background image

9

4-1/2"

47-9/16"

7-1/2"

4-1/16 DIA.

POWER THRU

THE CURB

RETURN

19-3/8

31-3/8

LOW VOLTAGE

ENTRANCE

HIGH VOLTAGE ENTRANCE

(REMOVE PLUG)

electrical entrance and thru curb

(bottom view of unit) 

Low Voltage Control Wiring 

1.  A 24V thermostat must be installed for unit operation.

2.  Locate thermostat or remote sensor in the 

conditioned space where it will sense average 

temperature. Do not locate the device where it may 

be directly exposed to supply air, sunlight or other 

sources of heat. Follow installation instructions 

packaged with the thermostat.

3.  Use #18 AWG wire for 24V control wiring runs not 

exceeding 75 feet. Use #16 AWG wire for 24V 

control wiring runs not exceeding 125 feet. Use #14 

AWG wire for 24V control wiring runs not exceeding 

200 feet. Low voltage wiring may be National 

Electrical Code (NEC) Class 2 where permitted by 

local codes.

4.  Route thermostat wires from sub-base terminals 

to the unit. Control wiring should enter through the 

condenser panel opening or through curb indicated 

in “Electrical Entrance” figure. Connect thermostat 

and any accessory wiring to low voltage terminal 

block TB1 in the main control box.

NOTE:  Field-supplied conduit may need to be 

installed depending on unit/curb configuration. 

Use #18 AWG solid conductor wire whenever 

connecting thermostat wires to terminals on 

sub-base. DO NOT use larger than #18 AWG wire. 

A transition to #18 AWG wire may be required 

before entering thermostat sub-base.

 

NOTE: Refer to unit wiring diagrams for 

thermostat or remote sensor connections.

CIRCULATING AIR AND FILTERS

Ductwork

The supply duct from the unit through a wall may be 

installed without clearance. However, minimum unit 

clearances must be maintained (see “Clearances” section).  

The supply duct should be provided with an access panel 

large enough to inspect the air chamber downstream of 

the heat exchanger.  A cover should be tightly attached to 

prevent air leaks.

Ductwork dimensions are shown in the roof curb 

installation manual.

If desired, supply and return duct connections to the unit 

may be made with flexible connections to reduce possible 

unit operating sound transmission.

CONDENSATE DRAIN CONNECTION

Condensate Drain Connection

A 3/4” female NPT drain connection is supplied on the 

end of the unit and bottom of the drain pan for condensate 

piping.  An external trap must be installed for proper 

condensate drainage. Hand tighten drain fitting to the drain 

connection.

DRAIN

CONNECTION

UNIT

2" MINIMUM

FLEXIBLE

TUBING-HOSE

OR PIPE

3" MINIMUM

A POSITIVE LIQUID

SEAL IS REQUIRED

drain connection 

Install condensate drain trap as shown. Use 3/4” drain line 

and fittings or larger. Do not operate without trap. 

Horizontal Drain 

Drainage of condensate directly onto the roof may be 

acceptable; refer to local code. It is recommended that a 

small drip pad of either stone, mortar, wood or metal be 

provided to prevent any possible damage to the roof. 

Vertical Drain

To use the bottom drain connection, remove the drain plug 

from the bottom connection and install it in the horizontal 

connection.

Cleaning

Due to the fact that drain pans in any air conditioning 

unit will have some moisture in them, algae and fungus 

will grow due to airborne bacteria and spores. Periodic 

cleaning is necessary to prevent this build-up from plugging 

the drain.

Содержание M Series

Страница 1: ...g to install adjust service or repair the equipment specified in this manual without proper training may result in product damage property damage personal injury or death WARNING INDEX ReplacementParts 2 Safety Instructions 2 GeneralInformation 3 Unit Location 4 Clearances 5 Roof Curb Post Installation Checks 5 Roof Top Duct Connections 5 RiggingDetails 6 Electrical Wiring 7 Circulating Air And Fi...

Страница 2: ...e place for future reference CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use any device that is not design certified by daikin for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may resul...

Страница 3: ...here applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services supply and return duct connections and drain connections ...

Страница 4: ... Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local codes Consult a structural engineer to determine the weight capabilities of the roof The unit may be installed directly on wood floors or on Class A Class B or Class C roof covering material To avoi...

Страница 5: ...CES Unit Clearances In situations that have multiple units a 36 minimum clearance is required between the condenser coils Adequate clearance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and condenser a...

Страница 6: ...h the following bullet points must be observed when installing the unit Unit must be lifted by the four lifting holes located at the base frame corners Lifting cables should be attached to the unit with shackles The distance between the crane hook and the top of the unit must not be less than 60 Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables Spreader ...

Страница 7: ... present Failure to do so may cause property damage personal injury or death WARNING HIGH VOLTAGE To avoid personal injury or death due to electrical shock do not tamper with factory wiring The interanl power and control wiring of these units are factory installed and have been thoroughly tested prior to shipment Contact your local representative if assistance is required CAUTION Conduit and fitti...

Страница 8: ...ovided for this purpose Do not use the ground lug for connecting a neutral conductor Connect power wiring to the electrical power block located within the main control box Control Box control box Connections note depending on the options installed the location of the components may vary in some models WARNING Failure of unit due to operation on improper line voltage or with excessive phase unbalan...

Страница 9: ...ILTERS Ductwork The supply duct from the unit through a wall may be installed without clearance However minimum unit clearances must be maintained see Clearances section The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks Ductwork dimensions are shown in the roof cur...

Страница 10: ...are not covered under the warranty After the machines are used for temporary heating or cooling inspect the coils fans and motors for unacceptable levels of construction dust and dirt and install new filters Contractor Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instructions All therm...

Страница 11: ...er speed setting than the G Y1 and W1 speed setting If Electric Heater kit is installed use the red wire provided with the literature kit to jumper terminal TB1 W1 to an unoccupied speed tap that satisfies the minimum airflow required for the heater kit This must be a different tap than Y2 is connected to Refer to Appendix D for minimum required airflow for electric heaters Note On Heat Pump units...

Страница 12: ...running with the reversing valve in the deenergized heating position After giving the unit time to settle out make sure the unit is supplying heated air Note If the outdoor ambient is above 80 F the unit may trip on its high pressure cut out when on heating The compressor should stop The heating cycle must be thoroughly checked so postpone the test to another day when conditions are more suitable ...

Страница 13: ... to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45 F It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump such as a compressor or refrigerant leak etc Since the temperature of the refrigerant in the outdoor coil on the heating cycle ...

Страница 14: ...fficiency or equipment damage due to dust and lint build up on internal parts never operate unit without an air filter installed in the return air system Every application may require a different frequency of replacement of dirty filters Filters must be replaced at least every three 3 months during operating seasons Dirty filters are the most common cause of inadequate heating or cooling performan...

Страница 15: ...15 Wiring Example Electric Heat Wiring Example ...

Страница 16: ...80 0 8 1960 1045 0 86 0 2 2189 902 0 81 0 2 2234 960 0 86 0 4 2119 943 0 84 0 4 2162 1003 0 90 0 6 2059 979 0 88 0 6 2101 1042 0 93 0 8 2012 1009 0 90 0 8 2053 1073 0 96 0 2 2254 923 0 88 0 2 2300 982 0 93 0 4 2178 964 0 92 0 4 2222 1025 0 98 0 6 2127 997 0 95 0 6 2170 1061 1 01 0 8 2078 1029 0 98 0 8 2120 1095 1 04 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommende...

Страница 17: ...25 7 2 6 5 119 129 125 150 134 148 150 150 7 2 6 5 142 155 150 175 Power Supply Model Number Electrical Rating Compressor Outdoor Fan Motor Indoor Fan Motor Optional Electric Heat Optional Powered Convienience Outlet FLA Optional Power Exhaust FLA 6 9 1 0 3 3 5 Direct Drive Standard Static 1 APH1660M 208 230 1 60 1 26 9 152 9 EH 1S15 11 3 15 0 54 2 62 5 EH 1S20 15 0 20 0 72 2 83 3 EH 1S05 3 76 5 0...

Страница 18: ...URB LOCATION EMBOSS FOR THRU THE BASE UTILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A 47 5 8 73 3 8 5 6 3 16 7 3 8 SUPPLY 12 X 17 RETURN 11 X 25 Model Dim A 5 Ton Heat Pump 43 1 2 ...

Страница 19: ...Electric Heater Heater Type X Staged S SCR modulating Voltage 1 208 230 1 60 Single phase 60 Hz Chassis S Small Kilowatt 5 5 kW 10 10 kW 15 15 kW 18 18 KW 20 20 kW 30 30 kW EH S05 5 1500 EH S10 10 1500 EH S15 15 1500 EH S20 20 1550 2500 MAXIMUM SCFM UNIT HEATER KIT MODEL NUMBER APH1660M kW MINIMUM SCFM ...

Страница 20: ...CE INSTALLED NOTES 4 3 2 1 5 6 BLACK BLUE BLUE WITH PINK STRIPE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW YELLOW WITH PINK STRIPE BK BL BL PK BR GR GY OR PK PU RD TN WH YL YL PK HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND FIELD WIRING FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE EARTH GROUND COMPONENT LEGEND 12 11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7...

Страница 21: ...21 ...

Страница 22: ...22 ...

Страница 23: ...23 THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Страница 24: ...he QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by ...

Отзывы: