![Amana PCC24C02E Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/amana/pcc24c02e/pcc24c02e_technical-information_2916129016.webp)
16
COOLING PERFORMANCE DA
T
A
MODEL: PCC42C02E
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Outdoor Ambient Temperature
65
75
85
95
105
115
Entering Indoor Wet Bulb Temperature
IDB*
Airflow
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
MBh
40.4
41.8
45.8
-
39.4
40.9
44.8
-
38.5
39.9
43.7
-
37.5
38.9
42.6
-
35.7
37.0
40.5
-
33.0
34.2
37.5
-
S/T
0.69
0.58
0.40
-
0.72
0.60
0.42
-
0.74
0.62
0.43
-
0.76
0.64
0.44
-
0.79
0.66
0.46
-
0.80
0.67
0.46
-
Delta T
17
15
11
-
17
15
11
-
17
15
11
-
18
15
12
-
17
15
11
-
16
14
11
-
1500
KW
3.25
3.32
3.42
-
3.49
3.57
3.68
-
3.71
3.78
3.90
-
3.89
3.98
4.10
-
4.05
4.14
4.27
-
4.19
4.28
4.42
-
AMPS
15.0
15.3
15.7
-
16.0
16.3
16.8
-
17.2
17.5
18.0
-
18.2
18.6
19.1
-
19.2
19.6
20.2
-
20.2
20.7
21.3
-
HI PR
162
175
185
-
182
196
207
-
207
223
236
-
236
254
268
-
266
286
302
-
294
316
334
-
LO PR
63
67
73
-
66
70
77
-
69
73
80
-
72
77
84
-
76
80
88
-
78
83
91
-
MBh
40.0
41.4
45.4
-
39.0
40.5
44.3
-
38.1
39.5
43.3
-
37.2
38.5
42.2
-
35.3
36.6
40.1
-
32.7
33.9
37.1
-
S/T
0.68
0.57
0.39
-
0.70
0.59
0.41
-
0.72
0.60
0.42
-
0.75
0.62
0.43
-
0.77
0.65
0.45
-
0.78
0.65
0.45
-
Delta T
18
15
12
-
18
16
12
-
18
16
12
-
18
16
12
-
18
16
12
-
17
15
11
-
70
1400
KW
3.25
3.31
3.41
-
3.49
3.56
3.67
-
3.70
3.78
3.89
-
3.88
3.97
4.09
-
4.04
4.13
4.26
-
4.18
4.27
4.41
-
AMPS
14.9
15.2
15.6
-
15.9
16.3
16.7
-
17.1
17.5
18.0
-
18.1
18.5
19.1
-
19.2
19.6
20.2
-
20.2
20.6
21.2
-
HI PR
162
174
184
-
182
196
207
-
207
222
235
-
235
253
268
-
265
285
301
-
293
315
333
-
LO PR
62
66
72
-
66
70
76
-
68
73
79
-
72
76
83
-
75
80
88
-
78
83
91
-
MBh
39.4
40.8
44.7
-
38.4
39.8
43.7
-
37.5
38.9
42.6
-
36.6
37.9
41.6
-
34.8
36.1
39.5
-
32.2
33.4
36.6
-
S/T
0.66
0.55
0.38
-
0.68
0.57
0.39
-
0.70
0.58
0.40
-
0.72
0.60
0.42
-
0.75
0.62
0.43
-
0.75
0.63
0.44
-
Delta T
18
16
12
-
18
16
12
-
19
16
12
-
19
16
12
-
18
16
12
-
17
15
11
-
1300
KW
3.21
3.27
3.37
-
3.44
3.51
3.62
-
3.65
3.72
3.84
-
3.83
3.91
4.04
-
3.99
4.07
4.20
-
4.12
4.21
4.35
-
AMPS
14.7
15.0
15.4
-
15.7
16.1
16.5
-
16.9
17.2
17.7
-
17.9
18.3
18.8
-
18.9
19.3
19.9
-
19.9
20.3
20.9
-
HI PR
159
171
181
-
179
192
203
-
203
219
231
-
231
249
263
-
260
280
296
-
288
310
327
-
LO PR
61
65
71
-
65
69
75
-
67
72
78
-
71
75
82
-
74
79
86
-
77
81
89
-
MBh
41.0
42.3
45.7
49.1
40.1
41.3
44.7
47.9
39.1
40.3
43.6
46.8
38.2
39.3
42.5
45.7
36.3
37.3
40.4
43.4
33.6
34.6
37.4
40.2
S/T
0.79
0.71
0.53
0.34
0.82
0.73
0.55
0.36
0.84
0.75
0.57
0.36
0.86
0.77
0.59
0.38
0.90
0.80
0.61
0.39
0.91
0.81
0.61
0.39
Delta T
20
18
15
10
20
18
15
10
20
19
15
10
20
19
15
11
20
18
15
10
19
17
14
10
1500
KW
3.28
3.35
3.45
3.55
3.52
3.60
3.71
3.82
3.74
3.81
3.93
4.06
3.92
4.01
4.14
4.27
4.09
4.17
4.31
4.45
4.22
4.32
4.46
4.60
AMPS
15.1
15.4
15.8
16.3
16.1
16.4
16.9
17.5
17.3
17.7
18.2
18.8
18.3
18.7
19.3
19.9
19.4
19.8
20.4
21.1
20.4
20.8
21.5
22.2
HI PR
164
177
187
195
184
198
209
218
209
225
238
248
239
257
271
283
268
289
305
318
297
319
337
351
LO PR
63
67
73
78
67
71
77
83
69
74
81
86
73
77
85
90
76
81
89
94
79
84
92
98
MBh
40.6
41.8
45.3
48.6
39.7
40.9
44.2
47.5
38.7
39.9
43.2
46.3
37.8
38.9
42.1
45.2
35.9
37.0
40.0
43.0
33.3
34.2
37.1
39.8
S/T
0.77
0.69
0.52
0.34
0.80
0.72
0.54
0.35
0.82
0.73
0.56
0.36
0.85
0.76
0.57
0.37
0.88
0.79
0.60
0.38
0.89
0.79
0.60
0.39
Delta T
21
19
16
11
21
19
16
11
21
19
16
11
21
19
16
11
21
19
16
11
19
18
15
10
75
1400
KW
3.27
3.34
3.44
3.55
3.51
3.59
3.70
3.81
3.73
3.81
3.93
4.05
3.92
4.00
4.13
4.26
4.08
4.16
4.30
4.44
4.21
4.30
4.44
4.59
AMPS
15.0
15.3
15.8
16.3
16.1
16.4
16.9
17.4
17.3
17.6
18.1
18.7
18.3
18.7
19.2
19.9
19.3
19.7
20.3
21.0
20.3
20.8
21.4
22.1
HI PR
164
176
186
194
184
198
209
218
209
225
237
248
238
256
270
282
268
288
304
317
296
318
336
350
LO PR
63
67
73
78
67
71
77
82
69
74
80
86
73
77
84
90
76
81
88
94
79
84
91
97
MBh
40.0
41.2
44.6
47.9
39.1
40.3
43.6
46.8
38.2
39.3
42.5
45.6
37.2
38.3
41.5
44.5
35.4
36.4
39.4
42.3
32.8
33.7
36.5
39.2
S/T
0.75
0.67
0.50
0.32
0.77
0.69
0.52
0.34
0.79
0.71
0.54
0.35
0.82
0.73
0.55
0.36
0.85
0.76
0.57
0.37
0.86
0.77
0.58
0.37
Delta T
21
19
16
11
21
20
16
11
21
20
16
11
22
20
16
11
21
20
16
11
20
18
15
10
1300
KW
3.23
3.30
3.40
3.50
3.47
3.54
3.65
3.76
3.68
3.75
3.87
4.00
3.86
3.94
4.07
4.20
4.02
4.11
4.24
4.38
4.15
4.24
4.38
4.53
AMPS
14.8
15.1
15.6
16.1
15.9
16.2
16.6
17.2
17.0
17.4
17.9
18.5
18.0
18.4
19.0
19.6
19.1
19.5
20.0
20.7
20.1
20.5
21.1
21.8
HI PR
161
173
183
191
180
194
205
214
205
221
233
243
234
252
266
277
263
283
299
312
291
313
330
344
LO PR
62
66
72
77
65
70
76
81
68
72
79
84
71
76
83
88
75
80
87
93
77
82
90
96
* Entering Indoor Dry Bulb Temperature
NOTE: Shaded area is ARI Rating Conditions
Содержание PCC24C02E