2

16 3/4"

426 mm

26"

661 mm

15 3/4"

401 mm

Figure 1

Wall Sleeve Dimensions

Inside Wall

Lintels

1" Min.

1" Min.

5" Min.

Outside Wall

6"

6"

Ceiling

24"

Min.

Figure 2

Minimum Unit Clearances

1

5

 1

3

/1

6

"

4

0

1

.6

 m

m

M

in

im

u

m

Finished Floor

5"

Figure 3

Minimum Wall Opening Dimensions

Preinstallation Considerations

Before proceeding with the sleeve installation, ensure the
following guidelines for locating the wall opening and sleeve
are met:

The wall opening must be the correct size.  See Figure
1 for wall sleeve dimensions and Figure 3 for minimum
wall opening size.

The wall sleeve must be installed with a 5” minimum
clearance to the floor and 1 1/2” to adjacent walls.  See
Figure 2 for minimum projections of the sleeve into and
out of the room.

If installed in a concrete or masonry wall, a lintel must
be provided in the wall opening for support.  

Do not use

the wall sleeve as a lintel. 

 If the wall is less than 8”

thick or of hollow construction, an alternate means of
support for the sleeve must be provided.  See Figure 4
for a typical lintel construction.

Wood
Frame

Lintel

Figure 4

Framing with Lintel

When installed in the opening, the wall sleeve must be
level from side to side and sloped one quarter bubble
front to back.  DO NOT SLOPE THE WALL SLEEVE
TOWARD THE ROOM.  See Figure 5.

1/4 Bubble Lower

Front to Back

Level

Rail

F

lashing

Figure 5

Sleeve Installation

Waterproof Barrier