided for removal of
condensate water from the indoor coil.  (Do not reduce the
drain line size).

Refrigerant flow control is achieved by use of restrictor ori-
fices.

The single phase units use permanent split capacitors (PSC)
design compressors.  Starting components are therefore not
required.  A low MFD run capacitor assists the compressor
to start and remains in the circuit during operation.

The outdoor fan and indoor blower motors are single phase
capacitor type motors (PCC60's use ECM motors).

Air for condensing (cooling cycle)  is drawn through the out-
door coil by a propeller fan, and is discharged vertically out
the top of the unit.  The outdoor coil is designed for .0 static.
No additional restriction (ductwork) shall be applied.

Conditioned air is drawn through the filter(s), field installed,
across the coil and back into the conditioned space by the
indoor blower.

All models of PCC  series package units use the Compliant
Scroll compressor, there are a number of design characteris-
tics which are different from the traditional reciprocating com-
pressor.

-

Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant.  NOTE:  Even though the
compressor section of a Scroll compressor is more toler-
ant of liquid refrigerant, continued floodback or flooded
start conditions may wash oil from the bearing surfaces
causing premature bearing failure.

-

These Scroll compressors use white oil which is compat-
ible with 3GS.  3GS oil may be used if additional oil is
required.

-

Operating pressures and amp draws may differ from stan-
dard reciprocating compressors.  This information may
be found in the "Cooling Performance Data" section.

Location and Clearances

36"

Maximum
Overhang

48" Minimum

Overhang

36" Side

Clearance

for Servicing

Recommended

Minimum 36"

Clearance for

Service Required

0" Minimum

Clearance to

Combustibles

Vinyl Coated
Canvas
Connections

  Insulated 
  Return
  Duct

  Insulated 
  Supply
  Duct

24" Clearance
(Condenser End)

In installations where the unit is installed above ground level
and not serviceable from the ground (Example: Roof Top in-
stallations) the installer must provide service platform for ser-
vice person with rails or guards in accordance with local codes
or ordinances or in their absence with the latest edition of the
Uniform Mechanical Code Section 305.

NOTE:  Unit can also use roof curb (and platform for leveling,
where necessary) to utilize bottom discharge.

WARNING

TO PREVENT POSSIBLE PROPERTY DAMAGE, THE UNIT
SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL
RIGGING AND MOVING OPERATIONS.  TO FACILITATE
LIFTING AND MOVING IF A CRANE IS USED, PLACE THE
UNIT IN AN ADEQUATE CABLE SLING.

IMPORTANT:  If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing
the unit.

Refer to Roof curb Installation Instructions for proper curb
installation.  Curbing must be installed in compliance with
the National Roofing Contractors Association Manual.

Содержание PCC24C02E

Страница 1: ...ied person Technical Information MODEL M N Refer to Service Manual RS6300003 for installation op eration and troubleshooting information All safety information must be followed as provided in the Serv...

Страница 2: ...the manufacturing number will change It is very important to use the model and manufacturing numbers at all times when requesting service or parts information IF REPAIRS ARE ATTEMPTED BY UNQUALIFIED P...

Страница 3: ...erent from the traditional reciprocating com pressor Due to their design Scroll compressors are inherently more tolerant of liquid refrigerant NOTE Even though the compressor section of a Scroll compr...

Страница 4: ...K O 2 3 8 BOTTOM DUCT OPENING RETURN 25 9 16 PCC24 36 BOTTOM DUCT OPENING SUPPLY 47 5 32 12 INSIDE 12 INSIDE 12 INSIDE 12 INSIDE 3 3 4 2 7 32 16 1 4 REF 3 13 16 7 1 4 18 5 8 ELECTRICAL 3 4 1 1 4 K O 2...

Страница 5: ...LOAD AMPS 1 3 1 3 1 3 LOCKED ROTOR AMPS 2 0 2 0 2 0 BLADE DIAMETER NUMBER 22 4 22 4 22 4 CFM 2200 2200 2200 FACE AREA SQ FT 10 2 10 2 10 2 NUMBER OF ROWS 1 1 2 FINS PER INCH 20 20 20 HORSEPOWER NO OF...

Страница 6: ...5 1 5 RPM 825 825 FULL LOAD AMPS 1 3 1 3 LOCKED ROTOR AMPS 2 0 2 0 BLADE DIAMETER NUMBER 22 4 22 4 CFM 2200 2200 FACE AREA SQ FT 12 12 NUMBER OF ROWS 2 2 FINS PER INCH 20 20 HORSEPOWER NO OF SPEEDS 3...

Страница 7: ...OAD AMPS 28 9 LOCKED ROTOR AMPS 169 HORSEPOWER 1 3 RPM 1100 FULL LOAD AMPS 2 4 LOCKED ROTOR AMPS 5 8 BLADE DIAMETER NUMBER 22 4 CFM 3000 FACE AREA SQ FT 12 2 NUMBER OF ROWS 2 FINS PER INCH 20 HORSEPOW...

Страница 8: ...WATTS CFM WATTS CFM WATTS 0 2 1540 620 1780 735 2265 1010 0 3 1520 600 1755 705 2160 965 0 4 1495 575 1700 670 2095 925 0 5 1460 555 1640 640 1980 880 0 6 1400 520 1570 600 1885 840 0 7 1335 490 1500...

Страница 9: ...BLOWER PERFORMANCE DATA 9 TEMPERATURE RISE...

Страница 10: ...9 22 5 24 4 26 1 21 3 22 0 23 8 25 5 20 3 20 9 22 6 24 2 18 8 19 3 20 9 22 4 S T 0 84 0 76 0 57 0 37 0 88 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 40 0 96 0 86 0 65 0 42 0 97 0 87 0 66 0 4...

Страница 11: ...HI PR 145 156 165 172 163 175 185 193 185 199 210 219 211 227 240 250 237 255 270 281 262 282 298 311 LO PR 60 64 70 75 64 68 74 79 66 71 77 82 70 74 81 86 73 78 85 90 76 80 88 94 MBh 23 7 24 2 25 3 2...

Страница 12: ...1 5 25 0 25 7 27 9 29 9 23 2 23 8 25 8 27 7 S T 0 82 0 73 0 55 0 36 0 85 0 76 0 57 0 37 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 93 0 83 0 63 0 41 0 94 0 84 0 64 0 41 Delta T 21 19 16 11 21 19 16 11...

Страница 13: ...4 7 15 2 HI PR 155 167 177 184 174 188 198 207 198 213 225 235 226 243 257 268 254 274 289 301 281 302 319 333 LO PR 63 67 73 78 66 71 77 82 69 73 80 85 73 77 84 90 76 81 88 94 79 84 91 97 MBh 29 3 29...

Страница 14: ...7 4 29 7 30 6 33 1 35 5 27 5 28 3 30 7 32 9 S T 0 78 0 70 0 53 0 34 0 81 0 72 0 55 0 35 0 83 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 88 0 79 0 60 0 39 0 89 0 80 0 60 0 39 Delta T 20 18 15 10 20 19 15 11...

Страница 15: ...7 6 18 2 HI PR 154 165 174 182 172 185 196 204 196 211 223 232 223 240 254 265 251 270 285 298 277 299 315 329 LO PR 61 65 71 76 65 69 75 80 67 71 78 83 71 75 82 87 74 79 86 92 77 81 89 95 MBh 34 8 35...

Страница 16: ...7 36 3 37 3 40 4 43 4 33 6 34 6 37 4 40 2 S T 0 79 0 71 0 53 0 34 0 82 0 73 0 55 0 36 0 84 0 75 0 57 0 36 0 86 0 77 0 59 0 38 0 90 0 80 0 61 0 39 0 91 0 81 0 61 0 39 Delta T 20 18 15 10 20 18 15 10 2...

Страница 17: ...1 3 22 0 HI PR 162 175 185 193 182 196 207 216 207 223 236 246 236 254 268 280 266 286 302 315 294 316 334 348 LO PR 63 67 73 77 66 70 77 82 69 73 80 85 72 77 84 89 76 80 88 93 78 83 91 97 MBh 42 5 43...

Страница 18: ...5 42 5 43 7 47 3 50 8 39 4 40 5 43 9 47 1 S T 0 76 0 68 0 51 0 33 0 79 0 71 0 53 0 34 0 81 0 72 0 55 0 35 0 83 0 75 0 56 0 36 0 87 0 77 0 59 0 38 0 87 0 78 0 59 0 38 Delta T 21 19 16 11 21 20 16 11 2...

Страница 19: ...3 3 24 1 HI PR 164 176 186 194 184 198 209 218 209 225 237 248 238 256 270 282 268 288 304 317 296 318 336 350 LO PR 60 64 69 74 63 67 73 78 66 70 76 81 69 73 80 85 72 77 84 89 75 79 87 92 MBh 49 8 50...

Страница 20: ...4 0 50 9 52 4 56 7 60 8 47 1 48 5 52 5 56 3 S T 0 75 0 67 0 51 0 33 0 78 0 70 0 53 0 34 0 80 0 71 0 54 0 35 0 82 0 74 0 56 0 36 0 85 0 76 0 58 0 37 0 86 0 77 0 58 0 38 Delta T 21 19 16 11 21 19 16 11...

Страница 21: ...9 3 30 4 HI PR 177 190 201 209 198 213 225 235 225 242 256 267 257 276 292 304 289 311 328 342 319 343 362 378 LO PR 56 60 66 70 60 63 69 74 62 66 72 77 65 69 76 81 68 73 79 84 71 75 82 87 MBh 59 6 60...

Страница 22: ...ature drop T Low and high side pressures and power will not change 2 As indoor CFM decreases a slight increase will occur in indoor temperature drop T A slight decrease will occur in low and high side...

Страница 23: ...BU 23 USE COPPER CONDUCTORS ONLY 75 C MIN COMMON HI MED HI MED LOW LOW 3 2 1 6 5 9 8 7 4 VIEW A A A A G W O Y R C ALTERNATE UNIT POWER REFRIGERANT LEADS MAY BE USED WITH ELECTRIC HEATER ACCESSORIES S...

Страница 24: ...31 RD 27 BU 8 VT 14 BU 9 BU 8 YL BK RD 27 RD 31 VT 20 RD 10 BU 23 RD 31 BK 26 VT 18 BU 23 USE COPPER CONDUCTORS ONLY 75 C MIN COMMON HI MED LOW 3 2 1 6 5 9 8 7 4 VIEW A A A A G W O Y R C ALTERNATE UNI...

Страница 25: ...PIN 7 PIN 8 PIN 9 GY 70 TO HEATER KIT BU 34 RD 13 BR 21 YL 27 COM FAN HERM CAPACITOR YL 12 BK 27 BR 11 GND L2 T2 L1 T1 W1 G E C R W O Y 24V COMMON CAP L2 START CAP 5 2 1 START RELAY VT 7 RD 6 BU 9 BU...

Отзывы: